2080-10

60708-151

11

4.  If the start button is release before the engine starts or the unit  

does not stay running the key switch (A) has to be turn to the off 

position and back to the run position before the starter can be 

reengage using the start button (D).  This protects the starter from 

accidently being engage with the unit running.

5.  Once the unit is running and the safety on time has elapsed the 

engine monitoring switches are active.

6.  If the unit should shut down and display a fault light (H,K or N) 

clear the fault before attempting to restart the unit.

7. After the engine is up an running the circuit breaker can be 

closed to power your loads.  During periods of very cold operation 

it is best to let the engine warm up for a few seconds before 

applying the load.

8.  When stopping the unit it is best to turn off all the loads before 

turning the key switch to the off (B) position.  This prevents your 

loads from getting low voltage while still running during unit 

shutdown.

ENGINE CONTROL PANEL 

LAYOUT MANUAL KEY START

 

A-   FOUR POSITION START SWITCH 

1.   Prehea

t - This position is used on the DE20 and DE30 

only.  With the switch in this position the  glow plugs on the 

engine are activated.

2.  OFF 

- In this position all power to the engine is  

 

turn off and the engine is stopped.

3.  RUN 

- With the switch in this position the fuel solenoid 

and the fuel pump on the engine are activated. A 12 Volt 

signal is also being sent to the voltage regulator on the 

engine alternator to activate it.

4.  START 

- This position on the switch will  activate the 

starter on the engine to start it.

B.  CHECK ENGINE LIGHT

 - This light will come on when the 

low oil pressure switch or the high water temperature sensor 

switches have  been activated on the engine.  This light will also 

come on when you go to start the engine, and stay on until the 

engine has built sufficient oil pressure to open the low oil pressure 

switch.

C.   RUNNING TIME METER 

- This meter records the actual 

hours of engine operation.

D.   25 AMP FUSE

 - This fuse protect all the DC wiring in the 

engine control panel and on the engine.  If this Fuse if blown 

nothing will work on the engine.

E.  SAFETY LATCHING RELAY

 - This safety latching relay 

provides the 12 volt DC power to the fuel solenoid and the engine  

alternator field circuit during normal operation.  If the system 

experiences a low oil pressure fault or a high water temperature 

fault this relay will trip disconnecting the fuel solenoid and shutting 

down the engine.  When tripped the button on the panel will 

extend out about 1 inch.  This button must also be held in during 

starting until the check engine light goes out.  

INITIAL START UP 

   *************

*****  WARNING  *****

    ************* 

EQUIPMENT DAMAGE

 - 

DO NOT jump start these engine 

generator  sets. Starting these units on a low battery or 

jump starting them will cause damage to the engine control 

module.

Use the following check list to verify correct installation before 

starting the engine:

 

1.  Engine oil.  Fill as required with proper grade/qty.

 

2.  Engine coolant.  Fill as required with proper mixture.

 

3.  Unit mounting base properly bolted down.

 

4.  Clearance for service and maintenance on all sides.

 

5.  Proper fuel line material and size. 

 

6.  All fuel line connections tight.

 

7.  Battery connections clean and tight.

  

8.  Battery fully charged.

  

9.  All AC and DC wiring installed and properly protected.

After completing the above checklist, the engine-generator set is 

ready for the initial start-up test.

STARTING PROCEDURE

1.  Rotate start switch (A) to the preheat position and hold for 10 

seconds. NOTE:  

This step applies to the DE20 & DE30 ONLY.

2.    Rotate the Start Switch (A) to the Run position.  Then while 

depressing the Safety Latching Relay button (E) rotate the switch 

to the Start position.  At this point the starter should engage and 

the unit will start.

3.  As the unit starts release the Start Switch and it will return to 

the run position.  You must continue to depress the Safety Latch 

Relay button until the Check Engine light goes out.  When this 

light goes out, it indicates that the engine has built sufficient oil 

pressure to operate properly and the high coolant temperature 

has not been exceeded.  

Содержание WINPOWER DE20I4

Страница 1: ...INSTALLATION AND OPERATIONS MANUAL DE20I4 DE30I4 DE45I4 DE65I4 INSTALLATION AND OPERATIONS MANUAL MODELS DE20I4 DE30I4 DE45I4 DE65I4 DSE702 START MODULE AND MANUAL KEY START...

Страница 2: ...L NUMBER________________________ M Spec ______________________________ PURCHASE DATE_______________________ DEALER_______________________________ TABLE OF CONTENTS INTRODUCTION i GUIDE TO PRODUCT SAFE...

Страница 3: ...into the earth 2 FIRE HAZARD Diesel fuel presents a hazard of possible explosion and or fire a Do not smoke or use open flame near the generator set b Keep a fire extinguisher nearby and know its prop...

Страница 4: ...Muffler Standard Stop System Key Emergency Fuel Consumption full Load 2 6 Gal hour Owner Must Provide Fuel ASTM D 975 1D or 2D EN590 or equivalent See engine manual for additional fuel types specifica...

Страница 5: ...nd replacement parts Be sure to have the main WINPOWER unit data plate information recorded inside the front cover of this manual for future reference and for identification whenever requesting field...

Страница 6: ...hysical damage locate and check the following items packed with the unit a Owner s operators manual b Engine manufacturer s instruction manual c Battery hold down brackets hardware d Unit components o...

Страница 7: ...should be 1 1 2 time as large as the area of the radiator face to prevent back pressure In addition to a hot air discharge you must plan for a fresh air intake opposite the radiator discharge These fr...

Страница 8: ...tive ground system If you are using the truck batteries to start these units you may have to disable the charging system to keep it from interfering with the vehicle charging system Installation and s...

Страница 9: ...leted in accordance with the Nation Electric Code as well as any state or local codes You must pay particular attention to wire size requirement for the amperage of service you are dealing with The ta...

Страница 10: ...60708 151 2080 10 CONTROL BOX AC WIRING WARNING THESE GENERATORS ARE WIRED WITH A FLOATING NEUTRAL...

Страница 11: ...h to The lugs on the 65 kW will handle wire sizes 6 AWG to 300 MCM and should be torqued to 250 in lbs The lugs on the 20 through 45 kW will accommodate 10 AWG to 2 0 AWG and should be torqued to 200...

Страница 12: ...detects that the engine coolant temperature has exceeded the limit the coolant temperature switch after the Safety On timer has expired and a shutdown is initiated NOTE All warnings are reset but tur...

Страница 13: ...ours of engine operation D 25 AMP FUSE This fuse protect all the DC wiring in the engine control panel and on the engine If this Fuse if blown nothing will work on the engine E SAFETY LATCHING RELAY T...

Страница 14: ...nit stopped with the relay button popped out it could have been caused by either low oil pressure or high water temperature TROUBLESHOOTING TABLES ENGINE WILL NOT CRANK WITH GENERATOR RUN PUSH BUTTON...

Страница 15: ...2080 10 60708 151 13 DE30 OUTLINE DRAWING DE20 OUTLINE DRAWING...

Страница 16: ...60708 151 2080 10 14 DE45 DE60 OUTLINE DRAWING...

Страница 17: ...2080 10 60708 151 15 DE20 DE30 DC SCHEMATIC FOR DSE702...

Страница 18: ...60708 151 2080 10 16 DE45 DE65 DC SCHEMATIC FOR DSE702...

Страница 19: ...2080 10 60708 151 17 START CONTROL PANEL ENGINE WIRING HARNESS DE20 DE30 KEY START SCHMATIC...

Страница 20: ...60708 151 2080 10 18 START CONTROL PANEL ENGINE WIRING HARNESS DE45 DE65 KEY START SCHMATIC...

Страница 21: ...2080 10 60708 151 19 THREE PHASE AC WIRING HIGH AND LOW WYE...

Страница 22: ...60708 151 2080 10 20 THREE PHASE AC WIRING DELTA SINGLE PHASE AC WIRING...

Страница 23: ...of merchantability and fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINPOWER liable for incidental or consequent...

Страница 24: ...225 S Cordova ave Le Center MN 56057 507 357 6831 www winpowerinc com 60708 151 2080 10...

Отзывы: