1027212
UPS 225 - 275 kVA/300kVAPF0.8
97
Revision E
User’s and Installation Guide
1.
The normal start position should be the following:
2.
Turn ON rectifier switch to connect rectifier input to UPS.
3.
Turn ON Static bypass switch to connect bypass input to UPS:
4.
Perform the UPS start-up procedure (bypass mode) in Section 7.3.2.
5.
Turn S10 switch from bypass position to UPS position to connect UPS output to load.
6.
Perform transfer from bypass to normal mode as described in Section 7.3.12.
Remember to verify the transfer before proceeding to the next step.
UPS is now in Normal mode. See below: