APT3700N Smart Pressure Transmitter for Nuclear Service Operation Manual M3700N-K01E
47
6.
6. Specification and Reference Data
6.1. Overview
The following page describes the equipment’s verification and application code of
the case.
6.2. Nuclear Specification
Duon System Co., LTD’s APT3700N Series is IEEE Std. 323-2003 and IEEE Std.
344-2004, and USNRC RG. 1.180 Rev.1 verification was processed, and the processed
result of the Report shown the verification as followed.
G401-635
“Equipment Qualification Test Procedure”
G401-637 “Aging
Analysis
Report”
G401-638
“Environmental Test Report”
G401-639
“EMC test Report”
G401-640
“Seismic Test Report”
6.3. Environment Condition & SEISMIC Condition
Environment condition and Seismic condition of Shin Go Lee nuclear power plant
number 3.4 of the Package NO. J230C’s has been verified by KHNP's 9-183-J230C
technical specification.
6.4. Quality Assurance Program
Electric Industry Techology (KEPIC)’s nuclear power quality guarantee that has been
certified by KEPIC-EN. [Refered to www.kepic.or.kr‘s present business condition]
6.4.1. Nuclear Cleaning
Perform a Cleaning job of the KEPIC Nuclear Energy Quality skill requirement of
QAP-II.1’s water quality requirement.
6.4.2. Hydrostatic and Pneumatic Pressure Testing
Test the design pressure to 1.5 times the pressure in the case of Hydrostatic user, and
Test the design pressure to 1.2 times in the case of Pneumatic Pressure.
6.4.3. Traceability
KEPIC QAP-1 included.