4.2.2 Normal Operation
LED1 and LED2 indicate the GSM signal strength and device status:
LED2 (Green) LED1 (Yellow)
Status
Off
Off
Power is off
On (blink)
On (blink)
Initialising (blinking off every 2s)
Off
On
Signal strength is low CSQ < 11
On
On
Signal strength is OK between 11 and 18
On
Off
Signal strength is good CSQ > 18
ignore
Flash (4Hz)
Call or notification in progress
Flash alt
Flash alt
Self-test in progress (1s each)
Flash alt
Flash alt
Fault condition (250ms each)
Blink 1min
Off
Power saving mode
ignore
Blink 10sec
Engineer on site mode
Flash sync
Flash sync (2Hz)
Test button press for between 5-10s
The signal strength thresholds (low and good) are fixed.
In normal operation the test button can be configured to do multiple things: these include
entering/exiting
“Engineer on site” mode, overriding power saving mode, making a call,
sending a notification and sending a status report.
When TEST is pressed:
Power saving mode will be overridden for 15 minutes
Call to host initialled.** (POINT button CALL)
Notification to users.**(POINT button ALARM)
Hold TEST for 5 seconds: (LED1 and LED2 flash in sync)
Status report to all users.** (OPTION RINGMODE)
E
xit “Engineer on site” mode.** (OPTION SUPPRESS)
Cancel the 15 minute-powered state above.
Hold TEST for 10 seconds:
E
nter “Engineer on site” mode.** (OPTION SUPPRESS)
** Feature can be disabled/enabled by configuration
4.2.3 Radio Module Status
LED3 (Red)
Status
Off
Radio module is off
Flash (1s)
Module is searching for network
Flash (3s)
Module is registered on a network
On
Module is currently in a call
4.3
“Engineer-on-site” Mode
When in this mode, the MesCom will monitor all inputs and allow outputs to be changed but
will not generate notifications or trigger calls to the host. This mode should be used when
any work is being performed on the system.
“Engineer on site” input can be configured to any input - see section 7.7.22.
By default “Engineer on site” mode is entered holding the test button for longer than 10
second and exiting by holding the test button for 5-10 seconds.