English (GB)
20
7.11 Controller (
Controller settings
)
The pumps have a factory default setting of gain (K
p
) and integral
time (T
i
).
However, if the factory setting is not the optimum setting, you can
change the gain and the integral time:
• Set the gain (K
p
) within the range from 0.1 to 20.
• Set the integral-action time (T
i
) within the range from 0.1 to
3600 s.
If you select 3600 s is, the controller will function as a P
controller.
Furthermore, you can set the controller to inverse control.
This means that if you increase the setpoint, the speed will be
reduced. In the case of inverse control, you must set the gain (K
p
)
within the range from -0.1 to -20.
Guidelines for setting of PI controller
The tables below show the recommended controller settings:
L1 = Distance [m] between pump and sensor.
1)
In heating systems, an increase in pump performance will
result in a rise in temperature at the sensor.
2)
In cooling systems, an increase in pump performance will
result in a drop in temperature at the sensor.
L2 = Distance [m] between heat exchanger and sensor.
L2 = Distance [m] between heat exchanger and sensor.
General rules of thumb
If the controller is too slow-reacting, increase K
p
.
If the controller is hunting or unstable, dampen the system by
reducing K
p
or increasing T
i
.
Factory setting
See section
Pump variant
Controller
(Controller settings)
CME
●
CRE, CRIE, CRNE, SPKE, MTRE
●
Constant differential
pressure
K
p
T
i
0.5
0.5
0.5
L1 < 5 m: 0.5
L1 > 5 m: 3
L1 > 10 m: 5
Constant
temperature
K
p
T
i
Heating
system
1)
Cooling
system
2)
0.5
-0.5
10 + 5L2
0.5
-0.5
30 + 5L2
p
p
p
p
ǻS
L1
L1
ǻS
L2
t
L2
t
Constant differential
temperature
K
p
T
i
-0.5
10 + 5L2
Constant flow rate
K
p
T
i
0.5
0.5
Constant pressure
K
p
T
i
0.5
0.5
0.5
0.5
Constant level
K
p
T
i
-2.5
100
2.5
100
t
L2
t
t
t
L2
Q
p
p
L
L
Содержание VT Booster Set
Страница 1: ...VT Booster Set O M Manual...
Страница 3: ...1 Important Health Safety Information Page 3 VT Booster Set...
Страница 10: ...2 System Information Installation and Commissioning Page 10 VT Booster Set...
Страница 11: ...2 1 Booster Set Components VT Booster Set Components Page 11 VT Booster Set...
Страница 12: ...2 2 Control Panel Wiring Diagrams Twin Pump Wiring Diagram Single Phase Page 12 VT Booster Set...
Страница 13: ...Twin Pump Wiring Diagram 3 Phase Page 13 VT Booster Set...
Страница 14: ...VT3 Single Phase Control Panel Wiring Diagram VR VASCO Cold Water Booster Sets Page 14 VT Booster Set...
Страница 15: ...VR VASCO Cold Water Booster Sets Page 15 VT Booster Set...
Страница 16: ...VT3 Three Phase Control Panel Wiring Diagram Page 16 VT Booster Set...
Страница 17: ...Page 16a VT Booster Set...
Страница 23: ...3 User Maintenance and Troubleshooting Page 22 VT Booster Set...
Страница 43: ...Appendix 14...
Страница 50: ...Appendix 21...
Страница 51: ...Appendix 22...
Страница 55: ...Appendix 26...
Страница 56: ...Appendix 27...