60708-151
2080-10
12
*************
***** WARNING *****
*************
EQUIPMENT DAMAGE
- DO NOT DEPRESS THE SAFETY
LATCHING RELAY BUTTON FOR OVER 10 SECONDS. IF THE
LIGHT HAS NOT GONE OUT IN 10 SECONDS IT INDICATES
THAT EITHER THE ENGINE HAS NOT BUILT OIL PRESSURE
OR THE COOLANT TEMPERATURE HAS EXCEEDED THE
ALLOWABLE MAXIMUM.
4. After the engine is up an running the circuit breaker can be
closed to power your loads. During periods of very cold operation
it is best to let the engine warm up for a few seconds before
applying the load.
5. When stopping the unit it is best to turn off all the loads before
turning the Start Switch to the off position. This prevents your
loads from getting low voltage while still running during unit
shutdown.
If for some reason during operation the oil pressure should drop
below the allowable oil pressure or the water temperature should
exceed allowable level the Safety Latching Relay button will pop-
out and the unit will shutdown. You will also get a check engine
light at this time.
If you find the unit stopped with the relay button popped-out, it
could have been caused by either low oil pressure or high water
temperature.
TROUBLESHOOTING TABLES
ENGINE WILL NOT CRANK WITH GENERATOR
RUN PUSH-BUTTON DEPRESSED.
1. Low/dead battery.
2. Blown DC fuses 2 amp or 25 amp.
3. Defective DSE702.
4. Loose or dirty battery terminals.
5. Defective starter.
6. Defective start solenoid.
7. Locked up engine genset.
ENGINE CRANKS BUT WILL NOT START
1. Improper fuel delivery to the unit.
2. Fuel supply shut off.
3. Fuel tank empty.
4. Air in the fuel system.
5. Engine fuel solenoid has not opened.
6. Defect fuel pump.
ENGINE STARTS AND THEN STOPS AND ALARM LIGHT
COMES ON
1. Engine oil pressure is low.
2. Engine has high water temperature.
3. Engine has overspeed.
ENGINE WILL NOT COME UP TO SPEED AFTER IT
STARTS
1. Insufficient fuel volume getting to the unit.
a. Too small of fuel line.
b. Fuel racks not opened properly.
2. Governor is defective.
3. AC short in generator components.
NO AC OUTPUT FROM GENERATOR
1. Defective diode.
2. Defective voltage regulator.
3. Defective rotor.
4. Defective stator.
5. Defective exciter rotor.
6. Defective exciter stator.
7. AC short in the output leads.
8. Defective/open generator output breaker.
9. Wiring error.
Содержание WINPOWER DE20I4
Страница 10: ...60708 151 2080 10 CONTROL BOX AC WIRING WARNING THESE GENERATORS ARE WIRED WITH A FLOATING NEUTRAL...
Страница 15: ...2080 10 60708 151 13 DE30 OUTLINE DRAWING DE20 OUTLINE DRAWING...
Страница 16: ...60708 151 2080 10 14 DE45 DE60 OUTLINE DRAWING...
Страница 17: ...2080 10 60708 151 15 DE20 DE30 DC SCHEMATIC FOR DSE702...
Страница 18: ...60708 151 2080 10 16 DE45 DE65 DC SCHEMATIC FOR DSE702...
Страница 19: ...2080 10 60708 151 17 START CONTROL PANEL ENGINE WIRING HARNESS DE20 DE30 KEY START SCHMATIC...
Страница 20: ...60708 151 2080 10 18 START CONTROL PANEL ENGINE WIRING HARNESS DE45 DE65 KEY START SCHMATIC...
Страница 21: ...2080 10 60708 151 19 THREE PHASE AC WIRING HIGH AND LOW WYE...
Страница 22: ...60708 151 2080 10 20 THREE PHASE AC WIRING DELTA SINGLE PHASE AC WIRING...
Страница 24: ...225 S Cordova ave Le Center MN 56057 507 357 6831 www winpowerinc com 60708 151 2080 10...