• Influence table with Stop at Min.
The setpoint is influenced by a curve made out of two to eight
points. There will be a straight line between the points and a
horizontal line before the first point and after the last point.
If the input signal is below 10 %, the pump will change to
operating mode "Stop".
If the input signal is increased above 15 %, the operating
mode will be changed back to "Normal".
See fig.
Fig. 34
Influence table with Stop at Min. (example with five
points)
• Influence table with Stop at Max.
The setpoint is influenced by a curve made out of two to eight
points. There will be a straight line between the points and a
horizontal line before the first point and after the last point.
If the input signal is above 90 %, the pump will change to
operating mode "Min.".
If the input signal is reduced below 85 %, the operating mode
will be changed back to "Normal".
See fig.
.
Fig. 35
Influence table with Stop at Max. (example with five
points)
Factory setting
See section
7.14 Predefined setpoints
You can set and activate seven predefined setpoints by
combining the input signals to digital inputs 2, 3 and 4 as shown
in the table below.
Set the digital inputs 2, 3 and 4 to "Predefined setpoints" if all
seven predefined setpoints are to be used. You can also set one
or two of the digital inputs to "Predefined setpoints" but this will
limit the number of predefined setpoints available.
Example
Figure
shows how you can use the digital inputs to set up
seven predefined setpoints. Digital input 2 is open and digital
inputs 3 and 4 are closed. If you compare with the table above,
you can see that "Predefined setpoint 6" is activated.
Fig. 36
Principle sketch showing how predefined setpoints
function
If all digital inputs are open, the pump will either stop or run at the
normal setpoint. Set the desired action with Grundfos GO or with
the advanced control panel.
Factory setting
See section
TM
06 41
71 161
5
TM
06 417
2 161
5
100
0
20
0
0.5
0
0
0
4
-50
100 %
3.5 V
5 V
10 V
20 mA
20 mA
204 C
Setpoint influence [%]
External
input
Normal
Min. or
Stop
100
0
80
0
0.5
0
0
0
4
-50
100 %
3.5 V
5 V
10 V
20 mA
20 mA
204 C
Setpoint influence [%]
External
input
Normal
Min. or
Stop
Pump variant
Predefined setpoints
CME
-
CRE, CRIE, CRNE, SPKE, MTRE
●
Digital inputs
Setpoint
2
3
4
0
0
0
Normal setpoint or stop
1
0
0
Predefined setpoint 1
0
1
0
Predefined setpoint 2
1
1
0
Predefined setpoint 3
0
0
1
Predefined setpoint 4
1
0
1
Predefined setpoint 5
0
1
1
Predefined setpoint 6
1
1
1
Predefined setpoint 7
0 = Open contact
1 = Closed contact
TM
06
42
69
18
15
0
1
2
3
4
5
6
7
Digital input 4
Setpoint 1
Setpoint 2
Setpoint 3
Setpoint 4
Setpoint 5
Setpoint 6
Setpoint 7
Digital input 3
Digital input 2
Actual setpoint
Stop
Normal
setpoint
Содержание VT Booster Set
Страница 1: ...VT Booster Set O M Manual...
Страница 3: ...1 Important Health Safety Information Page 3 VT Booster Set...
Страница 10: ...2 System Information Installation and Commissioning Page 10 VT Booster Set...
Страница 11: ...2 1 Booster Set Components VT Booster Set Components Page 11 VT Booster Set...
Страница 12: ...2 2 Control Panel Wiring Diagrams Twin Pump Wiring Diagram Single Phase Page 12 VT Booster Set...
Страница 13: ...Twin Pump Wiring Diagram 3 Phase Page 13 VT Booster Set...
Страница 14: ...VT3 Single Phase Control Panel Wiring Diagram VR VASCO Cold Water Booster Sets Page 14 VT Booster Set...
Страница 15: ...VR VASCO Cold Water Booster Sets Page 15 VT Booster Set...
Страница 16: ...VT3 Three Phase Control Panel Wiring Diagram Page 16 VT Booster Set...
Страница 17: ...Page 16a VT Booster Set...
Страница 23: ...3 User Maintenance and Troubleshooting Page 22 VT Booster Set...
Страница 43: ...Appendix 14...
Страница 50: ...Appendix 21...
Страница 51: ...Appendix 22...
Страница 55: ...Appendix 26...
Страница 56: ...Appendix 27...