84
Mounting- and Operating Instruction CEAG DualGuard-S
40071860347 January 2020 www.ceag.de
40 DualGuard-S LAD 100
23,3 Ah Battery wiring standing cabinet
32 Ah Battery wiring standing cabinet
Technical description
Battery type (C10; 1,8 V/Z; +20 °C):
12 V / 23,3 Ah
Nominal battery voltage of all connected
cells
216 V
Numbers of battery blocks:
18 á 12 V
Dimensions per block in mm (L x W x H): 168 x 127 x 174
End poles
M6
Order Number battery block:
40066070461
Dimensions Battery cabinet
in mm (B x H x D):
800 x 2050 x 400
Battery consoles:
3
Terminals:
max. 35 mm²
Weight incl. Batterys:
295 kg
Degree of protection:
IP21
Order Number wiring set:
40071346779
15 x Length 1:
300 mm
2 x Length 2:
1000 mm
1 x Length 3:
800 mm
1 x Length 4:
2000 mm
Technical description
Battery type (C10; 1,8 V/Z; +20 °C):
12 V / 32 Ah
Nominal battery voltage of all connected
cells
216 V
Numbers of battery blocks:
18 á 12 V
Dimensions per block in mm (L x W x H): 198 x 168 x 175
End poles
M6
Order Number battery block:
40066070116
Dimensions Battery cabinet
in mm (B x H x D):
800 x 2050 x 400
Battery consoles:
3
Terminals:
max. 35 mm²
Weight incl. Batterys:
370 kg
Degree of protection:
IP21
Order Number wiring set:
40071346779
15 x Length 1:
300 mm
2 x Length 2:
1000 mm
1 x Length 3:
800 mm
1 x Length 4:
2000 mm
1
2
3
4
1. Battery console
2. Battery console
3. Battery console
1
2
3
4
1. Battery console
2. Battery console
3. Battery console