APT3700N Smart Pressure Transmitter for Nuclear Service Operation Manual M3700N-K01E
40
5.5.2. Quick Manual
Ste
ps
Key Point
Contents
key point detailed contents
Tool Use
1
Unpacking
a) Unpacking Transmitter
2
Model and
inspect
specifications
a) Inspect if the Transmitter is same ordered
and the attached plate with specifications.
3 Storage
a) Not exposed to water and does not have
vibration or impact, it is stored in the
surrounding temperature 25
℃
relative
humidity 65%RH.
4
Correction in the
correction room
a) Range (Zero/Span setting), Unit setting,
Tag setting , Damping Time setting,
Transfer Function setting,
DA dream, other parameter’s setting
HHT,
Pressure
Source(Need)
amperemeter
5
Choosing
Installation place
a) The surrounding temperature is not severe.
b) where corrosion does not appear
according to corrosion substance.
c) where vibration and impact is not rough.
d) maintenance and management is easy.
(While
Engineering)
6
Instrumental
Case
a) Installed in the transmitter that is
manageable.
b) Pressure is not leaked.
(While
Engineering)
7 Electrical
Case
a) D.C. voltage power line is connected.
(Terminal input voltage 12 Vdc ~ 45 Vdc)
b) For HART communication, the Transmitter
Personal Socket of the total resistance is
250 ~ 550 Ohm.
(While
Engineering)
8
Fixation and
Installation
a) Transmitter’s Fixation uses the certain
Bracket
b) fixes the Transmitter not to shake.
(Fixation and
Installation)