INSTALLATION AND OPERATION INSTRUCTIONS

   MN280103EN   March 2023   www.eaton.com

Product information

Introduction

Eaton’s Service Information MN280103EN provides 

installation, operation, and service instructions for Eaton’s 

Cooper Power

E

 series NOVA

E

 NX-STS single-tank, triple-

single electronically controlled recloser.

Read this manual first

Read and understand the contents of this manual and follow 

all locally approved procedures and safety practices before 

installing or operating this equipment.
This recloser is used in conjunction with Eaton’s Cooper 

Power series Form 7 recloser control. Refer to 

Service 

Information MN280095EN Form 7 Microprocessor Based 

Pole Mount Recloser Control Installation and Operation 

Instructions

.

Additional information

These instructions can not cover all details or variations in 

the equipment, procedures, or processes described nor 

provide directions for meeting every possible contingency 

during installation, operation, or maintenance. For additional 

information, please contact your Eaton Cooper Power series 

product representative.

Acceptance and initial inspection

Each recloser is completely assembled, tested, and 

inspected at the factory. It is in good condition when 

accepted by the carrier for shipment. Upon receipt, inspect 

the shipping container for signs of damage. Unpack the 

recloser and inspect it thoroughly for damage incurred 

during shipment. If damage is discovered, file a claim with 

the carrier immediately.

Handling and storage

Be careful during handling and storage of the NOVA  

NX-STS recloser to minimize the possibility of damage.  

If the recloser is to be stored for any length of time prior  

to installation, provide a clean, dry storage area.
Eaton recommends transporting NOVA NX-STS reclosers in 

the closed position to maximize the operational performance 

of the unit.

Standards

NOVA NX-STS reclosers are designed and tested in 

accordance with:

 

IEEE

®

 Std C37.60

E

–2018

 

IEEE Std C37.90.1

E

–2012

 

IEEE Std C37.90.2

E

–2004

Quality standards

ISO

®

 9001 Certified Quality Management System

Description

The NOVA NX-STS single-tank, triple-single recloser 

consists of three single-phase reclosers in a single tank. 

Each recloser consists of an interrupting module, with an 

embedded current transformer, and mechanism mounted 

to an aluminum head casting. The thermoset polymer tank 

enclosure is suitable for pole or substation mounting and is 

corrosion resistant. The interrupter modules utilize outdoor 

cycloaliphatic-epoxy-encapsulated vacuum interrupters.
The NOVA NX-STS recloser is controlled by a single 

microprocessor-based recloser control that can be 

programmed for three operating modes:

 

Single-phase trip, single-phase lockout

 

Single-phase trip, three-phase lockout

 

Three-phase trip, three-phase lockout

Refer to 

Service Information MN280095EN Form 7 

Microprocessor Based Pole Mount Recloser Control 

Installation and Operation Instructions

 for a description  

of the control operation.

Содержание Cooper Power NOVA NX-STS

Страница 1: ...NOVA NX STS single tank triple single electronically controlled recloser installation and operation instructions Reclosers MN280103EN Effective March 2023 New Issue COOPER POWER SERIES...

Страница 2: ...A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS...

Страница 3: ...2 DIMENSIONS 3 INSTALLATION PROCEDURE 7 Removing recloser from service 9 RECLOSER OPERATION 10 Vacuum interrupter 10 Mechanism tripping and closing 10 Electronic control 11 Manual operation of energi...

Страница 4: ...nts WARNING INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH IF NOT AVOIDED COULD RESULT IN DEATH OR SERIOUS INJURY CAUTION INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH IF NOT AVOIDED MAY RESULT...

Страница 5: ...for damage incurred during shipment If damage is discovered file a claim with the carrier immediately Handling and storage Be careful during handling and storage of the NOVA NX STS recloser to minimi...

Страница 6: ...32 5 41 6 32 5 41 6 32 5 32 5 Rated duration of short circuit s 3 3 3 3 3 3 Rated short circuit breaking current kA sym 12 5 16 12 5 16 12 5 12 5 Rated symmetrical short circuit making current kA sym...

Страница 7: ...110 kV BIL inches mm 15 kV 125 kV BIL inches mm 27 kV 125 kV BIL inches mm 27 kV 150 kV BIL inches mm 38 kV 170 kV BIL inches mm Terminal to terminal 41 40 1052 0 41 40 1052 0 41 40 1052 0 41 40 1052...

Страница 8: ...0 38 0 170 kV BIL 58 20 1478 0 27 40 696 0 ote N All dimensions are in inches mm Dimensions shown are approximate 36 59 929 0 36 59 929 0 47 69 1211 0 A 15 24 387 0 42 87 1089 0 15 50 394 0 15 50 394...

Страница 9: ...s mm Dimensions shown are approximate Ground lug Grounding connection 0 50 mounting bolts 3 for outboard mounting 3 for inboard mounting 5 94 151 0 29 88 759 0 15 54 395 0 5 38 137 0 29 88 759 0 15 54...

Страница 10: ...8 70 1999 0 Dry 81 10 2060 0 ote N All dimensions are in inches mm Dimensions shown are approximate B B 28 13 715 0 28 18 716 0 29 34 745 0 21 99 559 0 14 23 361 0 Center of gravity for reference only...

Страница 11: ...ic condition of the recloser or the vacuum integrity of the interrupter WARNING FALLING EQUIPMENT USE THE LIFTING LUGS PROVIDED AND FOLLOW ALL LOCALLY APPROVED SAFETY PRACTICES WHEN LIFTING AND MOUNTI...

Страница 12: ...TO COMPLY COULD CAUSE SEVERE INJURY OR DEATH ote N Control is interlocked such that during normal operation voltage cannot appear unless correct 52a b status is reported by the recloser To ensure pro...

Страница 13: ...ED ALWAYS ESTABLISH A VISIBLE DISCONNECT FAILURE TO FOLLOW PROPER SAFETY PRACTICES CAN RESULT IN CONTACT WITH HIGH VOLTAGE WHICH WILL CAUSE DEATH OR SEVERE PERSONAL INJURY 1 Block ground tripping via...

Страница 14: ...o the Form 7 recloser control The recloser responds to trip and close commands from the control per the settings programmed in the control Refer to Service Information MN280095EN Form 7 Microprocessor...

Страница 15: ...the main contacts of the recloser Contact position is indicated by the OPEN flag of the contact position indicator located on the bottom of the recloser The yellow operating handle will remain down in...

Страница 16: ...NG HAZARDOUS VOLTAGE IF TERMINAL CONNECTIONS ARE REVERSED VOLTAGE SENSING MAY INDICATE ERRONEOUS VOLTAGES WHEN THE CONTACTS ARE OPEN DO NOT RELY ON VOLTAGE SENSING TO ENSURE THAT THE VOLTAGE IS ZERO A...

Страница 17: ...RFACES ARE CLEAN AND DRY BEFORE CONNECTING CABLES VOLTAGE SENSING ERRORS CAN RESULT FROM CONTAMINATION FAILURE TO COMPLY CAN RESULT IN CONTROL AND RECLOSER MISOPERATION The electrical connectors of th...

Страница 18: ...ION HAZARDOUS VOLTAGE DO NOT TOUCH THE RECEPTACLE CONNECTIONS OF THE CONTROL VOLTAGE SENSING CABLE IF THE RECLOSER IS ENERGIZED AND THE CONTROL VOLTAGE SENSING CABLE IS DISCONNECTED FROM THE RECLOSER...

Страница 19: ...ounting hanger Pole mounting accessory One pole mounting hanger which allows a variety of add on components to be mounted such as arresters and PTs dry or oil type is available for pole mount installa...

Страница 20: ...full rated ambient temperature range of the recloser and control The accuracy for this system applies when the following conditions are met Voltage range is greater than 50 to 100 of the rated maximum...

Страница 21: ...THE SWITCHGEAR APPARATUS AND CONTROL AND HIGH VOLTAGE TRANSFORMER MUST BE IN A TEST CAGE OR SIMILAR PROTECTED AREA TO PREVENT ACCIDENTAL CONTACT WITH THE HIGH VOLTAGE PARTS SOLIDLY GROUND ALL EQUIPMEN...

Страница 22: ...ply test voltage to terminals 1 3 and 5 for 60 seconds 9 The recloser should withstand the test voltage for 60 seconds Withstand test results The high potential withstand tests provide information on...

Страница 23: ...for damage Check the module surface and major and minor sheds for cracks holes and major chips If damage is present the module must be replaced Contact your Eaton representative 7 If no damage is fou...

Страница 24: ...rip Alt COIL Vendor Specific Close Trip COIL Close Trip Aux 52a Aux 52b Aux COM 69b combined SWITCH COM 52a 52b 69a Source VS Load VS VS Neutral PRESENT ONLY IF AUX SWITCH IS ORDERED THESE SIGNALS TER...

Страница 25: ...re 17 for typical configuration Phase C Internal Wiring See Figure 17 for typical configuration E SHIELD f VS Shield C CT C M Coil PhC Standard Interface Close Trip P Coil PhC Close Trip Y 52a PhC b 5...

Страница 26: ...S MN280103EN March 2023 www eaton com Figure 19 Auxiliary switch accessory wiring Phase A Phase B Phase C B1 F5 F3 F4 Aux 52a Aux 52b Aux Sw Com Aux 52a Aux 52b Aux Sw Com Customer connection B1 F5 F3...

Страница 27: ...23 Service information INSTALLATION AND OPERATION INSTRUCTIONS MN280103EN March 2023 www eaton com This page is intentionally left blank...

Страница 28: ...aton com cooperpowerseries 2023 Eaton All Rights Reserved Printed in USA Publication No MN280103EN Z27254 March 2023 KA2048 0774 Rev 00 Eaton is a registered trademark All trademarks are property of t...

Отзывы: