5.4 Programmable Features/
Table 2. Programmable Features/Setpoints
PROGRAMMABLE
FEATURE DISPLAY
DISPLAY
EXPLANATION
SETPOINT
RANGE
FACTORY DEFAULT
VALUE
MEASURE
TDES
Time Delay Engine Start Timer
0 to 120 Seconds
0:03
Minutes: Seconds
TDNE
Time Delay Normal to Emergency Timer
0 to 1800 Seconds
0:00
Minutes: Seconds
TDEN
Time Delay Emergency to Normal Timer
0 to 1800 Seconds
5:00
Minutes: Seconds
TDEC
Time Delay Engine Cool Down Timer
0 to 1800 Seconds
5:00
Minutes: Seconds
NOMF
System Nominal Frequency (Hertz)
50 or 60 Hz
3
60
Hertz
NOMV
System Nominal Voltage (Volts)
120 to 600 Volts
3
480
Volts
1UVD
Source 1 Undervoltage Dropout Range (Volts)
Breaker Switch Style ATS
Contactor Style ATS
50 to 97% of Nominal System Voltage
1
78 to 97% of Nominal System Voltage
1
80%
85%
Volts
2UVD
Source 2 Undervoltage Dropout Range (Volts)
Breaker Switch Style
Contactor Style ATS
50 to 97% of Nominal System Voltage
1
78 to 97% of Nominal System Voltage
1
80%
85%
Volts
1UVP
Source 1 Undervoltage Pickup Range (Volts)
Breaker Switch Style ATS
Contactor Style ATS
(D2%) to 99% of Nominal System Voltage
1
(D2%) to 99% of Nominal System Voltage
1
90%
90%
Volts
2UVP
Source 2 Undervoltage Pickup Range (Volts)
Breaker Switch Style ATS
Contactor Style ATS
(D2%) to 99% of Nominal System Voltage
1
(D2%) to 99% of Nominal System Voltage
1
90%
90%
Volts
1OVD
Source 1 Overvoltage Dropout Range (Volts)
Breaker Switch Style ATS
Contactor Style ATS
105 to 120% Nominal System Voltage
1
105 to 110% Nominal System Voltage
1
115%
110%
Volts
2OVD
Source 2 Overvoltage Dropout Range (Volts)
Breaker Switch Style ATS
Contactor Style ATS
105 to 120% Nominal System Voltage
1
105 to 110% Nominal System Voltage
1
115%
110%
Volts
1OVP
Source 1 Overvoltage Pickup (Volts)
Breaker Switch Style ATS
Contactor Style ATS
103% to (Dropout-2%) of Nominal System Voltage
1
103% to (Dropout-2%) of Nominal System Voltage
1
110%
105%
Volts
2OVP
Source 2 Overvoltage Pickup (Volts)
Breaker Switch Style ATS
Contactor Style ATS
103% to (Dropout-2%) of Nominal System Voltage
1
103% to (Dropout-2%) of Nominal System Voltage
1
110%
105%
Volts
1UFD
Source 1 Underfrequency Dropout (Hertz)
Breaker Switch Style ATS
Contactor Style ATS
90 to 97% of Nominal System Frequency
2
90 to 97% of Nominal System Frequency
2
94%
95%
Hertz
2UFD
Source 2 Underfrequency Dropout (Hertz)
Breaker Switch Style ATS
Contactor Style ATS
90 to 97% of Nominal System Frequency
2
90 to 97% of Nominal System Frequency
2
94%
95%
Hertz
1UFP
Source 1 Underfrequency Pickup (Hertz)
Breaker Switch Style ATS
Contactor Style ATS
(D1 Hz) to 99% of Nominal System Frequency
2
(D1 Hz) to 99% of Nominal System Frequency
2
96%
97%
Hertz
2UFP
Source 2 Underfrequency Pickup (Hertz)
Breaker Switch Style ATS
Contactor Style ATS
(D1 Hz) to 99% of Nominal System Frequency
2
(D1 Hz) to 99% of Nominal System Frequency
2
96%
97%
Hertz
1OFD
Source 1 Overfrequency Dropout (Hertz)
Breaker Switch Style ATS
Contactor Style ATS
103 to 110% of Nominal System Frequency
2
103 to 110% of Nominal System Frequency
2
106%
105%
Hertz
2OFD
Source 2 Overfrequency Dropout (Hertz)
Breaker Switch Style ATS
Contactor Style ATS
103 to 110% of Nominal System Frequency
2
103 to 110% of Nominal System Frequency
2
106%
105%
Hertz
1OFP
Source 1 Overfrequency Pickup (Hertz)
Breaker Switch Style ATS
Contactor Style ATS
101% to (Dropout -1 Hz) of Nominal System Frequency
2
101% to (Dropout -1 Hz) of Nominal System Frequency
2
104%
103%
Hertz
2OFP
Source 2 Overfrequency Pickup (Hertz)
Breaker Switch Style ATS
Contactor Style ATS
101% to (Dropout -1 Hz) of Nominal System Frequency
2
101% to (Dropout -1 Hz) of Nominal System Frequency
2
104%
103%
Hertz
TDN
Time Delay Neutral Timer
0 to 120 Seconds
0:00
Minutes: Seconds
TDNLD
Time Delay Neutral Load Decay
0 = Disabled
1 = Enabled
1
-
LDCY
Load Decay Voltage
2 to 30% of Nominal Voltage
30
Volts