10.5.6 Motor bearing monitoring (only three-phase motors)
The motor bearing monitoring function can be set to these values:
•
Active
•
Not active.
When the function is set to
Active
, a counter in the controller will
start counting the mileage of the bearings.
10.5.7 Confirming replacement of motor bearings
(only three-phase motors)
This function can be set to these values:
•
Replaced
•
Nothing done.
When the bearing monitoring function is active, the controller will
give a warning indication when the motor bearings are due to be
replaced. See section
.
When the motor bearings have been replaced, confirm this action
in the above display by pressing "OK".
10.5.8 Standstill heating (only three-phase motors)
The standstill heating function can be set to these values:
•
Active
•
Not active.
When the function is set to Active, an AC voltage will be applied
to the motor windings. The applied voltage will ensure that
sufficient heat is generated to avoid condensation in the motor.
11. External forced-control signals
The motor has inputs for external signals for the forced-control
functions:
• Start/stop of motor.
• Digital function.
11.1 Start/stop input
Functional diagram: Start/stop input:
11.2 Digital inputs
By means of the R100, one of the following functions can be
selected for the digital input:
• Reversing.
• Min. frequency.
• Max. frequency.
• Fault signal resetting.
• External fault.
• Not active.
Functional diagram: Digital function input:
Note
The counter will continue counting even if the
function is switched to Not active, but a warning
will not be given when it is time for replacement.
When the function is switched to Active again,
the accumulated mileage will again be used to
calculate the replacement time.
Start/stop (terminals 2 and 3)
Normal duty
Stop
Note
The terminals 2 and 3 must be connected when
the control panel is used. Otherwise the panel
can only be used for stopping and starting the
motor.
Note
See section
10.3.5 Selection of function for
Digital function
(terminals 1 and 9, terminals 10 and 9, terminals 11 and 9)
Normal duty
Reversing
Min. frequency
Max. frequency
Fault signal
resetting
External fault
Normal
Normal
Min.
Max.
Содержание VT Booster Set
Страница 1: ...VT Booster Set O M Manual...
Страница 3: ...1 Important Health Safety Information Page 3 VT Booster Set...
Страница 10: ...2 System Information Installation and Commissioning Page 10 VT Booster Set...
Страница 11: ...2 1 Booster Set Components VT Booster Set Components Page 11 VT Booster Set...
Страница 12: ...2 2 Control Panel Wiring Diagrams Twin Pump Wiring Diagram Single Phase Page 12 VT Booster Set...
Страница 13: ...Twin Pump Wiring Diagram 3 Phase Page 13 VT Booster Set...
Страница 14: ...VT3 Single Phase Control Panel Wiring Diagram VR VASCO Cold Water Booster Sets Page 14 VT Booster Set...
Страница 15: ...VR VASCO Cold Water Booster Sets Page 15 VT Booster Set...
Страница 16: ...VT3 Three Phase Control Panel Wiring Diagram Page 16 VT Booster Set...
Страница 17: ...Page 16a VT Booster Set...
Страница 23: ...3 User Maintenance and Troubleshooting Page 22 VT Booster Set...
Страница 43: ...Appendix 14...
Страница 50: ...Appendix 21...
Страница 51: ...Appendix 22...
Страница 55: ...Appendix 26...
Страница 56: ...Appendix 27...