12

Integrated voltage sensing option 

INSTALLATION AND OPERATION INSTRUCTIONS

   MN280103EN   March 2023   www.eaton.com

Contact position indicator

Located on the bottom of the recloser within the thermoset 

polymer housing, this indicator displays the word OPEN 

(green) when the recloser contacts are open and CLOSED 

(red) when the recloser contacts are closed. The position 

indicator is reflective and can be seen at night when a 

flashlight is shown on its surface. See 

Figure 10

.

Mechanical interlock feature

NOVA NX-STS recloser uses a mechanical interlock safety 

feature that is standard for all NOVA NX-STS reclosers 

to prevent an undesired close. When the yellow handle 

is pulled down from underneath the sleet hood, the 

mechanical interlock is engaged within the recloser tank and 

physically prevents the recloser contacts from closing. The 

mechanical interlock is disengaged when the yellow handle 

is moved upward into the sleet hood and the recloser can 

now be electrically closed.

Integrated voltage sensing option 

 WARNING

THIS EQUIPMENT IS NOT INTENDED TO PROTECT HUMAN LIFE. 

FOLLOW ALL LOCALLY APPROVED PROCEDURES AND SAFETY 

PRACTICES WHEN INSTALLING OR OPERATING THIS EQUIPMENT. 

FAILURE TO COMPLY CAN RESULT IN DEATH, SEVERE PERSONAL 

INJURY, AND EQUIPMENT DAMAGE.

 WARNING

HAZARDOUS VOLTAGE. ALWAYS USE A HOTSTICK WHEN 

WORKING WITH THIS EQUIPMENT.  FAILURE TO DO SO COULD 

RESULT IN CONTACT WITH HIGH VOLTAGE, WHICH WILL CAUSE 

DEATH OR SEVERE PERSONAL INJURY.

 WARNING

HAZARDOUS VOLTAGE. SOLIDLY GROUND ALL EQUIPMENT. 

FAILURE TO COMPLY CAN RESULT IN DEATH, SEVERE PERSONAL 

INJURY, AND EQUIPMENT DAMAGE.

 WARNING

HAZARDOUS VOLTAGE. IF TERMINAL CONNECTIONS ARE 

REVERSED,  VOLTAGE SENSING MAY INDICATE ERRONEOUS 

VOLTAGES WHEN THE CONTACTS ARE OPEN. DO NOT RELY ON 

VOLTAGE SENSING TO ENSURE THAT THE VOLTAGE IS ZERO AND 

THE LINE HAS BEEN DE-ENERGIZED. ALWAYS FOLLOW PROPER 

SAFETY PRACTICES AND USE A SEPARATE DETECTION METHOD 

TO VERIFY A DE-ENERGIZED CONDITION. FAILURE TO DO SO CAN 

RESULT IN CONTACT WITH HIGH VOLTAGE, WHICH WILL CAUSE 

DEATH OR SEVERE PERSONAL INJURY.

NOTICE

DISCONNECT SWITCHES FOR AC CONTROL POWER ARE 

NECESSARY TO ISOLATE THE CONTROL FOR TESTING AND 

SERVICING.

The NOVA NX-STS recloser is available with three or six 

voltage sensors (three internal for source voltage sensing, 

three integral sensors for load-side voltage sensing) when 

specified at time of order with the Form 7 control. Refer 

to the Installation Procedure section on page 7 for 

information on installing the NOVA NX-STS recloser. Refer to 

Service Information MN280095EN Form 7 Microprocessor 

Based Pole Mount Recloser Control Installation and 

Operation Instructions

 for further information on installing 

the Form 7 pole-mount control. 
Verify the correct load-side and source-side terminal 

connections. This is required for correct operation of both 

the internal and integrated load-side voltage sensors. 

NOTICE

WHEN THE LOAD-SIDE VOLTAGE SENSOR ACCESSORY IS 

INSTALLED, DO NOT GRASP THE TOP OF THE LOAD-SIDE VOLTAGE 

SENSOR AND LIFT. DOING SO CAN CAUSE INTERNAL DAMAGE TO 

THE LOAD-SIDE VOLTAGE SENSOR AND AFFECT VOLTAGE SENSING 

ACCURACY. ON THE SIDE OF THE LOAD-SIDE VOLTAGE SENSOR IS 

A “DO NOT LIFT” SYMBOL FOR VISUAL WARNING.

See 

Figure 11

 for a close up of “do not lift” symbol 

imprinted on the side of the load-side voltage sensor.

Figure 11 .  “Do not lift” symbol printed on the side of 

the load-side voltage sensor

“Do not lift” 

symbol

Содержание Cooper Power NOVA NX-STS

Страница 1: ...NOVA NX STS single tank triple single electronically controlled recloser installation and operation instructions Reclosers MN280103EN Effective March 2023 New Issue COOPER POWER SERIES...

Страница 2: ...A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS...

Страница 3: ...2 DIMENSIONS 3 INSTALLATION PROCEDURE 7 Removing recloser from service 9 RECLOSER OPERATION 10 Vacuum interrupter 10 Mechanism tripping and closing 10 Electronic control 11 Manual operation of energi...

Страница 4: ...nts WARNING INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH IF NOT AVOIDED COULD RESULT IN DEATH OR SERIOUS INJURY CAUTION INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH IF NOT AVOIDED MAY RESULT...

Страница 5: ...for damage incurred during shipment If damage is discovered file a claim with the carrier immediately Handling and storage Be careful during handling and storage of the NOVA NX STS recloser to minimi...

Страница 6: ...32 5 41 6 32 5 41 6 32 5 32 5 Rated duration of short circuit s 3 3 3 3 3 3 Rated short circuit breaking current kA sym 12 5 16 12 5 16 12 5 12 5 Rated symmetrical short circuit making current kA sym...

Страница 7: ...110 kV BIL inches mm 15 kV 125 kV BIL inches mm 27 kV 125 kV BIL inches mm 27 kV 150 kV BIL inches mm 38 kV 170 kV BIL inches mm Terminal to terminal 41 40 1052 0 41 40 1052 0 41 40 1052 0 41 40 1052...

Страница 8: ...0 38 0 170 kV BIL 58 20 1478 0 27 40 696 0 ote N All dimensions are in inches mm Dimensions shown are approximate 36 59 929 0 36 59 929 0 47 69 1211 0 A 15 24 387 0 42 87 1089 0 15 50 394 0 15 50 394...

Страница 9: ...s mm Dimensions shown are approximate Ground lug Grounding connection 0 50 mounting bolts 3 for outboard mounting 3 for inboard mounting 5 94 151 0 29 88 759 0 15 54 395 0 5 38 137 0 29 88 759 0 15 54...

Страница 10: ...8 70 1999 0 Dry 81 10 2060 0 ote N All dimensions are in inches mm Dimensions shown are approximate B B 28 13 715 0 28 18 716 0 29 34 745 0 21 99 559 0 14 23 361 0 Center of gravity for reference only...

Страница 11: ...ic condition of the recloser or the vacuum integrity of the interrupter WARNING FALLING EQUIPMENT USE THE LIFTING LUGS PROVIDED AND FOLLOW ALL LOCALLY APPROVED SAFETY PRACTICES WHEN LIFTING AND MOUNTI...

Страница 12: ...TO COMPLY COULD CAUSE SEVERE INJURY OR DEATH ote N Control is interlocked such that during normal operation voltage cannot appear unless correct 52a b status is reported by the recloser To ensure pro...

Страница 13: ...ED ALWAYS ESTABLISH A VISIBLE DISCONNECT FAILURE TO FOLLOW PROPER SAFETY PRACTICES CAN RESULT IN CONTACT WITH HIGH VOLTAGE WHICH WILL CAUSE DEATH OR SEVERE PERSONAL INJURY 1 Block ground tripping via...

Страница 14: ...o the Form 7 recloser control The recloser responds to trip and close commands from the control per the settings programmed in the control Refer to Service Information MN280095EN Form 7 Microprocessor...

Страница 15: ...the main contacts of the recloser Contact position is indicated by the OPEN flag of the contact position indicator located on the bottom of the recloser The yellow operating handle will remain down in...

Страница 16: ...NG HAZARDOUS VOLTAGE IF TERMINAL CONNECTIONS ARE REVERSED VOLTAGE SENSING MAY INDICATE ERRONEOUS VOLTAGES WHEN THE CONTACTS ARE OPEN DO NOT RELY ON VOLTAGE SENSING TO ENSURE THAT THE VOLTAGE IS ZERO A...

Страница 17: ...RFACES ARE CLEAN AND DRY BEFORE CONNECTING CABLES VOLTAGE SENSING ERRORS CAN RESULT FROM CONTAMINATION FAILURE TO COMPLY CAN RESULT IN CONTROL AND RECLOSER MISOPERATION The electrical connectors of th...

Страница 18: ...ION HAZARDOUS VOLTAGE DO NOT TOUCH THE RECEPTACLE CONNECTIONS OF THE CONTROL VOLTAGE SENSING CABLE IF THE RECLOSER IS ENERGIZED AND THE CONTROL VOLTAGE SENSING CABLE IS DISCONNECTED FROM THE RECLOSER...

Страница 19: ...ounting hanger Pole mounting accessory One pole mounting hanger which allows a variety of add on components to be mounted such as arresters and PTs dry or oil type is available for pole mount installa...

Страница 20: ...full rated ambient temperature range of the recloser and control The accuracy for this system applies when the following conditions are met Voltage range is greater than 50 to 100 of the rated maximum...

Страница 21: ...THE SWITCHGEAR APPARATUS AND CONTROL AND HIGH VOLTAGE TRANSFORMER MUST BE IN A TEST CAGE OR SIMILAR PROTECTED AREA TO PREVENT ACCIDENTAL CONTACT WITH THE HIGH VOLTAGE PARTS SOLIDLY GROUND ALL EQUIPMEN...

Страница 22: ...ply test voltage to terminals 1 3 and 5 for 60 seconds 9 The recloser should withstand the test voltage for 60 seconds Withstand test results The high potential withstand tests provide information on...

Страница 23: ...for damage Check the module surface and major and minor sheds for cracks holes and major chips If damage is present the module must be replaced Contact your Eaton representative 7 If no damage is fou...

Страница 24: ...rip Alt COIL Vendor Specific Close Trip COIL Close Trip Aux 52a Aux 52b Aux COM 69b combined SWITCH COM 52a 52b 69a Source VS Load VS VS Neutral PRESENT ONLY IF AUX SWITCH IS ORDERED THESE SIGNALS TER...

Страница 25: ...re 17 for typical configuration Phase C Internal Wiring See Figure 17 for typical configuration E SHIELD f VS Shield C CT C M Coil PhC Standard Interface Close Trip P Coil PhC Close Trip Y 52a PhC b 5...

Страница 26: ...S MN280103EN March 2023 www eaton com Figure 19 Auxiliary switch accessory wiring Phase A Phase B Phase C B1 F5 F3 F4 Aux 52a Aux 52b Aux Sw Com Aux 52a Aux 52b Aux Sw Com Customer connection B1 F5 F3...

Страница 27: ...23 Service information INSTALLATION AND OPERATION INSTRUCTIONS MN280103EN March 2023 www eaton com This page is intentionally left blank...

Страница 28: ...aton com cooperpowerseries 2023 Eaton All Rights Reserved Printed in USA Publication No MN280103EN Z27254 March 2023 KA2048 0774 Rev 00 Eaton is a registered trademark All trademarks are property of t...

Отзывы: