English (GB)
3
4. Standard control panel
The pumps are fitted with this control panel as standard.
Fig. 1
Standard control panel
4.1 Setpoint setting
Set the desired setpoint of the pump by pressing
or
. The
light fields on the control panel will indicate the setpoint set.
4.1.1 Pump in constant pressure control mode
The following example applies to a pump in an application where
a pressure sensor gives a feedback to the pump. If the sensor is
retrofitted to the pump, you must set it up manually as the pump
does not automatically register a connected sensor. See section
Figure
shows that the light fields 5 and 6 are activated,
indicating a desired setpoint of 3 bar with a sensor measuring
range from 0 to 6 bar. The setting range is equal to the sensor
measuring range.
Fig. 2
Setpoint set to 3 bar, constant pressure control
4.1.2 Pump in constant-curve control mode
In constant-curve control mode, the pump performance will lie
between the maximum and minimum curve of the pump. See fig.
.
Fig. 3
Pump in constant-curve control mode
Setting to maximum curve:
• Press
continuously to change over to the maximum curve
of the pump (top light field flashes). When the top light field is
on, press
for 3 seconds until the light field starts flashing.
• To change back, press
continuously until the desired
setpoint is indicated.
Example:
Pump set to maximum curve.
Figure
shows that the top light field is flashing, indicating
maximum curve.
Fig. 4
Maximum curve duty
TM
05
48
48
35
12
Pos. Symbol Description
1
Grundfos Eye
Shows the operating status of the pump.
See section
for further
information.
2
-
Light fields for indication of setpoint.
3
Changes the setpoint.
Resets warnings and alarms when one of the
buttons is briefly pressed.
4
Allows radio communication with Grundfos GO
and other products of the same type.
When you try to establish radio communication
between the pump and Grundfos GO or
another pump, the green indicator light in
Grundfos Eye on the pump will flash
continuously. Press
on the pump control
panel to allow radio communication with
Grundfos GO and other products of the same
type.
5
Makes the pump ready for operation/starts and
stops the pump.
Start:
If you press the button when the pump is
stopped, the pump will only start if no other
functions with higher priority have been
enabled. See section
Stop:
If you press the button when the pump is
running, the pump will always be stopped.
When the pump is stopped via this button, the
"Stop" text next to the button will illuminate.
1
2
3
4
5
Stop
TM
05
48
94
35
12
TM
0
5
4
895
2
812
T
M
05
48
96
28
1
2
0
6
3
bar
H
Q
Max.
Min.
H
Q
Содержание VT Booster Set
Страница 1: ...VT Booster Set O M Manual...
Страница 3: ...1 Important Health Safety Information Page 3 VT Booster Set...
Страница 10: ...2 System Information Installation and Commissioning Page 10 VT Booster Set...
Страница 11: ...2 1 Booster Set Components VT Booster Set Components Page 11 VT Booster Set...
Страница 12: ...2 2 Control Panel Wiring Diagrams Twin Pump Wiring Diagram Single Phase Page 12 VT Booster Set...
Страница 13: ...Twin Pump Wiring Diagram 3 Phase Page 13 VT Booster Set...
Страница 14: ...VT3 Single Phase Control Panel Wiring Diagram VR VASCO Cold Water Booster Sets Page 14 VT Booster Set...
Страница 15: ...VR VASCO Cold Water Booster Sets Page 15 VT Booster Set...
Страница 16: ...VT3 Three Phase Control Panel Wiring Diagram Page 16 VT Booster Set...
Страница 17: ...Page 16a VT Booster Set...
Страница 23: ...3 User Maintenance and Troubleshooting Page 22 VT Booster Set...
Страница 43: ...Appendix 14...
Страница 50: ...Appendix 21...
Страница 51: ...Appendix 22...
Страница 55: ...Appendix 26...
Страница 56: ...Appendix 27...