DSE702 CONTROL
A - KEY SWITCH
-Turns the controller on and off.
B - STOP/RESET
- With key in this position the unit is shut off.
This position also resets the controller if it has gone into fault.
C - RUN POSITION
- The key in this position will allow the glow
plugs to be turned on and the unit to be started.
D - START BUTTON
- When this button is depress the starter is
engaged and will stay engaged until the button is released.
E - GLOW PLUG SWITCH
- When this button is depress the glow
plug circuit is activated, operating the glow plugs on the engine.
When it is released the glow plug circuit is disconnected.
F - GLOW PLUG INDICATOR LED
- When the glow plug switch
is depressed this LED will light up indicating the circuit has been
activated.
G - RUNNING TIME METER
- This digital display will track the
hours of operation of the engine generator set. This meter runs
any time the key is in the run position.
H - OVERSPEED/UNDERSPEED LED
- Overspeed: This light
will illuminate if the engine speed exceed the preset trip point
(14% above nominal frequency or about 68 Hz) and a shutdown
is initiated. The overspeed is not delayed, it is an immediate
shutdown. Underspeed:
This light will flash if the engine speed
falls below 20Hz after the Safety On* time has expired and a
shutdown is initiated.
J - FAIL TO START
- Not used on the manual start controller.
K - LOW OIL PRESSURE
- This light will illuminate if the module
detects that the engine oil pressure has fallen below the oil
pressure switch setting (15 psi) after the Safety On* time has
expired and a shutdown is initiated.
M - BATTERY CHARGE FAILURE
- Not used in this application.
N - HIGH WATER TEMPERATURE
- This light will illuminat if the
module detects that the engine coolant temperature has exceeded
the limit the coolant temperature switch after the Safety On* timer
has expired and a shutdown is initiated.
NOTE: All warnings are reset but turning the key to off
position.
* SAFETY ON TIMER
- The safety on delay on this controller is
10 seconds. Should and fault condition still be detected after this
10 second delay the engine will shutdown and fault code will be
illuminated.
INITIAL START UP
*************
***** WARNING *****
*************
EQUIPMENT DAMAGE
-
DO NOT jump start these engine
generator sets. Starting these units on a low battery or
jump starting them will cause damage to the engine control
module.
Use the following check list to verify correct installation before
starting the engine:
1. Engine oil. Fill as required with proper grade/qty.
2. Engine coolant. Fill as required with proper mixture.
3. Unit mounting base properly bolted down.
4. Clearance for service and maintenance on all sides.
5. Proper fuel line material and size.
6. All fuel line connections tight.
7. Battery connections clean and tight.
8. Battery fully charged.
9. All AC and DC wiring installed and properly protected.
After completing the above checklist, the engine-generator set is
ready for the initial start-up test.
STARTING PROCEDURE
MANUAL MODE
****************
***** WARNING *****
****************
EQUIPMENT DAMAGE
-
BEFORE ATTEMPTING TO START
THIS UNIT COMPLETE YOUR PRE-START CHECKLIST AND
INSURE THE GENERATOR MAINLINE CIRCUIT BREAKER IS
IN THE PROPER POSITION PRIOR TO STARTING. STARTING
THIS UNIT WITHOUT IT PROPERLY CONNECTED CAN
CAUSE SERIOUS PERSONAL INJURY OR EQUIPMENT
DAMAGE.
1. Rotate the key (A) to the run position (C).
2. If your unit is equipped with glow plugs depress the glow plug
button (E) for about 10 seconds.
3. Depress the start button (D) to engage the start circuit. The
starter should engage and the unit will start. Once the unit has
started release the start button to disengage the starter.
H
J
K
D
G
N
M
F
B
A
C
E
Содержание WINPOWER DE20I4
Страница 10: ...60708 151 2080 10 CONTROL BOX AC WIRING WARNING THESE GENERATORS ARE WIRED WITH A FLOATING NEUTRAL...
Страница 15: ...2080 10 60708 151 13 DE30 OUTLINE DRAWING DE20 OUTLINE DRAWING...
Страница 16: ...60708 151 2080 10 14 DE45 DE60 OUTLINE DRAWING...
Страница 17: ...2080 10 60708 151 15 DE20 DE30 DC SCHEMATIC FOR DSE702...
Страница 18: ...60708 151 2080 10 16 DE45 DE65 DC SCHEMATIC FOR DSE702...
Страница 19: ...2080 10 60708 151 17 START CONTROL PANEL ENGINE WIRING HARNESS DE20 DE30 KEY START SCHMATIC...
Страница 20: ...60708 151 2080 10 18 START CONTROL PANEL ENGINE WIRING HARNESS DE45 DE65 KEY START SCHMATIC...
Страница 21: ...2080 10 60708 151 19 THREE PHASE AC WIRING HIGH AND LOW WYE...
Страница 22: ...60708 151 2080 10 20 THREE PHASE AC WIRING DELTA SINGLE PHASE AC WIRING...
Страница 24: ...225 S Cordova ave Le Center MN 56057 507 357 6831 www winpowerinc com 60708 151 2080 10...