![Eaton CGLine+ Web Controller Скачать руководство пользователя страница 6](http://html2.mh-extra.com/html/eaton/cgline-web-controller/cgline-web-controller_installation-and-operating-instructions-manual_3760995006.webp)
6
5 Installation
Installation and Operating Instructions Web-Controller
40071860236 (E) February 2019 www.eaton.com
5.2.2 Push button functions
The Web-Controller has 3 push buttons on the
front plate:
Service button
3
The service pin enables a luminaire search for subse-
quently installed luminaires, thus saved luminaires will
not be deleted. Also possible via the service pin to start a
function test for luminaires on all lines.
Functional method:
O
O
Press the service pin > 1 sec. but < 3 sec.: function
test started for all luminaires
O
O
Press the service pin > 6 sec.: „only new luminaires“
search started
1
6
7
8
9
10
2
3
4
5
3
Push buttons:
Service = e.g. starting a FT
System = establish a USB connection on USB2
Reset = hardware reset
4
USB1 host for connecting a USB stick
5
USB2 device for connection to PC
6
PE/N/L 230V 50/60Hz
7
Connection bus line 1-4
8
RS485, currently not in use
9
LAN (RJ45) with LED displays:
Yellow = Link; Green = Traffic
10
S1/S2 = Block input
In1, In2 = 2 x digital inputs
11, 12, 14, 21, 22, 24 = 2 x relay outputs
Fig . 4 . Electrical connections, push buttons and LED
displays