12
UPS 225 - 275 kVA/300kVAPF0.8
1027212
User’s and Installation Guide
Revision E
Table 3-3: Air conditioning or ventilation requirements during full load operation
Ventilation required for cooling air exhaust: approximately 900 liter/sec/225-275kVA unit, + 260 liter/sec
(ISBM).
Figure 3-1. UPS cabinet dimensions (front view)
Rating
Input/output voltage
Heat rejection
BTU/h x 1000
225 kVA
400/400
44.6
275 kVA
300 kVAPF0.8
400/400
54.5