Note 1: Voltage pickup and drop out settings are based upon a percentage of the base voltage
Note 2: Frequency pickup and drop out settings are based upon a percentage of the base frequency
Note 3: Set to order specific value
Table 2. Programmable Features/Setpoints (Cont.)
PROGRAMMABLE
FEATURE DISPLAY
DISPLAY
EXPLANATION
SETPOINT
POSSIBILITIES
FACTORY DEFAULT
VALUE
MEASURE
PRF SRC
Preferred Source
None
1=Source 1
2=Source 2
1
-
EXER
Plant Exerciser Enabled or Disabled
1=Enabled
0= Disabled
1
-
EXLD
Load Transfer with Plant Exerciser
1=Enabled
0= Disabled
1
-
PEDAY
Plant Exerciser Day of Week
1 to 7
(1= Sunday)
1
Week Day
PEH
Plant Exerciser Hour
1 am to 11 pm
1 AM
Hour
PREMIN
Plant Exerciser Minute
0 to 59 Minutes
0
Minutes
MANTR
Re-Transfer Mode
0= Automatic
1= PB Return
0
-
CTDNE
Commitment to Transfer in TDNE
0= Not Committed
1= Committed
0
-
TMODE
Engine Test With/Without Load Transfer
0= No Load Transfer
1= Load Transfer
2= Disable Test Pushbutton
1
-
TER
Engine Test/Plant Exerciser Run Time
0 to 600 Minutes
0:30
Hours: Minutes
TPRE
Pre-Transfer Sub-Network
Time Delay
1 to 300 Seconds
0:01
Minutes: Seconds
GENNO
Number of Generators
(Single Generator Must Be On Source 2)
0 to 2
1
-
PHASE
Number of System Phases
1 or 3
3
3
-
TSEQ
Time Delay Load Sequencing
1 to 120 Seconds
0:10
Minutes: Seconds
PT
PT Ratio
2:1 to 500:1
2:1
-
Closed
Close Transition
Enabled or
Disabled
1= Enabled
0= Disabled
1
CTFD
Close Transition
Frequency
Difference (Hertz)
0.0 to 0.3 Hz
0.3
Hz
CTVD
Close Transition
Voltage
Difference (Volts)
1 to 5 %
6
Volts
IPHASE
In-Phase Transition Enabled or Disabled
1= Enabled
0= Disabled
0
-
IPFD
In-Phase Transition Frequency Difference (Hertz)
0.0 to 3.0 Hz
1.0
Hertz
SYNC
Closed/In-Phase Transition Synchronization Timer
1 to 60 Minutes
5
Minutes
TDEF
Time Delay Engine Failure
0 to 60 Seconds
6
Seconds