UPS SYSTEM INSTALLATION
Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual
S
164201710 Rev 2
www.eaton.com\powerquality
4-18
3.
Remove the door. Remove the retaining screw located inside the door at the
bottom hinge pivot point, then lift the door off. Retain the hardware for later use.
4.
If installing interface wiring through the left interface entry conduit landing,
proceed to Step 5; otherwise, proceed to Step 7.
5.
If not already accomplished, remove one top screw and two bottom screws
securing the UPS left front panel (see Figure 4‐2 on page 4-4). Lift the panel
straight up to remove it from the panel hanger bracket at the top of the cabinet.
6.
Remove the screws securing the internal safety shield panel and remove the
panel. Retain the hardware for later use.
7.
Terminal block TB3 is accessible on the left side of the X-Slot communication
bay. To gain access to terminal blocks TB1 and TB2 and the interface entry
conduit landing plates, loosen the screws securing the small top internal safety
shield panel and remove the panel. This panel is to the right of the X-Slot
communication bay (see Figure 4‐13 on page 4-19).
8.
Remove the UPS cabinet top interface entry conduit landing plates to drill or
punch holes (see Figure 4‐4 on page 4-8).
9.
Reinstall the interface entry plates and install the conduit.
W
A
R
N
I
N
G
Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is
required.
10.
To locate the appropriate terminals and review the wiring and termination
requirements, see paragraph 3.2.3 on page 3-16, Table 4‐1 on page 4-20,
and
Figure 4‐13
through Figure 4‐16.
11.
Route and connect the wiring.
12.
If wiring TB1 battery interface connections, proceed to paragraph 4.6.2; if wiring
the X-Slot connections only, proceed to paragraph 4.6.3; otherwise, proceed to
Step 13.
13.
Reinstall the small top internal safety shield panel and secure with the cabinet
mounted screws.
14.
Reinstall the front door removed in Step 3 and secure with the retained
hardware.
15.
Close the door and secure the latch.
16.
If removed, reinstall the safety shield panel removed in Step 6. Secure with the
retained hardware.
17.
If removed, reinstall the left front panel removed in Step 5 and secure with the
retained hardware.