Installing Options and Accessories
Eaton
®
Power Xpert
®
9395C UPS Installation and Operation Manual P-164000821—Rev 01
www.eaton.com/powerquality
5-7
10. Restart the UPS. See Chapter 7, “UPS Operating Instructions” for startup instructions.
11. Contact an Eaton service representative for verification and testing of the RIM II and its connections prior
to making connections with J1 through J4 (see Table 5-3 and Figure 5-5).
You can order interface cables separately for connecting to the 15-Pin D-Sub Connectors.
Figure 5-5. J1, J2, J3, and J4 15-Pin D-Sub Connector
NOTE
Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an
authorized Eaton Customer Service Engineer. Contact an Eaton service
representative to schedule a date.
Table 5-3. J1 through J4 Interface Connectors
Status
J1 through J4
Description
UPS AVAILABLE
Pins 1 and 12
Contacts are closed when the UPS is operating in Normal mode or ready to
supply the load.
UPS OFFLINE
Pins 3 and 13
Contacts are open when the UPS is offline. Contacts are closed when the UPS is
operating in Normal mode.
BATTERY WEAK
Pins 5 and 14
Contacts are closed when approximately two minutes of battery time remains
before the critical load is lost.
UTILITY FAILURE
Pins 6 and 15
Contacts are closed when Utility Failure is detected.
15-Pin D
‐
Sub
Connectors
Figure 5
‐
9. J1, J2, J3, and J4 15-Pin D-Sub Connectors