![Dupline G3800 X036 Скачать руководство пользователя страница 33](http://html1.mh-extra.com/html/dupline/g3800-x036/g3800-x036_operation-manual_2540191033.webp)
© 2006 Carlo Gavazzi Industri A/S. All rights reserved
33
The following table gives an overview of all parameters:
Parameter
Description
Function
Select the function of an ordinary measuring sensor, light sensor, wind or
temperature sensor. Basically, all functions operate in the same way.
Disable address
When the channel or flag entered here is activated, all switching operations of
the sensor are disabled.
Control output
Select this function if the sensor are used to activate a relay on the
same address.
If the analog value is to be read by other Dupline modules or interfaces for, then
the contol output should be left un-checked.
Invert limits
This option inverts the switching function in relation to the limit values.
Alternative input
Select this option to get the Analink value from another adress set by the Net No
/ Adress
Sensor input range
The upper and lower limit values of the sensor. For example, the lower value
could be -30 ˚C, while the upper value could be 60 ˚C.
Note:
The entry of each value must be confirmed with the Enter-key.
Net No / Adress
Enter the address, from where the object are to fetch its AnaLink value.
Off < Limit
These are the switching limits of the sensor object. If the option “Invert limits” is
On > Limit
not selected, the limit values appear as described, ie if the values “17.0” and
or
“20.0” are entered, the channel switches off when the actual value is below 17.0
On < Limit
and switches on when the actual value is above 20.0.
Off > Limit
When the limit values are inverted, the sensor switches on when the actual value
is below 17.0 and switches off when the actual value is above 20.0. This setting
is typical for a heating control system.
The limit values are only active, when the address enabling a second pair of limit
values is not switched on.
Note:
The entry of each value must be confirmed with the Enter-key.
Enable limit 2
This option is selected in order to enter a second pair of limit values, for instance
for night setback.
Off < Limit
The second pair of limit values makes it possible to enable a different switching
On > Limit
operation through a different address - “Enabled by address”. If “Enabled by
or
address” is activated, the second pair of limit values will apply instead of the first
On < Limit
pair.
Off > Limit
The second pair of limit values can also be inverted by the “Invert limits” option.
Note:
The entry of each value must be confirmed with the Enter-key.
Enabled by address
When the selected channel or flag is not active, the first pair of limit values will
apply, when it is active, the second pair will apply.
The value can be overwritten at any time and deleted by the Delete-key.
G 3800 X036 Operation Manual
August 2006