46
9 - START UP PROCEDURE
P07
00..02
= No function is associated
03
= This is an input contact for CH request (e.g. trigger phone).
When contact CN2 is closed and Room Thermostat (RT) requiring heat switches burner on.
Note:
verify heating mode is enabled (winter or heat only mode)
04
= This is an input contact for Low Temperature Thermostat (e.g. floor heating system).
When Low Temperature Thermostat connected on CN2 cuts out, burner switches off and display shows
E178
anomaly.
Note:
verify heating mode is enabled (winter or heat only mode)
05
= This is an input contact for external DHW recirculation pump. When contact CN2 is closed the pump
runs for a specific period.
To enable input it is necessary to set parameter
P04 or P05 = 08
and
P69 = 05
.
Pump will run at
P19
minutes (Summer/Winter mode or Only Winter mode) or
P19/2
minutes (only
Summer mode).
00
P09
Manufacturer information
--
P10
Heating setpoint setting OT / RT (Open Therm / Room Thermostat 120V~)
00
= with Remote Control (RC) connected, temperature request is RC setpoint
01
= Temperature Request is highest set point between RC and PCB
02
= Temperature request is RU setpoint. The RT enable the gas boiler operates
00
P11..P12
Manufacturer information
--
P13
Max. heating output
(0-100%)
100
80
P14
DHW max. output
(0-100%)
100
P15
Min. heating output
(0-100%)
00
P16
Maximum CH setpoint (°C)
00
= 176°F (80°C)
01
= 113°F (45°C)
00
P17
Pump overrun time in heating mode
(01-240 minutes)
03
P18
Burner ignition delay in CH mode
(00-10 minutes) - 00=10 seconds
03
P19
Manufacturer information
07
P20
Pump overrun time in DHW mode
(seconds)
30
P21
Anti-legionellosis function
00
= Disabled -
01
= Enabled
00
P22
Manufacturer information
(set “
22
” to display parameters P71 and P72)
00
P23
Maximum DHW setpoint temperature
113°-140°F (45°-60°C), Default 49 = 120°F
49
P24
Manufacturer information
35
P25
No water safety device
00
P26..P31
Manufacturer information
--
P32..P41
Diagnostics (See SERVICE Instructions)
--
P44
Temperature unit setting
00
= °C
01
= °F
01
P71 * P
Maximum fan speed
--
P72 *
Minimum fan speed
--
*
See Tables : SECTION 12.2 - Parameters Setting For High Altitude.
NOTE
:
To scroll to parameter
P71
and
P72
it is necessary to set
P22
to
22
before scrolling up to the parameter.
P06
Outdoor temperature sensor input configuration
00
= with outdoor temperature sensor connected, external temperature value has influence to calculate
heating flow temperature setpoint
01
= with outdoor temperature sensor connected, display shows external temperature value (no influence)
02…05
= no function is associated
00
9.14 Description Of Parameters: Factory Settings conti.
FACTORY SETTINGS
125-165
150-205
240011947 REV B, [03/31/2018]
Содержание DCB-125
Страница 2: ...DCC 205 ...
Страница 4: ...DCB 165 ...
Страница 65: ...61 APPENDIX A WIRING DIAGRAMS A 1 MODELS 125 Heat Only 240011947 REV B 03 31 2018 ...
Страница 66: ...62 APPENDIX A WIRING DIAGRAMS A 2 MODELS 165 Heat Only 240011947 REV B 03 31 2018 ...
Страница 67: ...63 APPENDIX A WIRING DIAGRAMS A 3 MODELS 150 Combi 240011947 REV B 03 31 2018 ...
Страница 68: ...64 APPENDIX A WIRING DIAGRAMS A 4 MODELS 205 Combi 240011947 REV B 03 31 2018 ...
Страница 69: ...65 NOTES 240011947 REV B 03 31 2018 ...
Страница 70: ...66 NOTES 240011947 REV B 03 31 2018 ...
Страница 81: ...9 125 WITH ZONE CIRCULATOR PUMPS 125 with Zone Circulator Pumps PN 240011430 REV G 03 31 18 ...
Страница 84: ...12 125 WITH ZONE VALVES PIPING DIAGRAM 125 with Zone Valves PN 240011430 REV G 03 31 18 ...
Страница 87: ...15 165 WITH ZONE CIRCULATOR PUMPS PIPING DIAGRAM 165 with Zone Circulator Pumps PN 240011430 REV G 03 31 18 ...
Страница 90: ...18 165 with Zone Valves 165 WITH ZONE VALVES PIPING DIAGRAM PN 240011430 REV G 03 31 18 ...
Страница 94: ...22 150 205 WITH ZONE PUMPS WIRING DIAGRAM 150 205 With Zone Pumps PN 240011430 REV G 03 31 18 ...
Страница 95: ...23 150 205 with Zone Valves 150 205 WITH ZONE VALVES PIPING DIAGRAM PN 240011430 REV G 03 31 18 ...
Страница 96: ...24 150 205 WITH ZONE VALVES WIRING DIAGRAM 150 205 With Zone Valves PN 240011430 REV G 03 31 18 ...
Страница 102: ...30 MODEL 125 Heat Only 125 HEAT ONLY WIRING DIAGRAM PN 240011430 REV G 03 31 18 ...
Страница 103: ...31 MODEL 165 Heat Only 165 HEAT ONLY WIRING DIAGRAM PN 240011430 REV G 03 31 18 ...
Страница 104: ...32 MODEL 150 Combi 150 COMBI WIRING DIAGRAM PN 240011430 REV G 03 31 18 ...
Страница 105: ...33 MODEL 205 Combi 205 COMBI WIRING DIAGRAM PN 240011430 REV G 03 31 18 ...
Страница 110: ...38 Low Water Cutoff Detail LOW WATER CUTOFF NO NO YES PN 240011430 REV G 03 31 18 ...
Страница 111: ...39 NOTES PN 240011430 REV G 03 31 18 ...
Страница 112: ......
Страница 115: ......
Страница 116: ......