1.3. Basic Setup
General description
The text window is for entering general information, eg name of user, date of configuration, reference to
documentation, etc.
No. of Adresses
For selection of the number of channels desired in the system. The minimum is 16, the maximum is 128 in one
Dupline network.
Restore Channel Status upon Power-up
When this function is selected, the Mastergenerator will memorize the channel status on toggle channels and
real-time channels in case of a loss of power. The Mastergenerator will then restore the output status on
these channels when the power comes back.
The option can not be selected, unless the Generator is connected to the PC.
Channel restore Interval (1/10 Seconds)
In order to reduce the total in-rush current when using the "Restore Channel Status upon Power-up" function,
it is possible to define a delay between the activations of outputs. The delay is entered in 1/10 Seconds.
Long Activation time
Set-up the time, for how long a 'Long activation' must last, before an activation takes place.
Some channel objects, are able to be activated by a long activation from another address.
Eg. B2 is a Masterfunction, which reacts on a long activation of B1.
B1 may be a toggle switch for normal on/off.
Now by holding the B1 for the Long activation time, the Masterfunction
on B2 activates, this gives B1 two functions, and saves one push-button.