5   Installation

Installation and Operating Instructions  Web-Controller

   40071860236 (E)   February 2019   www.eaton.com

System button 

3

The system button enables the  Web-Controller 

to be connected to a PC. If pressed for ~ 3 seconds, the 

green USB2 LED turns on and an external storage from 

Windows will be detected. An access via PC software will 

be possible now. To remove the controller the following 

steps are required:
1.  Remove external hard drive via windows
2.  Press system button for 3 seconds, green USB2 LED 

will turn off

USB cable A-B

USB2

Fig . 3 .   Connecting the controller to a laptop with 

PC-Software via USB A-B

Reset button 

3

The reset button resets the  Web-Controller (not 

factory default). For this purpose, the button must be 

pressed and held for >1 second.

5.2.3   Connections

230 V/AC 

6

Connection terminals for power supply 230 V/ AC with 

50/60 Hz. 

Bus: 

7

The Web-Controller is compatible to the old CGLine 

technlogy. If one or more CGLine luminaires are con-

nected, the CGLine compatible mode is active. Following 

luminaires can be connected:

Table 2 .  Max . number of luminaires to be connected

Line No.

CGLine

4 lines

2 lines

1

100

200

400

2

100

200

400

3

100

200

-

4

100

200

-

Total

400

800

800

Polarity D1/D2 to the luminaires must not be observed. 

Cable routing for CGLine bus: 2-core bus line, unshielded, 

free bus topology possible.

Table 3 .  Cable length/line

Cross-section

Length

Total lines

0.5 qmm

260 m

660 m

1.0 qmm

520 m

1320 m

1.5 qmm

800 m

2000 m

Table 4 .  Electrical data/line

Power supply bus

25 V

Max. permissible voltage drop

6 V

Bus current

300 mA

NOTE

In case of a communication failure with a luminaire please 

check the following:
1.  Check the proper connection of the bus line at the lumi-

naire’s connector

2.  Check the correct bus voltage at the luminaire (see 

table 4.)

3.  In case the voltage is correct and the communication 

failure still exists: Check the bus line resistance which 

shouldn’t exceed 32 Ohm. For that please disconnect 

the relevant line from the web-controller, apply a short 

cut between the bus contacts at the affected luminaire 

and measure the resistance at the other end of the line.

RS485 

8

No function. Only for french market. 

LAN connection 

9

Ethernet connection via RJ45 socket. A LAN patch cable 

must be used for direct connection of a PC/notebook. 

Blocking input (S1/S2): 

10

All connected luminaires can be blocked via the blocking 

input, meaning the luminaires are switched off and the 

emergency light function deactivated, for example for idle 

operating times.
Connection is via a key switch or relay (e.g. alarm sys-

tem). To guarantee reliable operation from short-circuit 

or interruption of the blocking line, this input is equipped 

with differential loop monitoring (static current), meaning 

a 1kOhm resistance must be integrated for blocking that 

defines the static current.

Connection example:

With closer contact

S1 CGLine

S2 Interface

Resistor must be connected next to the switch.

1 kOhm

Содержание CGLine+ Web Controller

Страница 1: ...Installation and Operating Instructions CGLine Web Controller Target group Electrical specialists CGLine Web Controller...

Страница 2: ...EENS 13 7 1 Home start screen 13 7 2 Start screen after registration 14 7 3 Overview of all faulty luminaires complete overview 15 7 4 Overview of all faulty luminaires for each zone 16 7 5 Overview o...

Страница 3: ...each or 2 lines with max 400 luminaires each only with homogeneous installation of CGLine luminaires CGVision software Configuration and full visualisa tion of 32 x 800 luminaires Alternative Network...

Страница 4: ...s policies O O Restrict Network Access Ideally CGLine Web Controller should be installed on a segregated net work However when the CGLine Web Controller is connected to a wider network make sure that...

Страница 5: ...hnical regulations when set ting up and operating electrical operating equipment 5 1 Assembly Observe impermissible temperatures at the installation location during mounting The permissible ambient te...

Страница 6: ...tional method O O Press the service pin 1 sec but 3 sec function test started for all luminaires O O Press the service pin 6 sec only new luminaires search started 1 6 7 8 9 10 2 3 4 5 3 Push buttons...

Страница 7: ...Cable length line Cross section Length Total lines 0 5 qmm 260 m 660 m 1 0 qmm 520 m 1320 m 1 5 qmm 800 m 2000 m Table 4 Electrical data line Power supply bus 25 V Max permissible voltage drop 6 V Bus...

Страница 8: ...ction enables connection of the CGLine Web Controller to a standard PC Controller functions can be programmed via the PC and a configuration software e g luminaire configurations The PC configuration...

Страница 9: ...llowing screen is displayed 1 2 The following screen is displayed Mark the entry Internet protocol version 4 1 then con tinue with Properties 2 Usually the network card is on DHCP i e Automatically re...

Страница 10: ...to the address bar The start screen of the CGLine Web Controller opens The screen shows an overview of the installed CGLine system with sum status information To have access to the submenus a login 1...

Страница 11: ...ar In the submenu configura tion 1 It is possible to change the network set tings 1 6 5 Modifying of the language date and time To change the language to English please click on Configuration 1 in the...

Страница 12: ...via the names is pos sible The CGLine Web Controller is supplied with a factory set static IP address of 192 168 1 200 3 Operation via DHCP is possible but in this case it is recommended to select st...

Страница 13: ...Password GUEST 1 The Admin Account allows full access to the CGLine Web Controller e g start function test The User account allows only access for monitoring the status of the controller and connecte...

Страница 14: ...Yellow min 1 lumi naire faulty O O Red min 3 luminaires faulty e g lamp failure After the login the navigation menu appears on the left side 1 O O Home The start screen is accessed via Home at any tim...

Страница 15: ...le to enter to the building layout picture if it is prepared The menu Oveview 1 and the tab Overview luminaire failure 2 display all lumi naires with a fault 3 O O L line no 1 4 O O Z zone 2 16 O O B...

Страница 16: ...r 40071860236 E February 2019 www eaton com 7 4 Overview of all faulty luminaires for each zone All luminaires with a fault in a zone are displayed in the Overview menu 1 and the Zone tab 2 Via the dr...

Страница 17: ...erview luminaires 2 shows all installed luminaires on the CGLine Web Controller 1 2 7 6 Information information text of the luminaires This screen shows the name with max 20 char acters and informatio...

Страница 18: ...of luminaires addresses For changing the configuration of luminaires addresses please follow the steps below 1 Click on the tab Luminaires The table with all the lumi naires installed appears 2 Click...

Страница 19: ...uration tests are aborted O O Switch maintained mode ON OFF Luminaires in maintained mode L applied can be switched ON or OFF if luminaire supports this function O O Update luminaire status Actualisia...

Страница 20: ...s On the Test tab 2 in the configuration menu 1 it is possible to deter mine start times for a function test and duration test for up to 8 groups It is also possible to set a test interval via which t...

Страница 21: ...d mode luminaires of the line as long as the input is active O O Start function test With positive pulse starts the function test with all luminaires O O Stop FT DT Interrupts a duration test or funct...

Страница 22: ...necessary after the commissioning to correctly set the date and time in the CGLine Web Controller here 5 2 1 4 5 3 7 13 Network settings Follwing settings are possible O O DHCP Dynamic Host Control Pr...

Страница 23: ...plete logbook is downloadable via log book dat This file is only usable with the CGLine PC software see manual CGLine PC software The CGLine Web Controller contains an integrated e mail client 1 that...

Страница 24: ...n layouts of the building or areas It is pos sible to import up to 30 building layout plans with max 200 luminaires each The colour of the luminaire shows the status e g red luminaire failure To use t...

Страница 25: ...ing layouts can displayed now by the folder List of building layouts 1 With click on the name of the layout which is displayed as hyperlink with xml exten sion 2 the layout can load from the controlle...

Страница 26: ...n there is a search function 1 2 This enables quickly finding any defective luminaires in a building To find a luminaire in the layout plan the line the zone and the luminaire to address can be select...

Страница 27: ...entered here After confirming via Add the devices are automati cally created A device can be deleted from the list again via Delete 3 3 1 2 7 24 Overview all Web Controller With several installed CGLi...

Страница 28: ...ht solution for the application But decision makers demand more than just innovative pro ducts They turn to Eaton for an unwavering commitment to personal support that makes customer success a top pri...

Отзывы: