DTI Dyna Technology WINPOWER DE20I4 Скачать руководство пользователя страница 11

2080-10

60708-151

Minimum Conductor Sizes between the Generator and the load. 

Based on wire type and temperature rating. Wire has been 

derated for 40

C ambient temperatures.

 

 

 

 

     Cu Conductor 

      Al Conductor

 

 

 

C/B 

        Wire Temperature Rating

kW  Voltage  PH  Amp  750C 

900C 

750C 

900C 

20  120/240  1 

85 

#3 AWG  #4 AWG  #1 AWG 

#2 AWG

20  120/208  3 

70 

#4 AWG  #6 AWG  #3 AWG 

#4 AWG

20  120/240  3 

60 

#4 AWG  #6 AWG  #3 AWG 

#4 AWG

20  277/480  3 

30 

#8 AWG  #8 AWG  #8 AWG 

#8 AWG

30  120/240  1  125 

1/0 AWG  #1 AWG  3/0 AWG  2/0 AWG

30  120/208  3  100 

#2 AWG  #3 AWG  1/0 AWG  #1 AWG

30  120/240  3 

90 

#2 AWG  #3 AWG  1/0 AWG  #2 AWG

30  277/480  3 

45 

#6 AWG  #8 AWG  #4 AWG 

#6 AWG

45  120/240  1  175 

3/0 AWG  2/0 AWG  250 MCM  4/0 AWG

45  120/208  3  150 

2/0 AWG  1/0 AWG  3/0 AWG  2/0 AWG

45  120/240  3  125 

1/0 AWG  #1 AWG  3/0 AWG  2/0 AWG

45  277/480  3 

60 

#4 AWG  #6 AWG  #3 AWG 

#4 AWG

65  120/240  1  250 

300 MCM  250 MCM  500 MCM  350 MCM 

65  120/208  3  225 

250 MCM  4/0 AWG  400 MCM  300 MCM

65  120/240  3  200 

4/0 AWG  3/0 AWG  300 MCM  250 MCM

65  277/480  3  100 

#2 AWG  #3 AWG  1/0 AWG  #1 AWG

For additional information on wire sizing refer to table 310-16 of 

the National Electrical Code ANSI/NFPA 70..  

For additional information on wire sizing refer to table 310-16 of 

the National Electrical Code ANSI/NFPA 70.

Ground Lug

, These ground lugs are bonded to ground and are 

provided for you to connect your ground wire from the transfer 

switch to. The lugs on the 65 kW will handle wire sizes #6 AWG to 

300 MCM  and should be torqued to 250 in. lbs. The lugs on the 

20 through 45 kW will accommodate #10 AWG to 2/0 AWG  and 

should be torqued to 200 in. lbs.

    *************

*****  WARNING  *****

    *************

PERSONAL DANGER - 

These unit are shipped with a 

FLOATING NEUTRAL. If you not connecting to an existing 

power system you must install a neutral to ground bond in 

the generator connection box.  If your system already has a 

neutral to ground bond then you must run a separate ground 

lead to that location.  For additional questions refer to the 

current National Electric Code on grounding.

   *************

*****  WARNING  *****

    ************* 

EQUIPMENT DAMAGE

 - 

When installing a Three Phase 240 

volt system be sure you know which lead is the high voltage 

“wild” leg (208 Volt line to neutral). The generator normally 

carries the high voltage on the G2 lead.

 All wires should be installed in flexible conduit.  ( A knockout 

covered by a rubber plug is provided in the control box).

  

ENGINE CONTROL PANEL 

LAYOUT DSE702

A - 2 AMP FUSE

 This fuse supplies the DSE702 controller 

120 Volt AC.  This tells the controller that the unit is running. 

(Replacement AGC-2A-250V)

B -  2 AMP FUSE 

-This fuse is in the 12 volt DC power supply for 

the DSE702 controller circuitry on the board. It also supplies the 

voltage for the two or three control relay in the control cabinet. 

(Replacement AGC-2A-250V)

C - 25 AMP FUSE

- This fuse provides the 12 volt DC voltage 

for the relay controlling the starting, fuel, and glow plugs. 

(Replacement AGC-25A-250V)

D - DSE702 Start Controller

 - See Description Later

A

B

D

C

Содержание WINPOWER DE20I4

Страница 1: ...INSTALLATION AND OPERATIONS MANUAL DE20I4 DE30I4 DE45I4 DE65I4 INSTALLATION AND OPERATIONS MANUAL MODELS DE20I4 DE30I4 DE45I4 DE65I4 DSE702 START MODULE AND MANUAL KEY START...

Страница 2: ...L NUMBER________________________ M Spec ______________________________ PURCHASE DATE_______________________ DEALER_______________________________ TABLE OF CONTENTS INTRODUCTION i GUIDE TO PRODUCT SAFE...

Страница 3: ...into the earth 2 FIRE HAZARD Diesel fuel presents a hazard of possible explosion and or fire a Do not smoke or use open flame near the generator set b Keep a fire extinguisher nearby and know its prop...

Страница 4: ...Muffler Standard Stop System Key Emergency Fuel Consumption full Load 2 6 Gal hour Owner Must Provide Fuel ASTM D 975 1D or 2D EN590 or equivalent See engine manual for additional fuel types specifica...

Страница 5: ...nd replacement parts Be sure to have the main WINPOWER unit data plate information recorded inside the front cover of this manual for future reference and for identification whenever requesting field...

Страница 6: ...hysical damage locate and check the following items packed with the unit a Owner s operators manual b Engine manufacturer s instruction manual c Battery hold down brackets hardware d Unit components o...

Страница 7: ...should be 1 1 2 time as large as the area of the radiator face to prevent back pressure In addition to a hot air discharge you must plan for a fresh air intake opposite the radiator discharge These fr...

Страница 8: ...tive ground system If you are using the truck batteries to start these units you may have to disable the charging system to keep it from interfering with the vehicle charging system Installation and s...

Страница 9: ...leted in accordance with the Nation Electric Code as well as any state or local codes You must pay particular attention to wire size requirement for the amperage of service you are dealing with The ta...

Страница 10: ...60708 151 2080 10 CONTROL BOX AC WIRING WARNING THESE GENERATORS ARE WIRED WITH A FLOATING NEUTRAL...

Страница 11: ...h to The lugs on the 65 kW will handle wire sizes 6 AWG to 300 MCM and should be torqued to 250 in lbs The lugs on the 20 through 45 kW will accommodate 10 AWG to 2 0 AWG and should be torqued to 200...

Страница 12: ...detects that the engine coolant temperature has exceeded the limit the coolant temperature switch after the Safety On timer has expired and a shutdown is initiated NOTE All warnings are reset but tur...

Страница 13: ...ours of engine operation D 25 AMP FUSE This fuse protect all the DC wiring in the engine control panel and on the engine If this Fuse if blown nothing will work on the engine E SAFETY LATCHING RELAY T...

Страница 14: ...nit stopped with the relay button popped out it could have been caused by either low oil pressure or high water temperature TROUBLESHOOTING TABLES ENGINE WILL NOT CRANK WITH GENERATOR RUN PUSH BUTTON...

Страница 15: ...2080 10 60708 151 13 DE30 OUTLINE DRAWING DE20 OUTLINE DRAWING...

Страница 16: ...60708 151 2080 10 14 DE45 DE60 OUTLINE DRAWING...

Страница 17: ...2080 10 60708 151 15 DE20 DE30 DC SCHEMATIC FOR DSE702...

Страница 18: ...60708 151 2080 10 16 DE45 DE65 DC SCHEMATIC FOR DSE702...

Страница 19: ...2080 10 60708 151 17 START CONTROL PANEL ENGINE WIRING HARNESS DE20 DE30 KEY START SCHMATIC...

Страница 20: ...60708 151 2080 10 18 START CONTROL PANEL ENGINE WIRING HARNESS DE45 DE65 KEY START SCHMATIC...

Страница 21: ...2080 10 60708 151 19 THREE PHASE AC WIRING HIGH AND LOW WYE...

Страница 22: ...60708 151 2080 10 20 THREE PHASE AC WIRING DELTA SINGLE PHASE AC WIRING...

Страница 23: ...of merchantability and fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINPOWER liable for incidental or consequent...

Страница 24: ...225 S Cordova ave Le Center MN 56057 507 357 6831 www winpowerinc com 60708 151 2080 10...

Отзывы: