The Advanced Power Management Setup screen allows the selection of
the Advanced Power Management function to be configured. Select
ADVANCED POWER MANAGEMENT SETUP from the System Setup Level 0
menu to display the Advanced Power Management Setup screen. Use the
up or down arrow pushbutton to highlight the desired function, then press
the SELECT pushbutton. To return to the System Setup screen, press the
ESC pushbutton.
APM Load Limit
The APM Load Limit screen sets the maximum load that can be when
drawn from a UPM before additional UPMs are activated. Select APM
LOAD LIMIT from the Advanced Power Management Setup screen to dis-
play the APM Load Limit screen. Use the up or down arrow pushbutton to
set the counter. Press SAVE or ABORT. Once the action is completed, the
Advanced Power Management screen is displayed.
APM UPM Redundancy
The APM UPM Redundancy screen sets the number of UPMs to remain
active to maintain redundancy. Select APM UPM REDUNDANCY from the
Advanced Power Management Setup screen to display the APM UPM
Redundancy screen. Use the up or down arrow pushbutton to set the time.
Press SAVE or ABORT. Once the action is completed, the Advanced Power
Management Setup screen is displayed.
High Alert Timer
The High Alert Timer screen sets the length of time the all UPMs remain
active before transferring back to Advanced Power Management mode.
The time can be set in 10-minute increments from 0 to 990 minutes. Select
HIGH ALERT TIMER from the Advanced Power Management Setup screen
to display the High Alert Timer screen. Use the up or down arrow pushbut-
ton to set the time. Press SAVE or ABORT. Once the action is completed,
the Advanced Power Management Setup screen is displayed.
Variable Module
Management System
The Module Management System Setup screen allows the Variable Mod-
ule Management System function to be configured. Select MODULE MAN-
AGEMENT SYSTEM SETUP from the System Setup Level 0 menu to display
the Module Management System Setup screen. Use the up or down arrow
pushbutton to highlight the desired function, then press the SELECT push-
button. To return to the System Setup screen, press the ESC pushbutton.
System Level 1
Setup
Password
The System Setup Level 1 screen can be used to set the UPS date and time,
set the serial ports, change the Level 1 password, and log out of Level 1. In
addition, the Level 0 functions are available. A password is required to
access the Level 1 functions. To enter the password, select ENTER PASS-
WORD from the System Setup Level 0 menu to display the Enter Password
screen.
Use the left or right arrow pushbutton to select the password character
position. Use the up or down arrow pushbutton to change the password
character. Once the password is entered, press the DONE pushbutton. The
System Setup Level 1 menu screen is displayed. The default password is
L1.
Function Selection
Use the up or down arrow pushbutton to highlight the setup function
screen desired, then press the SELECT pushbutton to display the function
screen. The Level 1 screen times out after 60 minutes or can be logged out
at any time by selecting the LOG OUT function from the menu screen.
Function
Subfunction
Operation