Instructions for Installation, Operation and Maintenance of the 

Eaton ATC-800 Closed/Open Transition Transfer Switch Controller

4.4.3 ATC Annunciator

The ATC Annunciator provides remote annunciation of an ATC-

800 which may be located up to 1000 feet away. The ATC 

Annunciator will communicate with the ATC-800 over the INCOM 

Subnetwork using a twisted shielded pair cable. Required power is 

either 120 VAC 50/60Hz or 24 VDC.
The ATC Annunciator displays the ATC-800 information through 

six LEDs as described below:

Source 1 Available

This white LED is lit if Source 1 meets the criteria for programmed 

Source 1 setpoints.

Source 1 Connected 

This green LED is lit when the Source 1 breaker is closed.

Source 2 Available

This amber LED is lit if Source 2 meets the criteria for pro-

grammed Source 2 setpoints.

Source 2 Connected

This red LED is lit when the Source 2 breaker is closed.

Comm OK

This green LED is lit when the ATC Annunciator is communicating 

properly with the ATC-800.

In Test

This red LED indicates that the ATC-800 is in Test mode.

4.5  Relay Outputs

As described in Section 2, the rear access area provides for 

access to all output connections. Refer to Figure 

3

 for a graphical 

representation and position of all output connections. The relay 

functions are divided into two categories:

Customer Connections

Transfer Operation Contacts

4.5.1  Customer Connections

S2 Generator

This latched coil relay provides a Form A contact on Pins 1 and 2 

of Connector J5. The relay is the generator start relay for system 

configurations employing a generator on the input source desig-

nated Source 2. The generator start relay contacts are rated for 

5A, 1/6 HP @ 250 VAC. The DC rating is 5A @ 30VDC with a 

150W maximum load.

S1 Generator

This latched coil relay provides a Form A contact on Pins 3 and 4 

of Connector J5. The relay is the generator start relay for system 

configurations employing a generator on the input source desig-

nated Source 1. The generator start relay contacts are rated for 

5A, 1/6 HP @ 250 VAC. The DC rating is 5A @ 30VDC with a 

150W maximum load.

Alarm

This Form C relay is used to indicate an alarm condition. The full 

Form C contact of this relay is implemented with Common Pin 8, 

Normally Closed Pin 7, and Normally Open Pin 6 of Connector J5. 

The relay is normally de-energized to indicate the absence of an 

alarm state. Energization of the relay indicates the presence of an 

alarm condition. Alarm conditions include improper 
circuit breaker operation, motor operator failure, and unsuccessful 

closed or in-phase transition. An alarm may be reset by simultane-

ously pressing the Increase and Decrease Pushbuttons.  The relay 

contacts are rated for 10A, 1-3 HP @ 250 VAC. The DC rating is 

10A @30VDC.

S2 Available

This Form C relay is used to indicate the availability of Source 2. 

The full Form C contact of this relay is implemented with Com-

mon Pin 11, Normally Closed Pin 10, and Normally Open Pin 9 of 

Connector J5. This relay essentially duplicates the Source 2 avail-

able status LED meaning that the setpoint criteria has been met. 

The relay contacts are rated for 10A, 1-3 HP @ 250 VAC. The 

DC rating is 10A @30VDC.

S1 Available

This Form C relay is used to indicate the availability of Source 1. 

The full Form C contact of this relay is implemented with Com-

mon Pin 14, Normally Closed Pin 13, and Normally Open Pin 12 of 

Connector J5. This relay essentially duplicates the Source 1 avail-

able status LED meaning that the setpoint criteria has been met. 

The relay contacts are rated for 10A, 1-3 HP @ 250 VAC. The 

DC rating is 10A @30VDC.

4.5.2 Transfer Operation Connections

K1, K2, K3, and K4 are factory wired to operate the transfer 

switch. The relay contacts for each are rated for 10A, 1/3 HP @ 

250 VAC. The DC rating is 10A @30VDC. K1– K4 are Form C 

relays but only the Form A contacts are used to operate the trans-

fer switch.

Note: 

The ATC-800 Controller MUST BE properly grounded at J-5, Pin 5 

for proper operation.

Output Relay K1

The K1 output is used for control of the transfer switch motor to 

close the Source 1 switching device (i.e. circuit breaker) for 

motor-operator transfer switches. The K1 relay momentarily ener-

gizes until the ATC-800 senses that the Source 1 switching 

device is closed, then K1 de-energizes. For transfer switches with 

power breakers, this relay opens the Source 2 breaker via its trip 

coil. The k1 output is found on pins 21 and 22 of Connector J5

Output Relay K2

The K2 output is used for control of the transfer switch motor to 

close the Source 2 switching device (i.e. circuit breaker) for 

motor-operator transfer switches. The K2 relay momentarily ener-

gizes until the ATC-800 senses that the Source 2 switching 

device is closed, then K2 de-energizes. For transfer switches with 

power breakers, this relay opens the Source 1 breaker via its trip 

coil. The K2 output is found on pins 19 and 20 of Connector J5.

Output Relay K3

The K3 output is used for control of the close coil of the Source 1 

breaker in transfer switches with power breakers. The K3 relay 

momentarily energizes until the ATC-800 senses that the Source 

1 breaker is closed, then K3 de-energizes. The K3 output is found 

on pins 17 and 18 of Connector J5.

Содержание ATC-800

Страница 1: ...roller Instructional Booklet Description Page 1 Introduction 2 2 Hardware Description 7 3 Operator Panel 11 4 Operation 14 5 Programming 20 6 Troubleshooting and Maintenance 23 Appendix A Status Displ...

Страница 2: ...al or conse quential damage or loss whatsoever including but not limited to damage or loss of use of equipment plant or power system cost of capital loss of power additional expenses in the use of exi...

Страница 3: ...from most system voltages available worldwide at 50 or 60 Hertz In addition a period of no control power operation is provided ATC 800 moni tors the condition of the 3 phase line to line voltage and...

Страница 4: ...ce is already available the TDES timer is bypassed Standard Feature 3 Time Delay Emergency to Normal TDEN TDEN delays the transfer to the Normal Source to permit stabiliza tion of the Normal power sou...

Страница 5: ...ual to or above the pickup setting to become available again Underfrequency Monitoring for Source 1 1UFD 1UFP This feature constantly monitors Source 1 for an underfrequency condition When the Source...

Страница 6: ...time delay in the transfer switch Neutral position when both breakers are open This delay takes place when the load is transferred in either direction to prevent excessive in rush currents due to out...

Страница 7: ...Modbus compatible devices A separately mounted communications mod ule will enable the automatic transfer controller to be remotely monitored controlled and programmed via the network Optional Feature...

Страница 8: ...ssages 5 Display LEDs seven LEDs to identify the Display Win dow Information 6 Help Pushbutton provides English language help information in any operational mode 7 Increase Decrease Pushbuttons used i...

Страница 9: ...e communication module PONI to the back of the ATC 800 Figure 3 or in a remote location Since the ATC 800 is always supplied with a communications port a PONI can be easily retrofitted to the ATC 800...

Страница 10: ...kup Range Volts Breaker Switch Style ATS Contactor Style ATS Dropout 2 to 99 of Nominal System Voltage Dropout 2 to 99 of Nominal System Voltage Overvoltage Dropout Range Volts Breaker Switch Style AT...

Страница 11: ...Source 1 is the preferred source choice Source 1 Connected Status LED This LED is lit green if Source 1 is connected This is accom plished by sensing the Source 1 breaker via the S1 closed auxil iary...

Страница 12: ...sfer will occur and the engine will run for the programmed run time 3 3 4 Display Select Pushbutton As the Display Select Pushbutton is pressed and released ATC 800 steps through the following display...

Страница 13: ...le conditions will be shown OVER V The source has risen above the dropout setting and not dropped below the pickup setting UNDER V The source has dropped below the dropout setting and not risen above...

Страница 14: ...ated by the features supplied and their programmed setpoint values It provides a sum mary of ATC 800 s intelligence and supervisory circuits which constantly monitor the condition of both normal and e...

Страница 15: ...g this contact will activate the Emergency Inhibit input If the Emergency Inhibit contact is opened when the load is con nected to the Normal Source no action will be taken if the Normal Source is ava...

Страница 16: ...able up to 10 separate loads The Addressable Relay II must be set for 1200 BAUD rate WATCHDOG feature disabled RELAY PULSE feature disabled Address range from 002 to 00B Under normal condition with so...

Страница 17: ...itions include improper circuit breaker operation motor operator failure and unsuccessful closed or in phase transition An alarm may be reset by simultane ously pressing the Increase and Decrease Push...

Страница 18: ...the TDNE countdown the Emergency Source goes unavailable more than three times Each time TDNE will restart 4 If the Emergency Source is powering the load and it goes unavailable for more than the TDEF...

Страница 19: ...ransition require that both sources be available and synchronized in voltage frequency and phase The frequency difference must be less than the closed transition fre quency difference set point 0 0 to...

Страница 20: ...The Setpoints LED will be lit red and the first programming possibility will appear in the display Use the Step Pushbutton to move from one feature setpoint to another stopping at those in need of rep...

Страница 21: ...ltage1 115 110 Volts 1OVP Source 1 Overvoltage Pickup Volts Breaker Switch Style ATS Contactor Style ATS 103 to Dropout 2 of Nominal System Voltage1 103 to Dropout 2 of Nominal System Voltage1 110 105...

Страница 22: ...ser Minute 0 to 59 Minutes 0 Minutes MANTR Re Transfer Mode 0 Automatic 1 PB Return 0 CTDNE Commitment to Transfer in TDNE 0 Not Committed 1 Committed 0 TMODE Engine Test With Without Load Transfer 0...

Страница 23: ...nutes of inactivity with pushbuttons when changing set points Voltage dropout and pickup setpoints are different than what was programmed Adjusted nominal voltage setpoint Re adjust all dropout and pi...

Страница 24: ...open when Source 1 contactor opened S1 Aux Close contacts did not close when Source 1 Contactor closed Check Source 1 contactor trip wiring Press Increase and Decrease push buttons simultaneously to c...

Страница 25: ...ts Determine the cause and rectify if possible Replace defective com ponents after the cause is determined Step 5 Press the push to close button on the normal switching device Verify whether or not th...

Страница 26: ...the correct line voltage and frequency available at ter minals E1 E2 and E3 Record the readings If YES Proceed to Step 3 If NO Verify that there is output voltage from the generator Step 3 Is the volt...

Страница 27: ...e ATC 800 are de energized These may also be present on some of the terminal blocks Step 3 Before disconnecting any wires from the unit make sure they are individually identified to assure that reconn...

Страница 28: ...Waiting for load voltage to decay before completing the transfer TDP Countdown timing while waiting for a pre transfer acknowledge input TSEQ Countdown timing between sequenced loads NO R xx No commun...

Страница 29: ...Source 2 Connected Time This counter logs time in hours whenever Source 2 is connected to the load Time will start being logged at the time the S2 AUX control input is closed This counter will count u...

Страница 30: ...erator 7 Engine test 8 Manual re transfer 9 Engine Test via communications 10 Go to neutral 11 Program mode 12 Options or setpoints error 13 Emergency Inhibit 14 Go to Emergency 15 Lock out 16 Failed...

Страница 31: ...sly roll over between AM and PM values Minutes By using the Increase or Decrease Pushbuttons the minutes of the day can be adjusted to the present value The number will continuously roll over between...

Страница 32: ...For 1 Phase Sensing with Open Transition FREQ Condition VOLT FREQ Condition VAB VBC VCA FREQ Condition VOLT FREQ Condition Display is blank or a status message appears Note All menu items are not nece...

Страница 33: ...D 2UFD 1UFP 2UFP 1OFD 2OFD 1OFP 2OFP TDN TDNLD LDCY PRF SRC EXER EXLD PEDAY PEH PEMIN MANTR CTDNE TMODE TER TPRE GENNO PHASE TSEQ STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP...

Страница 34: ...breaker Momentarily energize K3 Source 1 becomes unavailable or Engine Test Plant Exerciser Go To Emergency TDES timer times out Send Engine Start signal Energize Gen Start relay TDNE timer times out...

Страница 35: ...eaker Momentarily energize K3 Source 1 becomes unavailable or Go To Emergency TDNE timer times out Open Source 1 breaker Energize K2 Y Source 2 is powering the load Close Source 1 breaker Momentarily...

Страница 36: ...signal Energize Gen Start relay TDNE timer times out Y Source 2 is powering the load Energize Alarm relay Open Source 1 Energize K2 Close Source 2 out of Sync Momentarily energize K4 Source 1 is powe...

Страница 37: ...tion visit www eaton com Instructional Booklet Effective March 2012 Page 37 Instructions for Installation Operation and Maintenance of the Eaton ATC 800 Closed Open Transition Transfer Switch Controll...

Страница 38: ...let Page 38 Effective March 2012 Instructions for Installation Operation and Maintenance of the Eaton ATC 800 Closed Open Transition Transfer Switch Controller For more information visit www eaton com...

Страница 39: ...re information visit www eaton com Instructional Booklet Effective March 2012 Page 39 Instructions for Installation Operation and Maintenance of the Eaton ATC 800 Closed Open Transition Transfer Switc...

Страница 40: ...DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN In no event will Eaton be responsible to the purchaser or user in contract in tort inclu...

Отзывы: