4. Construction and Function
MANUAL CEAG AUtoMAtiC tEst systEM At-s
+
40071860177 (C) December 2016 www.ceag.de
t > 100ms
t > 1s
Level trigger:
Edge trigger:
Z1
Z2
Z3
Z4
Comments:
No function
–
factory setting
Switch
Level triggered (by use of a switch)
24VDC = ON, 0V = OFF
Used as a switch and switches the circuit or the luminaires
with “S” function.
Switch inverted
Level triggered (by use of a switch)
24VDC = OFF, 0V = ON
Manual reset
Edge triggered (by use of a push switch)
LOW HIGH
To reset the circuit arrangement ”manual reset“.
Start functiontest
Start a function test.
All luminaires on
Level triggered (by use of a switch)
24VDC = ON, 0V = OFF
For switching on all luminaires
F-Test cancellation
Edge triggered (by use of a push switch)
LOW HIGH
Cancel function test
Block device
Block / Release function of mains/emergency lighting during shut downs.
Maintained off
Switch off all luminaires /circuits, which are programmed as maintained light.
Non-maintained on
Switch on all luminaires /circuits, which are programmed
as non-maintained light.
Ventilator monitor
Level triggered (by use of a switch)
24VDC = OK, 0V = Failure
Set charging failure at the potential-free relay contacts of
the control module to the CG IV relay module and the CGVision,
as long as 0 V is present.
Ext. ISO monitor
Ext. Battery monitor
Ext. Monitor
Ext. Source ready
Level triggered (by use of a switch)
24VDC = normal operation, 0V = not ready
Sets „Ready“ at the potential-free relay contacts of the control module
and the CGVision, as long as 24 V DC is present.
Ext. Source active
Level triggered (by use of a switch)
24VDC = ext. Source active
0V = normal operation
Sets „Ext. Source active“ at the potential-free relay contacts of
the control module and the CGVision, as long as 24 V DC is present.
Ext. Source failure
Level triggered (by use of a switch)
24VDC = normal operation
0V = failure
Sets „Ext. Source failue“ at the potential-free relay contacts of
the control module and the CGVision, as long as 0 V is present.
Optional inputs Z1 - Z4
Z1 to Z4, connection for analogue inputs:
4 freely assignable 24 V analogue inputs, can
be programmed either inverted or non-inverted
Control inputs
The 24V analog inputs Z1 ... Z4 are to control the external
control panels, a programmable trip of operational
functions (e. g. bloc / release system, manual reset, etc.)
is given.