34
Eaton 93PM Integrated Accessory Cabinet-Tie (50 kW and 100 kW IAC-T) Installation and Operation Manual P-164000371—Rev 05
3.
Locate the four 1/2" jacking bolts from the parts kit and install them in the threaded holes in the front and
rear supports as shown in
. Place a floor protector from the parts kit underneath each jacking bolt,
and screw the bolts down against them.
The floor protectors protect the floor from being marred by the jacking bolts.
Figure 9. emoving the Pallet Skids and Supports – Eaton 93PM 50 kW IAC-T or 93PM 100 kW IAC-T
Cabinet
Mounting Bolts
(4 places front)
(4 places rear)
Pallet Skid
Skid Mounting Bolts
(4 places front)
(4 places rear)
Floor Protectors
(2 places front)
(2 places rear)
Right Side
Cabinet Support
Rear Cabinet
Support
Jacking Bolts
(2 places front)
(2 places rear)
Front Cabinet
Support
Cabinet
Support Bolts
(2 places at
each corner)
Left Side
Cabinet Support
WARNING
Do not remove or loosen the cabinet mounting or cabinet support bolts until instructed. If unpacking and
unloading instructions are not closely followed, the cabinet may tip and cause serious injury or death.
4.
Loosen, but do not remove, the skid mounting bolts holding the pallet skids to the front and rear supports,
and to the left and right side supports (see
).
WARNING
RISK OF INSTABILITY. Turning the jacking bolts unevenly may cause the cabinet to become unbalanced. To
prevent tipping the cabinet, raise the cabinet no more than 3 mm (1/8") above the floor (just enough to allow the
removal of the pallet skids). Failure to follow these instructions can result in serious injury or death.
5.
Turn each jacking bolt consecutively, two full turns, until the pallet skids clear the floor by approximately
3 mm (1/8").
Содержание 93PM IAC-T Series
Страница 98: ...P 16400037105 P 164000371 05 ...