Integrated voltage sensing option 

INSTALLATION AND OPERATION INSTRUCTIONS

   MN280103EN   March 2023   www.eaton.com

Verify correct ground of the NOVA NX-STS recloser and 

control prior to making any high-voltage connections and 

before high-potential testing. A proper ground connection 

consists of a good electrical ground connection to the surge 

ground connector located on the mechanism housing. 

Provide a good electrical ground connection to the control 

cabinet ground.

ote: 

N

Poor grounding of the mechanism housing may result 

in the presence of high voltage on the mechanism 

housing associated with the high-voltage resistor 

connections used with voltage sensing options 

(source and/or load-side voltage sensors).

 CAUTION

HAZARDOUS VOLTAGE. DO NOT TOUCH THE RECEPTACLE 

CONNECTIONS OF THE CONTROL/VOLTAGE-SENSING CABLE. 

IF THE RECLOSER IS ENERGIZED AND THE CONTROL/VOLTAGE-

SENSING CABLE IS DISCONNECTED FROM THE RECLOSER OR THE 

CONTROL, A VOLTAGE CLAMPED AT 250 VAC WILL BE PRESENT AT 

THE RECEPTACLE. CONTACT WITH THIS VOLTAGE CAN RESULT IN 

PERSONAL INJURY.

The recloser utilizes a 37-pin control cable to carry the 

source and integrated load-side voltage-sensing signals 

from the recloser to the control. Additional voltage-sensing 

cables are not required when using the voltage-sensing 

feature for source and load. There are no additional custom 

connections required.

NOTICE

EQUIPMENT MISOPERATION. VERIFY ALL CONNECTOR PINS 

AND BOTH MATING INTERFACE SURFACES ARE CLEAN AND 

DRY BEFORE CONNECTING CABLES. VOLTAGE-SENSING ERRORS 

CAN RESULT FROM CONTAMINATION. FAILURE TO COMPLY CAN 

RESULT IN CONTROL AND RECLOSER MISOPERATION.

The electrical connectors of the recloser, control, and cable 

must be clean and dry. Contaminated surfaces may be 

cleaned with denatured alcohol and wet connector surfaces 

may be dried with a heat gun. Dry surfaces are particularly 

important for the integrated voltage sensor connections. 

The accuracy of the sensors can be influenced by moisture 

contamination.
Connect control and power cables to the control. Verify that 

the proper cable/receptacle connections are made. Improper 

cable connections can result in damage to the recloser  

and/or control.
Complete the control programming before making the 

high-voltage line connections. See the Recloser Operation 

section on page 10.
When the NOVA NX-STS recloser is equipped with three 

or six integrated voltage sensors, then the Form 7 control 

must have LEA selected in the drop-down menu for each 

source/load bushing in the System Configuration screen. 

The Form 7 control will automatically apply the correct  

PT ratio and phase angle adjustment automatically based 

upon control cable length entered. Refer to 

Figure 12

  

for reference.
If potential transformers (PTs) are used for voltage sensing, 

then select either wye or delta connection type in the 

System Configuration screen with appropriate PT ratio and 

phase angle adjustment values entered. Refer to 

Service 

Information MN280095EN Form 7 Microprocessor Based 

Pole Mount Recloser Control Installation and Operation 

Instructions

 for more information on installing the  

Form 7 control.

Содержание Cooper Power NOVA NX-STS

Страница 1: ...NOVA NX STS single tank triple single electronically controlled recloser installation and operation instructions Reclosers MN280103EN Effective March 2023 New Issue COOPER POWER SERIES...

Страница 2: ...A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS...

Страница 3: ...2 DIMENSIONS 3 INSTALLATION PROCEDURE 7 Removing recloser from service 9 RECLOSER OPERATION 10 Vacuum interrupter 10 Mechanism tripping and closing 10 Electronic control 11 Manual operation of energi...

Страница 4: ...nts WARNING INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH IF NOT AVOIDED COULD RESULT IN DEATH OR SERIOUS INJURY CAUTION INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH IF NOT AVOIDED MAY RESULT...

Страница 5: ...for damage incurred during shipment If damage is discovered file a claim with the carrier immediately Handling and storage Be careful during handling and storage of the NOVA NX STS recloser to minimi...

Страница 6: ...32 5 41 6 32 5 41 6 32 5 32 5 Rated duration of short circuit s 3 3 3 3 3 3 Rated short circuit breaking current kA sym 12 5 16 12 5 16 12 5 12 5 Rated symmetrical short circuit making current kA sym...

Страница 7: ...110 kV BIL inches mm 15 kV 125 kV BIL inches mm 27 kV 125 kV BIL inches mm 27 kV 150 kV BIL inches mm 38 kV 170 kV BIL inches mm Terminal to terminal 41 40 1052 0 41 40 1052 0 41 40 1052 0 41 40 1052...

Страница 8: ...0 38 0 170 kV BIL 58 20 1478 0 27 40 696 0 ote N All dimensions are in inches mm Dimensions shown are approximate 36 59 929 0 36 59 929 0 47 69 1211 0 A 15 24 387 0 42 87 1089 0 15 50 394 0 15 50 394...

Страница 9: ...s mm Dimensions shown are approximate Ground lug Grounding connection 0 50 mounting bolts 3 for outboard mounting 3 for inboard mounting 5 94 151 0 29 88 759 0 15 54 395 0 5 38 137 0 29 88 759 0 15 54...

Страница 10: ...8 70 1999 0 Dry 81 10 2060 0 ote N All dimensions are in inches mm Dimensions shown are approximate B B 28 13 715 0 28 18 716 0 29 34 745 0 21 99 559 0 14 23 361 0 Center of gravity for reference only...

Страница 11: ...ic condition of the recloser or the vacuum integrity of the interrupter WARNING FALLING EQUIPMENT USE THE LIFTING LUGS PROVIDED AND FOLLOW ALL LOCALLY APPROVED SAFETY PRACTICES WHEN LIFTING AND MOUNTI...

Страница 12: ...TO COMPLY COULD CAUSE SEVERE INJURY OR DEATH ote N Control is interlocked such that during normal operation voltage cannot appear unless correct 52a b status is reported by the recloser To ensure pro...

Страница 13: ...ED ALWAYS ESTABLISH A VISIBLE DISCONNECT FAILURE TO FOLLOW PROPER SAFETY PRACTICES CAN RESULT IN CONTACT WITH HIGH VOLTAGE WHICH WILL CAUSE DEATH OR SEVERE PERSONAL INJURY 1 Block ground tripping via...

Страница 14: ...o the Form 7 recloser control The recloser responds to trip and close commands from the control per the settings programmed in the control Refer to Service Information MN280095EN Form 7 Microprocessor...

Страница 15: ...the main contacts of the recloser Contact position is indicated by the OPEN flag of the contact position indicator located on the bottom of the recloser The yellow operating handle will remain down in...

Страница 16: ...NG HAZARDOUS VOLTAGE IF TERMINAL CONNECTIONS ARE REVERSED VOLTAGE SENSING MAY INDICATE ERRONEOUS VOLTAGES WHEN THE CONTACTS ARE OPEN DO NOT RELY ON VOLTAGE SENSING TO ENSURE THAT THE VOLTAGE IS ZERO A...

Страница 17: ...RFACES ARE CLEAN AND DRY BEFORE CONNECTING CABLES VOLTAGE SENSING ERRORS CAN RESULT FROM CONTAMINATION FAILURE TO COMPLY CAN RESULT IN CONTROL AND RECLOSER MISOPERATION The electrical connectors of th...

Страница 18: ...ION HAZARDOUS VOLTAGE DO NOT TOUCH THE RECEPTACLE CONNECTIONS OF THE CONTROL VOLTAGE SENSING CABLE IF THE RECLOSER IS ENERGIZED AND THE CONTROL VOLTAGE SENSING CABLE IS DISCONNECTED FROM THE RECLOSER...

Страница 19: ...ounting hanger Pole mounting accessory One pole mounting hanger which allows a variety of add on components to be mounted such as arresters and PTs dry or oil type is available for pole mount installa...

Страница 20: ...full rated ambient temperature range of the recloser and control The accuracy for this system applies when the following conditions are met Voltage range is greater than 50 to 100 of the rated maximum...

Страница 21: ...THE SWITCHGEAR APPARATUS AND CONTROL AND HIGH VOLTAGE TRANSFORMER MUST BE IN A TEST CAGE OR SIMILAR PROTECTED AREA TO PREVENT ACCIDENTAL CONTACT WITH THE HIGH VOLTAGE PARTS SOLIDLY GROUND ALL EQUIPMEN...

Страница 22: ...ply test voltage to terminals 1 3 and 5 for 60 seconds 9 The recloser should withstand the test voltage for 60 seconds Withstand test results The high potential withstand tests provide information on...

Страница 23: ...for damage Check the module surface and major and minor sheds for cracks holes and major chips If damage is present the module must be replaced Contact your Eaton representative 7 If no damage is fou...

Страница 24: ...rip Alt COIL Vendor Specific Close Trip COIL Close Trip Aux 52a Aux 52b Aux COM 69b combined SWITCH COM 52a 52b 69a Source VS Load VS VS Neutral PRESENT ONLY IF AUX SWITCH IS ORDERED THESE SIGNALS TER...

Страница 25: ...re 17 for typical configuration Phase C Internal Wiring See Figure 17 for typical configuration E SHIELD f VS Shield C CT C M Coil PhC Standard Interface Close Trip P Coil PhC Close Trip Y 52a PhC b 5...

Страница 26: ...S MN280103EN March 2023 www eaton com Figure 19 Auxiliary switch accessory wiring Phase A Phase B Phase C B1 F5 F3 F4 Aux 52a Aux 52b Aux Sw Com Aux 52a Aux 52b Aux Sw Com Customer connection B1 F5 F3...

Страница 27: ...23 Service information INSTALLATION AND OPERATION INSTRUCTIONS MN280103EN March 2023 www eaton com This page is intentionally left blank...

Страница 28: ...aton com cooperpowerseries 2023 Eaton All Rights Reserved Printed in USA Publication No MN280103EN Z27254 March 2023 KA2048 0774 Rev 00 Eaton is a registered trademark All trademarks are property of t...

Отзывы: