DSC 3G4010 Скачать руководство пользователя страница 8

5

must be added to the 3G4010 current when determining the total draw on the host panel or 
power supply. Jumper CON5 does not limit the electrical current available on this output.

Tamper (12-13) -

 These terminals are connected in series to the Tamper switch [10]. They will close 

when the cabinet is properly closed, and will open when the front cover is removed.

Z1-Z4 (15-16-17-18) Programmable Inputs

 - These terminals can be set up to trigger events. Refer 

to ‘Inputs’ for details.

12V (19), COM (20) Device Power Supply

 - These terminals must be connected to a rated power 

supply.  Once the connections are completed, connect the battery leads (Red and Black wires, [12] in 
Figure 1) to a 12V, 7Ah battery.

Jumper CON5

CON5 ON

 - Full power, including standby capacity, comes from the host panel or external power 

supply. Supply must be capable of up to 700mA. The 3G4010 battery must 

not 

be connected.

CON5 OFF

 - Current limiting mode, the host panel or external supply provides standby current. 

Supply must be capable of 120mA plus any current drawn from AUX+ terminal. 3G4010 battery 
must be installed for proper operation.

Status LEDs

NOTE: The power supply must have a minimum voltage of 13.5V to ensure a sufficient battery 
charge. An example of a suitable power supply is the DSC Model ADP1310-NA with DC output 
rated 13.8 VDC, 1Amp. This is to be used in conjunction with a 12V/7Ah rated battery for UL/ULC 
listed residential installations.
NOTE: This mode of operation must not be used for ULC Listed Fire Monitoring installations.
NOTE: When disposing of batteries, follow the instructions and precautions printed on the bat-
teries, and contact your municipal offices for information on the disposal of used batteries.

The 3G4010 interface has four status LEDs. The following describes the control panel status LEDs.

NOTE: The top two LEDs blink during the Initializing and Programming phases.

 

RED

 - This LED is normally Off; but, it will flash in the event of a trouble. This LED will switch on 

within three minutes in the event of wireless Module [16] trouble, or when the wireless Network is 
unavailable, ‘No Service’. If this LED flashes, the following list indicates the specific trouble based on 
the number of flashes, by priority. When turned on, the 3G4010 checks for the trouble conditions to 
be restored in the order listed below. The 3G4010 indicates the status of the highest priority, 
unrestored trouble condition with the corresponding number of flashes of the red LED. Once the 
highest priority trouble condition has been cleared, the next highest priority trouble condition is 
displayed (if applicable).

1 flash 

- Battery Trouble (Battery with low voltage output)

2 flashes

 - Radio/SIM Trouble (Battery absent or SIM Card disconnected)

3 flashes 

- Wireless Network Problem (SIM not active, poor signal strength, antenna not connected)

4 flashes

 - Insufficient Signal Strength (poor location)

5 flashes

 - Connect 24 Configuration SMS Trouble (Improper VRU programming. Once the configu-

ration is ready, turn off power for 2-3 seconds to allow the unit to restart and request again)

6 flashes

 - Receiver not available (Improper VRU programming, receiver absent)

7 flashes

 - Power Supply Trouble (DC power supply absent)

Off

 - No Troubles

YELLOW

 - When this LED is On (solid), a Phone Line Trouble condition exists. This LED switches 

on when the interface switches to the Wireless Network (due to a Landline trouble condition). 
This LED flashes slowly in the event of an incoming or outgoing voice call (regardless of the 
operating status of the landline). This LED can also flash quickly once (Wireless TX) or twice 
(Wireless RX).

GREEN (Top) 

- When this LED is On, the reception is optimal. This LED switches On only when 

the other Green LED is on.

GREEN (Bottom)

 - If this LED is Off and the Red LED is On, the Wireless Network service is 

unavailable (NO SERVICE). This LED flashes when the Wireless Network reception is poor. If this 
LED is on, the 3G4010 is able to communicate with the 3G (HSPA) or 2G (GPRS) network.

Содержание 3G4010

Страница 1: ...CATOR INSTALLATION MANUAL V4 0 WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manu facturer The en...

Страница 2: ...10 4 Status LEDS 5 Operating Principles 6 Simulated Landline Mode 6 Panel Transmission Monitoring PTM 6 Wireless Communications Sequence 6 Inputs 6 Outputs 7 Activating the Outputs 7 Swinger Shutdown...

Страница 3: ...user to Not attempt to service this product Opening or removing covers may expose the user to dangerous voltages or other risks Any servicing shall be referred to trained service persons only Use aut...

Страница 4: ...upply rated for the application external power limited source NOTE The power supply must be Class 2 Power Limited For residential applications a suitable power adap tor is model DSC ADP1310 NAU for US...

Страница 5: ...ircuit boards Maintain at least 1 25 4mm separation A minimum 1 4 6 4mm of separation must be maintained at all points between Power Limited wiring and all other non Power Limited wiring Route wires a...

Страница 6: ...d as a sole means of communication supervision window of 200s required at monitoring station or as a back up when used in conjunction with a POTS line dialer The 3G4010 shall be powered from any compa...

Страница 7: ...OTE The green LEDs will indicate the signal strength The bottom green LED must be ON for the location to be acceptable Please refer to the Status LEDs section for more information 6 Power down the 3G4...

Страница 8: ...ED This LED is normally Off but it will flash in the event of a trouble This LED will switch on within three minutes in the event of wireless Module 16 trouble or when the wireless Network is unavaila...

Страница 9: ...ction sequence before switching The 3G4010 performs this sequence on any phone number that is detected on the line Specific central station phone numbers can be programmed into the 3G4010 if desired U...

Страница 10: ...he 3G4010 must be set as Active High NOTE Once an output has been activated automatically it will not restore its state until all the causes of activation are cleared Contact ID Events Description Eve...

Страница 11: ...panel or DC transformer to DC input backup battery if CON5 OFF Wiring Backup Incoming line to RING TIP on 3G4010 R 1 T 1 of 3G4010 to RING TIP of control panel R 1 T 1 of control panel to house phone...

Страница 12: ...means Trouble Status Trouble Status Troubleshooting Steps One Flash 3G4010 Low Battery Measure the battery under load and verify it is charged to at least 12 5 VDC If not wait at least 1 hour for the...

Страница 13: ...ion to verify that the 3G4010 programming is correct port IP address DNIS Contact your central station to verify they are not experiencing any receiver issues Seven Flashes DC Supply Trouble Ensure th...

Страница 14: ...control panel has the correct account num ber programmed Verify the reporting codes are programmed or the auto Contact ID option is enabled Ensure the control panel communicator is enabled Connect a h...

Страница 15: ...he lights will continue to flash in this sequence until the battery is charged above 12 4VDC Swinger Shutdown for Telephone Line Monitor TLM transmissions for backup units If the 3G4010 is configured...

Страница 16: ...ections are correct before turning on Connect relay contacts to a zone input on the alarm control panel for 3G4010 troubles supervision 24hr type zone Optional use of PGM output See Programming WARNIN...

Страница 17: ...tor NOTES 1 Program the Zone Point as Supervisory type with keypad only annunciation when in Alarm Do NOT use a point that is normally used for 2 Wire Smoke detectors 2 The power Supervision relay RM...

Страница 18: ...Control Unit Outputs Fire Supervisory Trouble DSC Subscribers Unit Fire Zone Inputs TIP TIP RING PGM1 DSC Keypad LCD4501 PK55XX 3G Wireless Transmitter 3G4010 T1 R1 TIP RING Zone Input PGM4 AUX Power...

Страница 19: ...TIP RING PGM1 DSC Keypad LCD4501 PK55XX 3G Wireless Transmitter 3G4010 T1 R1 PGM1 TIP RING Zone Input PGM4 AUX Power 12V 700mA RM1C ULC Relay PC5003C PC4050CR cabinet 3G HSPA 2G GPRS PSTN AC Input AC...

Страница 20: ...eless Network Supervision Relay Redundant Fire Alarm Transmission NOTE Use EOL resistor in series with N O contacts of the relay connected to PGM4 3 2 DC IN AUX 2 3 1 COM 4 1 COM T1 R1 TIP RING 4 PGM...

Страница 21: ...ork Supervision Relay Phone Line Supervision Relay and Redundant Fire Alarm Transmission NOTE Use EOL resistor in series with N O contacts of the relay connected to PGM4 5 6 KOhm 5 6 KOhm Wireless Net...

Страница 22: ...ees to the terms of this EULA If the SOFTWARE PRODUCT is an upgrade any transfer must also include all prior versions of the SOFTWARE PRODUCT f Termination Without prejudice to any other rights DSC ma...

Страница 23: ...AAAEQ TXXXX The digits represented by are the REN without a decimal point e g 03 is a REN of 0 3 For earlier products the REN is separately shown on the label Incidence of Harm If this equipment 3G401...

Страница 24: ...d damage from improper maintenance damage arising out of any other abuse mishandling or improper application of the products Items Not Covered by Warranty In addition to the items which void the Warra...

Отзывы: