background image

IB ATS-C103

For more information visit: www.eaton.com

Instructional Booklet

Effective: March 2012

Page

19

Instructions for Installation, Operation and Maintenance of the 

Eaton ATC-800 Closed/Open Transition Transfer Switch Controller

History information:

Source 1 Engine Run Time
Source 2 Engine Run Time
Source 1 Available Time
Source 2 Available Time
Source 1 Connected Time
Source 2 Connected Time
Load Energized Time
Number of Transfers

All history information is in hours and minutes. Each individual 

value is resettable over IMPACC.

Time-stamped history (time/date/reason) for all previous trans-

fers.

Capability to initiate an engine test.

Updates the ATC-800 real-time clock.

4.9  Closed/In-phase Transition

Closed Transition is a feature that will temporarily parallel two live 

sources in a make-before-break scheme when performing a trans-

fer.  This achieves a transfer between sources with no power 

interruption.  Both sources must be synchronized in frequency, 

phase, and voltage before the transfer is initiated.
In-phase Transition is a feature that will allow a transfer between 

two live sources only when the phase difference between the two 

sources is near zero.  This is an open transition transfer that pre-

vents in-rush currents from exceeding normal starting currents in 

the case where motor loads are being transferred.
The following sequence of transitions is implemented: If Closed 

Transition does not occur in a specified amount of time, we will 

proceed to In-phase Transition.  If this transition does not occur 

within a specified amount of time, we will then perform an Open 

Transition with the Time Delay Neutral or Time Delay Load Sense 

feature.

4.9.1  Closed Transition

The Closed Transition transfer switch will close the breakers for 

both sources for a maximum time of 100 milliseconds after the 

sources are synchronized.  The breaker for the Normal source will 

then be opened.
The closed transition scheme is anticipatory in that the breaker 

close command is initiated before the sources are exactly in-

phase.  This phase angle is called the advance angle.  The 

advance angle compensates for the closing time of the breaker.  

The advance angle is calculated based on the frequency differ-

ence between the two sources and also the response time of the 

breaker.  This results in the optimum reconnect angle of 0 degrees 

for all of the frequency difference values.

The criteria for closed transition require that both sources be 

available and synchronized in voltage, frequency, and phase.  The 

frequency difference must be less than the closed transition fre-

quency difference set point (0.0 to 0.3 Hz).  The voltage differ-

ence must be less than the closed transition voltage difference 

setpoint (1 to 5%).  When these conditions are met, the ATC-800 

will monitor the phase difference between the two sources.  The 

synchronization timer will count down and be displayed as 

“TSCT” while waiting for synchronization to be detected.  When 

the phase difference is within the advance angle window, the 

“breaker close” command is given.  When the breaker closes, the 

two Sources are paralleled and then the first source is discon-

nected.  The parallel time is less than 100 milliseconds.
If the synchronization does not occur within a specified amount of 

time, the transfer will take place under in-phase transition or 

delayed transition.  If a closed transition transfer is performed and 

the Normal source is not opened within 100 milliseconds, then 

the Emergency source is opened and the alarm relay is energized.

4.9.2  In-Phase Transition

In-phase transition is an open transition with both sources in-

phase.  The same anticipatory scheme used for closed transition 

is also used for in-phase transition.  The advance angle is calcu-

lated based on the frequency difference between the two sources 

and also the response time of the breaker.  This results in the opti-

mum reconnect angle of 0 degrees for all of the frequency differ-

ence values.
The criteria for in-phase transition are similar to closed transition.  

Both sources must be available and the frequency difference must 

be less than the in-phase transition frequency difference setpoint 

(0.0 to 3.0 Hz).  When these conditions are met, the ATC-800 

will monitor the phase difference between the two sources.  The 

synchronization timer will count down and be displayed as “TSIP” 

while waiting for synchronization to be detected.  When the 

phase difference is within the advance angle window, the “trans-

fer” command is given.  This is an open transition but both 

sources will be in phase when the transfer occurs.
If the synchronization does not occur within a specified amount of 

time, the transfer will take place under delayed transition.The 

Alarm relay will energize and the failure will be logged into the 

Transfer History as either “Sync Fail - Freq” or “Sync Fail - Phase” 

depending on whether the frequency difference or the phase dif-

ference was excessive.

NOTICE

IF THE ATC-800 RUN/PROGRAM SWITCH IS IN THE PROGRAM POSI-

TION, THE SETPOINTS CANNOT BE DOWNLOADED OVER IMPACC.

Содержание ATC-800

Страница 1: ...roller Instructional Booklet Description Page 1 Introduction 2 2 Hardware Description 7 3 Operator Panel 11 4 Operation 14 5 Programming 20 6 Troubleshooting and Maintenance 23 Appendix A Status Displ...

Страница 2: ...al or conse quential damage or loss whatsoever including but not limited to damage or loss of use of equipment plant or power system cost of capital loss of power additional expenses in the use of exi...

Страница 3: ...from most system voltages available worldwide at 50 or 60 Hertz In addition a period of no control power operation is provided ATC 800 moni tors the condition of the 3 phase line to line voltage and...

Страница 4: ...ce is already available the TDES timer is bypassed Standard Feature 3 Time Delay Emergency to Normal TDEN TDEN delays the transfer to the Normal Source to permit stabiliza tion of the Normal power sou...

Страница 5: ...ual to or above the pickup setting to become available again Underfrequency Monitoring for Source 1 1UFD 1UFP This feature constantly monitors Source 1 for an underfrequency condition When the Source...

Страница 6: ...time delay in the transfer switch Neutral position when both breakers are open This delay takes place when the load is transferred in either direction to prevent excessive in rush currents due to out...

Страница 7: ...Modbus compatible devices A separately mounted communications mod ule will enable the automatic transfer controller to be remotely monitored controlled and programmed via the network Optional Feature...

Страница 8: ...ssages 5 Display LEDs seven LEDs to identify the Display Win dow Information 6 Help Pushbutton provides English language help information in any operational mode 7 Increase Decrease Pushbuttons used i...

Страница 9: ...e communication module PONI to the back of the ATC 800 Figure 3 or in a remote location Since the ATC 800 is always supplied with a communications port a PONI can be easily retrofitted to the ATC 800...

Страница 10: ...kup Range Volts Breaker Switch Style ATS Contactor Style ATS Dropout 2 to 99 of Nominal System Voltage Dropout 2 to 99 of Nominal System Voltage Overvoltage Dropout Range Volts Breaker Switch Style AT...

Страница 11: ...Source 1 is the preferred source choice Source 1 Connected Status LED This LED is lit green if Source 1 is connected This is accom plished by sensing the Source 1 breaker via the S1 closed auxil iary...

Страница 12: ...sfer will occur and the engine will run for the programmed run time 3 3 4 Display Select Pushbutton As the Display Select Pushbutton is pressed and released ATC 800 steps through the following display...

Страница 13: ...le conditions will be shown OVER V The source has risen above the dropout setting and not dropped below the pickup setting UNDER V The source has dropped below the dropout setting and not risen above...

Страница 14: ...ated by the features supplied and their programmed setpoint values It provides a sum mary of ATC 800 s intelligence and supervisory circuits which constantly monitor the condition of both normal and e...

Страница 15: ...g this contact will activate the Emergency Inhibit input If the Emergency Inhibit contact is opened when the load is con nected to the Normal Source no action will be taken if the Normal Source is ava...

Страница 16: ...able up to 10 separate loads The Addressable Relay II must be set for 1200 BAUD rate WATCHDOG feature disabled RELAY PULSE feature disabled Address range from 002 to 00B Under normal condition with so...

Страница 17: ...itions include improper circuit breaker operation motor operator failure and unsuccessful closed or in phase transition An alarm may be reset by simultane ously pressing the Increase and Decrease Push...

Страница 18: ...the TDNE countdown the Emergency Source goes unavailable more than three times Each time TDNE will restart 4 If the Emergency Source is powering the load and it goes unavailable for more than the TDEF...

Страница 19: ...ransition require that both sources be available and synchronized in voltage frequency and phase The frequency difference must be less than the closed transition fre quency difference set point 0 0 to...

Страница 20: ...The Setpoints LED will be lit red and the first programming possibility will appear in the display Use the Step Pushbutton to move from one feature setpoint to another stopping at those in need of rep...

