DSE702 CONTROL

A - KEY SWITCH

 -Turns the controller on and off.

B - STOP/RESET 

- With key in this position the unit is shut off.  

This position also resets the controller if it has gone into fault.

C - RUN POSITION

  - The key in this position will allow the glow 

plugs to be turned on and the unit to be started.

D - START BUTTON 

-  When this button is depress the starter is 

engaged and will stay engaged until the button is released.

E - GLOW PLUG SWITCH 

- When this button is depress the glow 

plug circuit is activated, operating the glow plugs on the engine.  

When it is released the glow plug circuit is disconnected.

F - GLOW PLUG INDICATOR LED

 - When the glow plug switch 

is depressed this LED will light up indicating the circuit has been 

activated.

G - RUNNING TIME METER

 - This digital display will track the 

hours of operation of the engine generator set.  This meter runs 

any time the key is in the run position.

H - OVERSPEED/UNDERSPEED LED

 -  Overspeed: This light 

will illuminate if the engine speed exceed the preset trip point 

(14% above nominal frequency or about 68 Hz) and a shutdown 

is initiated.  The overspeed is not delayed, it is an immediate 

shutdown.   Underspeed: 

 This light will flash if the engine speed 

falls below 20Hz after the Safety On* time has expired and a 

shutdown is initiated.

J - FAIL TO START

 - Not used on the manual start controller.

K - LOW OIL PRESSURE

 - This light will illuminate if the module 

detects that the engine oil pressure has fallen below the oil 

pressure switch setting (15 psi) after the Safety On* time has 

expired and a shutdown is initiated.

M - BATTERY CHARGE FAILURE 

- Not used in this application.

N - HIGH WATER TEMPERATURE

 -  This light will illuminat if the 

module detects that the engine coolant temperature has exceeded 

the limit the coolant temperature switch after the Safety On* timer 

has expired and a shutdown is initiated.

NOTE:  All warnings are reset but turning the key to off 

position.

* SAFETY ON TIMER

 - The safety on delay on this controller is 

10 seconds.  Should and fault condition still be detected after this 

10 second delay the engine will shutdown and fault code will be 

illuminated.

INITIAL START UP 

   *************

*****  WARNING  *****

    ************* 

EQUIPMENT DAMAGE

 - 

DO NOT jump start these engine 

generator  sets. Starting these units on a low battery or 

jump starting them will cause damage to the engine control 

module.

Use the following check list to verify correct installation before 

starting the engine:

 

1.  Engine oil.  Fill as required with proper grade/qty.

 

2.  Engine coolant.  Fill as required with proper mixture.

 

3.  Unit mounting base properly bolted down.

 

4.  Clearance for service and maintenance on all sides.

 

5.  Proper fuel line material and size. 

 

6.  All fuel line connections tight.

 

7.  Battery connections clean and tight.

  

8.  Battery fully charged.

  

9.  All AC and DC wiring installed and properly protected.

After completing the above checklist, the engine-generator set is 

ready for the initial start-up test.

STARTING PROCEDURE

MANUAL MODE

    ****************

*****  WARNING  *****

      **************** 

EQUIPMENT DAMAGE 

-

 BEFORE ATTEMPTING TO START 

THIS UNIT COMPLETE YOUR PRE-START CHECKLIST AND 

INSURE THE GENERATOR MAINLINE CIRCUIT BREAKER IS 

IN THE PROPER POSITION PRIOR TO STARTING.  STARTING 

THIS UNIT WITHOUT IT PROPERLY CONNECTED CAN 

CAUSE SERIOUS PERSONAL INJURY OR EQUIPMENT 

DAMAGE.

1.  Rotate the key (A) to the run position (C).

2.  If your unit is equipped with glow plugs depress the glow plug 

button (E) for about 10 seconds.

3.  Depress the start button (D) to engage the start circuit.  The 

starter should engage and the unit will start.  Once the unit has 

started release the start button to disengage the starter.

H

J

K

D

G

N

M

F

B

A

C

E

Содержание WINPOWER DE20I4

Страница 1: ...INSTALLATION AND OPERATIONS MANUAL DE20I4 DE30I4 DE45I4 DE65I4 INSTALLATION AND OPERATIONS MANUAL MODELS DE20I4 DE30I4 DE45I4 DE65I4 DSE702 START MODULE AND MANUAL KEY START...

Страница 2: ...L NUMBER________________________ M Spec ______________________________ PURCHASE DATE_______________________ DEALER_______________________________ TABLE OF CONTENTS INTRODUCTION i GUIDE TO PRODUCT SAFE...

Страница 3: ...into the earth 2 FIRE HAZARD Diesel fuel presents a hazard of possible explosion and or fire a Do not smoke or use open flame near the generator set b Keep a fire extinguisher nearby and know its prop...

Страница 4: ...Muffler Standard Stop System Key Emergency Fuel Consumption full Load 2 6 Gal hour Owner Must Provide Fuel ASTM D 975 1D or 2D EN590 or equivalent See engine manual for additional fuel types specifica...

Страница 5: ...nd replacement parts Be sure to have the main WINPOWER unit data plate information recorded inside the front cover of this manual for future reference and for identification whenever requesting field...

Страница 6: ...hysical damage locate and check the following items packed with the unit a Owner s operators manual b Engine manufacturer s instruction manual c Battery hold down brackets hardware d Unit components o...

Страница 7: ...should be 1 1 2 time as large as the area of the radiator face to prevent back pressure In addition to a hot air discharge you must plan for a fresh air intake opposite the radiator discharge These fr...

Страница 8: ...tive ground system If you are using the truck batteries to start these units you may have to disable the charging system to keep it from interfering with the vehicle charging system Installation and s...

Страница 9: ...leted in accordance with the Nation Electric Code as well as any state or local codes You must pay particular attention to wire size requirement for the amperage of service you are dealing with The ta...

Страница 10: ...60708 151 2080 10 CONTROL BOX AC WIRING WARNING THESE GENERATORS ARE WIRED WITH A FLOATING NEUTRAL...

Страница 11: ...h to The lugs on the 65 kW will handle wire sizes 6 AWG to 300 MCM and should be torqued to 250 in lbs The lugs on the 20 through 45 kW will accommodate 10 AWG to 2 0 AWG and should be torqued to 200...

Страница 12: ...detects that the engine coolant temperature has exceeded the limit the coolant temperature switch after the Safety On timer has expired and a shutdown is initiated NOTE All warnings are reset but tur...

Страница 13: ...ours of engine operation D 25 AMP FUSE This fuse protect all the DC wiring in the engine control panel and on the engine If this Fuse if blown nothing will work on the engine E SAFETY LATCHING RELAY T...

Страница 14: ...nit stopped with the relay button popped out it could have been caused by either low oil pressure or high water temperature TROUBLESHOOTING TABLES ENGINE WILL NOT CRANK WITH GENERATOR RUN PUSH BUTTON...

Страница 15: ...2080 10 60708 151 13 DE30 OUTLINE DRAWING DE20 OUTLINE DRAWING...

Страница 16: ...60708 151 2080 10 14 DE45 DE60 OUTLINE DRAWING...

Страница 17: ...2080 10 60708 151 15 DE20 DE30 DC SCHEMATIC FOR DSE702...

Страница 18: ...60708 151 2080 10 16 DE45 DE65 DC SCHEMATIC FOR DSE702...

Страница 19: ...2080 10 60708 151 17 START CONTROL PANEL ENGINE WIRING HARNESS DE20 DE30 KEY START SCHMATIC...

Страница 20: ...60708 151 2080 10 18 START CONTROL PANEL ENGINE WIRING HARNESS DE45 DE65 KEY START SCHMATIC...

Страница 21: ...2080 10 60708 151 19 THREE PHASE AC WIRING HIGH AND LOW WYE...

Страница 22: ...60708 151 2080 10 20 THREE PHASE AC WIRING DELTA SINGLE PHASE AC WIRING...

Страница 23: ...of merchantability and fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINPOWER liable for incidental or consequent...

Страница 24: ...225 S Cordova ave Le Center MN 56057 507 357 6831 www winpowerinc com 60708 151 2080 10...

Отзывы: