DSE Model 5210 Automatic Start Engine Management and Instrumentation System Operators Manual
057-011 5210 OPERATING MANUAL ISSUE 5.1 18/06/2007 AM
29
9.1.3 PLUG “D” 4 WAY (OPTIONAL)
PIN
No
DESCRIPTION
CABLE
SIZE
NOTES
23 RS485
port
Common
0.5mm Use only 120
Ω
RS485 approved cable
24 RS485
port
B
0.5mm Use only 120
Ω
RS485 approved cable
25 RS485
port
A
0.5mm Use only 120
Ω
RS485 approved cable
26 Not
connected
-
NOTE:- Connector E is not fitted to the 5210 remote start module.
9.1.4 PLUG “F” 4 WAY
PIN
No
DESCRIPTION
CABLE
SIZE
NOTES
35 Generator
L1
voltage
monitoring input
1.0mm
Connect to generator L1 output (AC)
(Recommend 2A fuse)
36 Generator
L2
voltage
monitoring input
1.0mm
Connect to generator L2 output (AC)
(Recommend 2A fuse)
37 Generator
L3
voltage
monitoring input
1.0mm
Connect to generator L3 output (AC)
(Recommend 2A fuse)
38 Generator
Neutral
input
1.0mm Connect to generator Neutral terminal (AC)
9.1.5 PLUG “G” 5 WAY
PIN
No
DESCRIPTION
CABLE
SIZE
NOTES
39
CT Secondary for L1
2.5mm
Connect to secondary of L1 monitoring CT
40
CT Secondary for L2
2.5mm
Connect to secondary of L2 monitoring CT
41
CT Secondary for L3
2.5mm
Connect to secondary of L3 monitoring CT
42
CT secondary common
2.5mm
Connect to secondary of all monitoring CT’s
43 Not
connected
-
9.1.6 PLUG “H” 4 WAY
PIN
No
DESCRIPTION
CABLE
SIZE
NOTES
44
Oil Pressure Input
0.5mm
Connect to Oil pressure sender
45 Coolant
Temperature
Input
0.5mm
Connect to Coolant Temperature sender
46
Fuel Level input
0.5mm
Connect to Fuel Level sender
47
Sender Common Return
0.5mm
Return feed for senders*.
NOTE*:- If using single terminal senders refer to connection diagram. If using earth return type
senders connect return terminals to pin 47 and also connect pin 47 to earth. This is detailed in the
Appendix section entitled “Sender wiring recommendations” elsewhere in this manual.
9.1.7 PC CONFIGURATION INTERFACE CONNECTOR
8-way connector allows connection to PC via the 810 configuration interface.
Module can then be re-configured utilising the
5200 series configuration
software.
9.1.8 EXPANSION
OUTPUT
CONNECTOR
The expansion connector allows connection to the 157 relay expansion module
or to the 548 LED Remote annunciator module.