Eaton 93PM Integrated Accessory Cabinet-Tie (50 kW and 100 kW IAC-T) Installation and Operation Manual P-164000371—Rev 05
29
Table 17. External Input Power Cable Terminations for the Eaton 93PM 100 kW IAC-T 1+1, 2+0, 2+1, 3+0, 3+1, and 4+0
Parallel Configurations – with MIS and MBP (Continued)
Terminal Function
Termi-
nal
Func-
tion
Number and Size of
Pressure Termination
(AWG or kcmil)
Tightening
Torque Nm
(lb in)
Size Screw and
Type
MBP–
3B
Phase B
1 – 2 stud bus bar
mounting
12.2 (108)
M8 Stud with 13 mm
Hex Nut
MBP–
5C
Phase C
1 – 2 stud bus bar
mounting
12.2 (108)
M8 Stud with 13 mm
Hex Nut
AC Output to Critical Load
Load
Bus A
Phase A
2 – 6–350
42 (375)
5/16” Hex
Load
Bus B
Phase B
2 – 6–350
42 (375)
5/16” Hex
Load
Bus C
Phase C
2 – 6–350
42 (375)
5/16” Hex
Building and Load Ground
TBG
Ground
6 – 14–1/0
5.1 (45)
Slotted
33..22..33
IIA
AC
C--TT IInntteerrffaaccee W
Wiirriinngg P
Prreeppaarraattiioonn
Control wiring for features and options should be connected at the customer interface terminal blocks located
inside the IAC-T.
WARNING
Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is
required.
Read and understand the following notes while planning and performing the installation:
•
Use Class 1 wiring methods (as defined by NEC Article 725) for interface wiring from 30V to 600V. The
wire should be rated for 600V, 1A minimum. 12 AWG maximum wire size.
•
Use Class 2 wiring methods (as defined by NEC Article 725) for interface wiring up to 30V. The wire should
be rated for 24V, 1A minimum.
•
Use twisted-pair wires for each input and return or common.
•
All interface wiring and conduit is to be supplied by the customer.
•
Interface wiring can be installed using the inter-cabinet wiring access pass-through or by routing wiring
through conduit between cabinets.
•
Install the interface wiring in separate conduit from the power wiring.
33..33
IInnssppeeccttiinngg aanndd U
Unnppaacckkiinngg tthhee IIA
AC
C--TT
The cabinet is shipped bolted to a wooden pallet and covered with outer protective packaging material (see
).
NOTE
Startup and operational checks must be performed by an authorized Eaton Customer
Service Engineer, or the warranty terms specified on the product's resources page
become void. See
for details. This service is offered as part of the
sales contract for the UPS. Contact an Eaton service representative in advance (a
minimum two-week notice is required) to reserve a preferred startup date.