111
Mounting- and Operating Instruction CEAG DualGuard-S
40071860347 January 2020 www.ceag.de
44 DualGuard-S 12C4
Technical description
Field
Dimensions (W x H x D):
1800 x 600 x 400 mm
Colour:
RAL 7035
Weight:
115 kg
Assembly:
Ground
Degree of protection:
IP21, optional IP31, on request IP54
Protection class:
I
Ambient temperature:
-5°C to +35°C
Degree of pollution:
2
Electromagnetic compatibility:
Industry EN 61000-6-2, Commercial EN 61000-6-3
Rated voltage (Mains):
UN = 230 V AC
Rated current (Mains):
IN = 25 A
Rated voltage (Battery):
216 V DC
Rated current (Battery):
IN =25 A
Rated Frequency:
50 / 60 Hz
Overvoltage category:
Mains: III / Battery: II
Max. connected load:
At +35°C < 5,4 KW
Maximum numbers of modules:
Controller ACU DG / HMI:
1
A1
PSU:
1
C1
BCM.1:
1
C2
SKU.1.1 CG-S:
C-D
1x6A
0-12
2x3A
0-12
4x1,5A
0-12
Luminaire circuits:
48
A3-4
Charger CM 1,7A
1
C2
Terminals:
Luminaire circuits
4 mm² Rigid/flexible
A3-4
BCM.1
4 mm² Rigid/flexible
A2
ACU DG
2,5mm² Rigid/ 1,5mm² flexible
A1
Battery feed
16 mm² Rigid/flexible
B4
Battery distribution
16 mm² Rigid/flexible
B4
Mains feed
16 mm² Rigid/flexible
B1
Mains distribution board
16 mm² Rigid/flexible
B1
Order number accesories:
Cupboard base 100mm
40071362280
Cupboard base 200mm
40071362281
Door hinge left
40071362300
Special locking profile half cylinder
40037079790
IP 31 Retrofit kit
40071362290