7 Common operation of the web screens
Installation and Operating Instructions Web-Controller
40071860236 (E) February 2019 www.eaton.com
In the configuration menu
of the two digital inputs
1
,
2
the inputs can be
assigned specific com-
mands and the two relays
can be assigned condi-
tions when the relay’s
state changes.
Configuration of the two digital inputs
3
:
O
O
Not configured:
no function
O
O
Rest order:
During a mains failure (luminaires are in emergency mode), the rest mode
will switch OFF the luminaires. If mains return, the luminaires will go back in normal
mode. To the next mains failure, the luminaires switch again to emergency mode.
O
O
Activate IA mode:
Activate the Increase Affordance mode in line 1, 2, 3 and/or 4.
O
O
Maintained mode OFF per line:
Switches off the maintained mode luminaires of the
line as long as the input is active
O
O
Start function test:
With positive pulse, starts the function test with all luminaires
O
O
Stop FT/DT:
Interrupts a duration test or function test with all luminaires
O
O
External failure
Configuration of the two relay outputs
4
:
O
O
Not configured:
no function
O
O
One luminaire fault:
Common fault for at least one luminaire
O
O
Three consecutive luminaires failure:
At least 3 consecutive luminaires in a zone are
faulty
O
O
Communication fault:
At least 1 luminaire has a communication fault
O
O
Battery operation:
At least 1 luminaire is in battery mode, e.g. with mains failure
O
O
Function test:
At least 1 luminaire is in a function test
O
O
Duration test:
At least 1 luminaire is in a duration test
O
O
Charging failure:
At least 1 luminaire has a battery or charge fault
O
O
Test failure:
At least 1 luminaire has an FT or DT fault, e.g. nominal operating time not
reached
7.11 „Digital input/output“ configuration screen