DSE Model 5210 Automatic Start Engine Management and Instrumentation System Operators Manual
057-011 5210 OPERATING MANUAL ISSUE 5.1 18/06/2007 AM
37
14 FACTORY DEFAULT CONFIGURATION
In the tables below, the icon
#
indicates an item that can be adjusted from the module’s front panel editor.
Absence of the
#
icon beside an item means that adjustment of this parameter is only possible using the 5200
series configuration software in conjunction with the P810 interface.
For further details on adjustment from the front panel editor, see the section entitled “Front panel configuration”
elsewhere within this manual.
Module settings
Value
Base module
5210 remote start module
Miscellaneous settings
Value
Alternator fitted
Yes
Poles 4
Magnetic pickup fitted
No
AC System
3 phase, 4 wire
Enable fast loading feature
No
Number of start attempts
3
Input settings - Analogue
Value
Low oil pressure input type
VDO 10 bar
High coolant temp input type
VDO 120 degrees C
Trip
Return
Low oil pressure pre-alarm
#
1.17 Bar 17.0 PSI
1.24 Bar 18.0 PSI
Low oil pressure shutdown
#
1.03 Bar 14.9 PSI
N/A
High coolant temp pre-alarm
#
115°C 239°F
110°C 230°F
High coolant temp shutdown
#
120°C 248°F
N/A
Fuel level input type
VDO Ohm Range
Fuel pump control
No
Low fuel level
#
10%
Input settings - Digital
Value
1 Remote start
Close to activate
2 User configured
Close to activate, Indication Always active
3 User configured
Close to activate, Warning Active from safety on
4 User configured
Close to activate, Shutdown Always active
5 User configured
Close to activate, Shutdown Active from safety on
6 User configured
Close to activate, Electrical trip Always active
LCD indicator settings
Value
1 Lit
Remote start present
2 Lit
Digital input 2 active
3 Lit
System in auto mode
4 Lit
Common alarm
Output settings – Relay
Value
1 Energise
Preheat (during pre-heat timer)
2 Energise
Common alarm
3 Energise
Close generator