DSE Model 5210 Automatic Start Engine Management and Instrumentation System Operators Manual
057-011 5210 OPERATING MANUAL ISSUE 5.1 18/06/2007 AM
39
Engine settings – Crank disconnect
Value
Crank disconnect on generator frequency
21.0 Hz
Crank disconnect oil pressure
<Disabled>
Check oil pressure prior to starting
Yes
Engine settings – speed
Value
Underspeed trip
#
1250 RPM
Underspeed prealarm
#
1350 RPM
Overspeed prealarm
#
1650 RPM
Overspeed trip
#
1750 RPM
Overspeed overshoot
0%
Plant battery settings
Trip
Return
Under volts warning
#
8.0 V DC
9.0 V DC
Over volts warning
#
33.0 V DC
32.0 V DC
Charge alternator warning
#
8.0 V DC
N/A
Exercise scheduler settings
Value
Enable exercise scheduler
No