134
Mounting- and Operating Instruction CEAG DualGuard-S
40071860347 January 2020 www.ceag.de
57 DualGuard-S ESF30 US SOU2
57 DualGuard-S ESF30 US SOU2
The DualGuard-S ESF30 US SOU2 sub-station in accordance
with EN 50171 supplies 230V / 216V AC/DC safety and
escape sign luminaires and is particularly suitable for instal-
lation in fire compartments in buildings with a large number
of fire compartments. Thus, the decentralised design of the
system can contribute to reducing the costs for function
maintenance cabling. The automatic test device and indivi-
dual luminaire monitoring with individual status and name
indication per luminaire in conjunction with system-related
ECG / LED supply module including monitoring module
without additional data line reports and proclaims the ope-
rating states.
Consisting of:
Fire protection wall distributor with cable entry from above
and two SOU CG-S 2x4A circuit switches.
Technical description
Field
Dimensions (W x H x D):
690x400x230 mm
Colour:
RAL 7035
Weight:
51 kg
Assembly:
Wand
Degree of protection:
IP65
Protection class:
II Schutzisoliert nach VDE 0106
Ambient temperature:
-5°C to +35°C
Degree of pollution:
2
Electromagnetic compatibility:
Industry EN 61000-6-2, Commercial EN 61000-6-3
Rated voltage (Mains):
UN = 230V AC
A1
Rated current (Mains):
IN = 9A
Rated voltage (Battery):
216 V DC
A1
Rated current (Battery):
IN =9 A
Rated Frequency:
50 / 60 Hz
Overvoltage category:
Mains: III / Battery: II
Max. connected load:
At +35°C < 1,9 KW
Maximum numbers of modules:
SOU CG-S 2x4A
2
A-B
Max. numbers luminaire circuits:
4
Terminals:
Luminaire circuits:
4 mm² Rigid/flexible
A-B
Battery feed:
10 mm² Rigid/flexible
A1-2
Battery through-wiring:
10 mm² Rigid/flexible
A1-2
Mains feed:
10 mm² Rigid/flexible
A1-2
Mains through-wiring:
10 mm² Rigid/flexible
A1-2
1 2 3 4
A
B
C
D
396
230
685