Страница 21: ...ltage1 115 110 Volts 1OVP Source 1 Overvoltage Pickup Volts Breaker Switch Style ATS Contactor Style ATS 103 to Dropout 2 of Nominal System Voltage1 103 to Dropout 2 of Nominal System Voltage1 110 105...

Страница 22: ...ser Minute 0 to 59 Minutes 0 Minutes MANTR Re Transfer Mode 0 Automatic 1 PB Return 0 CTDNE Commitment to Transfer in TDNE 0 Not Committed 1 Committed 0 TMODE Engine Test With Without Load Transfer 0...

Страница 23: ...nutes of inactivity with pushbuttons when changing set points Voltage dropout and pickup setpoints are different than what was programmed Adjusted nominal voltage setpoint Re adjust all dropout and pi...

Страница 24: ...open when Source 1 contactor opened S1 Aux Close contacts did not close when Source 1 Contactor closed Check Source 1 contactor trip wiring Press Increase and Decrease push buttons simultaneously to c...

Страница 25: ...ts Determine the cause and rectify if possible Replace defective com ponents after the cause is determined Step 5 Press the push to close button on the normal switching device Verify whether or not th...

Страница 26: ...the correct line voltage and frequency available at ter minals E1 E2 and E3 Record the readings If YES Proceed to Step 3 If NO Verify that there is output voltage from the generator Step 3 Is the volt...

Страница 27: ...e ATC 800 are de energized These may also be present on some of the terminal blocks Step 3 Before disconnecting any wires from the unit make sure they are individually identified to assure that reconn...

Страница 28: ...Waiting for load voltage to decay before completing the transfer TDP Countdown timing while waiting for a pre transfer acknowledge input TSEQ Countdown timing between sequenced loads NO R xx No commun...

Страница 29: ...Source 2 Connected Time This counter logs time in hours whenever Source 2 is connected to the load Time will start being logged at the time the S2 AUX control input is closed This counter will count u...

Страница 30: ...erator 7 Engine test 8 Manual re transfer 9 Engine Test via communications 10 Go to neutral 11 Program mode 12 Options or setpoints error 13 Emergency Inhibit 14 Go to Emergency 15 Lock out 16 Failed...

Страница 31: ...sly roll over between AM and PM values Minutes By using the Increase or Decrease Pushbuttons the minutes of the day can be adjusted to the present value The number will continuously roll over between...

Страница 32: ...For 1 Phase Sensing with Open Transition FREQ Condition VOLT FREQ Condition VAB VBC VCA FREQ Condition VOLT FREQ Condition Display is blank or a status message appears Note All menu items are not nece...

Страница 33: ...D 2UFD 1UFP 2UFP 1OFD 2OFD 1OFP 2OFP TDN TDNLD LDCY PRF SRC EXER EXLD PEDAY PEH PEMIN MANTR CTDNE TMODE TER TPRE GENNO PHASE TSEQ STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP...

Страница 34: ...breaker Momentarily energize K3 Source 1 becomes unavailable or Engine Test Plant Exerciser Go To Emergency TDES timer times out Send Engine Start signal Energize Gen Start relay TDNE timer times out...

Страница 35: ...eaker Momentarily energize K3 Source 1 becomes unavailable or Go To Emergency TDNE timer times out Open Source 1 breaker Energize K2 Y Source 2 is powering the load Close Source 1 breaker Momentarily...

Страница 36: ...signal Energize Gen Start relay TDNE timer times out Y Source 2 is powering the load Energize Alarm relay Open Source 1 Energize K2 Close Source 2 out of Sync Momentarily energize K4 Source 1 is powe...

Страница 37: ...tion visit www eaton com Instructional Booklet Effective March 2012 Page 37 Instructions for Installation Operation and Maintenance of the Eaton ATC 800 Closed Open Transition Transfer Switch Controll...

Страница 38: ...let Page 38 Effective March 2012 Instructions for Installation Operation and Maintenance of the Eaton ATC 800 Closed Open Transition Transfer Switch Controller For more information visit www eaton com...

Страница 39: ...re information visit www eaton com Instructional Booklet Effective March 2012 Page 39 Instructions for Installation Operation and Maintenance of the Eaton ATC 800 Closed Open Transition Transfer Switc...

Страница 40: ...DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN In no event will Eaton be responsible to the purchaser or user in contract in tort inclu...

Отзывы: