NOTE: For UL/ULC installations, connections between alarm panel outputs and 3G4010 inputs must 
be run in protective mechanical conduits. To reduce interference with the antenna, it is recom-
mended that the metal conduit is not connected to the knock-outs in the top of the cabinet.

Outputs

The 3G4010 has four programmable outputs to activate in response to the associated events. Refer 
to the 3G4010 Wiring Diagram (Figure 2) at the back of this manual.

Activating the Outputs

The 3G4010 has four open collector outputs capable of a maximum of 50mA. Internal events on the 
3G4010 can trigger the outputs to turn on an LED or activate an input on the host panel. The default 
settings are as follows.

OUTPUT 1 Landline Trouble

 - Output is normally high and will switch to ground when the 

telephone line is down.

OUTPUT 2 Wireless Module or Network Trouble

 - Output is normally high and will switch to 

ground when the 3G4010 can not communicate with the 3G or 2G network.

OUTPUT 3 Power Supply or Battery Trouble

 - Output is normally high and will switch to ground 

when there is a problem with the power source.

OUTPUT 4 General Module Trouble

 - Output is normally low and will switch to high when a 

Wireless Network Trouble, Power Supply/Battery Trouble, and/or a Failure to Communicate (FTC) 
trouble is detected.

NOTE: PGM4 must be connected to the control panel as shown in Figure 4 (Residential appli-
cations) or Figures 8-9 (Commercial applications). Program the control panel input Zone/Point 
as 24hr ‘Supervisory’ with keypad-only notification when activated. Output 4 on the 3G4010 
must be set as ‘Active High’.
NOTE: Once an output has been activated automatically, it will not restore its state until all the 
causes of activation are cleared.

Contact ID

Events Description 

Event Codes

INPUT 1 ACTIVATION: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E110 FIRE ZONE 001 991
INPUT 1 RESTORAL: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .R110 FIRE ZONE 001 991
INPUT 2 ACTIVATION: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E120 PANIC ALARM ZONE 002 992
INPUT 2 RESTORAL: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R120 PANIC ALARM ZONE 002 992
INPUT 3 ACTIVATION: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  E130 BURGLARY ZONE 003 993
INPUT 3 RESTORAL: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R130 BURGLARY ZONE 003 993
INPUT 4 ACTIVATION: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E300 SYSTEM TROUBLE ZONE 004 994
INPUT 4 RESTORAL: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  R300 SYSTEM TROUBLE ZONE 004 994
PSTN LINE DOWN:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  E351 TELCO 1 FAULT 000
PSTN LINE RESTORAL: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R351 TELCO 1 FAULT 000
12V INPUT LOSS:  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E337 EXP. MOD. DC LOSS 000
12V INPUT RESTORAL: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  R337 EXP. MOD. DC LOSS 000
LOW BATTERY ALERT:  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E338 EXP. MOD. LOW BAT 000
LOW BATTERY RESTORAL: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R338 EXP. MOD. LOW BAT 000
PERIODIC REPORT: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E603 PERIODIC RF XMISSION 000
PERIODIC REPORT WITH OFF-NORMAL CONDITION:  . . .E608 PERIODIC TEST XMISSION SYSTEM TROUBLE PRESENT 000
3G UNIT ACTIVATION: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R552 RADIO XMITTER DISABLED 000
UNIT INTERNAL BUFFER FULL: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E624 EVENT LOG OVERFLOW 000
FTC RESTORAL:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R354 FAILURE TO COMMUNICATE 000

Swinger Shutdown

Swinger Shutdown is followed by a PSTN line trouble, limiting this event to a maximum of 3 trouble 
reports every 24 hours (including the PSTN line trouble sent when PTM is active). The condition will 
restore at midnight at which point the counter is reset.

Hardware Default

To perform a hardware default and force the unit to get the latest configuration from Connect 24, 
follow these steps:

• Power down the unit.
• Place a short between the PGM1 and Input 1 terminals.
• Power up the unit. This will perform a hardware default and request the configuration from 

Connect 24.

• Remove the short between PGM1 and Input 1.

Содержание 3G4010

Страница 1: ...CATOR INSTALLATION MANUAL V4 0 WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manu facturer The en...

Страница 2: ...10 4 Status LEDS 5 Operating Principles 6 Simulated Landline Mode 6 Panel Transmission Monitoring PTM 6 Wireless Communications Sequence 6 Inputs 6 Outputs 7 Activating the Outputs 7 Swinger Shutdown...

Страница 3: ...user to Not attempt to service this product Opening or removing covers may expose the user to dangerous voltages or other risks Any servicing shall be referred to trained service persons only Use aut...

Страница 4: ...upply rated for the application external power limited source NOTE The power supply must be Class 2 Power Limited For residential applications a suitable power adap tor is model DSC ADP1310 NAU for US...

Страница 5: ...ircuit boards Maintain at least 1 25 4mm separation A minimum 1 4 6 4mm of separation must be maintained at all points between Power Limited wiring and all other non Power Limited wiring Route wires a...

Страница 6: ...d as a sole means of communication supervision window of 200s required at monitoring station or as a back up when used in conjunction with a POTS line dialer The 3G4010 shall be powered from any compa...

Страница 7: ...OTE The green LEDs will indicate the signal strength The bottom green LED must be ON for the location to be acceptable Please refer to the Status LEDs section for more information 6 Power down the 3G4...

Страница 8: ...ED This LED is normally Off but it will flash in the event of a trouble This LED will switch on within three minutes in the event of wireless Module 16 trouble or when the wireless Network is unavaila...

Страница 9: ...ction sequence before switching The 3G4010 performs this sequence on any phone number that is detected on the line Specific central station phone numbers can be programmed into the 3G4010 if desired U...

Страница 10: ...he 3G4010 must be set as Active High NOTE Once an output has been activated automatically it will not restore its state until all the causes of activation are cleared Contact ID Events Description Eve...

Страница 11: ...panel or DC transformer to DC input backup battery if CON5 OFF Wiring Backup Incoming line to RING TIP on 3G4010 R 1 T 1 of 3G4010 to RING TIP of control panel R 1 T 1 of control panel to house phone...

Страница 12: ...means Trouble Status Trouble Status Troubleshooting Steps One Flash 3G4010 Low Battery Measure the battery under load and verify it is charged to at least 12 5 VDC If not wait at least 1 hour for the...

Страница 13: ...ion to verify that the 3G4010 programming is correct port IP address DNIS Contact your central station to verify they are not experiencing any receiver issues Seven Flashes DC Supply Trouble Ensure th...

Страница 14: ...control panel has the correct account num ber programmed Verify the reporting codes are programmed or the auto Contact ID option is enabled Ensure the control panel communicator is enabled Connect a h...

Страница 15: ...he lights will continue to flash in this sequence until the battery is charged above 12 4VDC Swinger Shutdown for Telephone Line Monitor TLM transmissions for backup units If the 3G4010 is configured...

Страница 16: ...ections are correct before turning on Connect relay contacts to a zone input on the alarm control panel for 3G4010 troubles supervision 24hr type zone Optional use of PGM output See Programming WARNIN...

Страница 17: ...tor NOTES 1 Program the Zone Point as Supervisory type with keypad only annunciation when in Alarm Do NOT use a point that is normally used for 2 Wire Smoke detectors 2 The power Supervision relay RM...

Страница 18: ...Control Unit Outputs Fire Supervisory Trouble DSC Subscribers Unit Fire Zone Inputs TIP TIP RING PGM1 DSC Keypad LCD4501 PK55XX 3G Wireless Transmitter 3G4010 T1 R1 TIP RING Zone Input PGM4 AUX Power...

Страница 19: ...TIP RING PGM1 DSC Keypad LCD4501 PK55XX 3G Wireless Transmitter 3G4010 T1 R1 PGM1 TIP RING Zone Input PGM4 AUX Power 12V 700mA RM1C ULC Relay PC5003C PC4050CR cabinet 3G HSPA 2G GPRS PSTN AC Input AC...

Страница 20: ...eless Network Supervision Relay Redundant Fire Alarm Transmission NOTE Use EOL resistor in series with N O contacts of the relay connected to PGM4 3 2 DC IN AUX 2 3 1 COM 4 1 COM T1 R1 TIP RING 4 PGM...

Страница 21: ...ork Supervision Relay Phone Line Supervision Relay and Redundant Fire Alarm Transmission NOTE Use EOL resistor in series with N O contacts of the relay connected to PGM4 5 6 KOhm 5 6 KOhm Wireless Net...

Страница 22: ...ees to the terms of this EULA If the SOFTWARE PRODUCT is an upgrade any transfer must also include all prior versions of the SOFTWARE PRODUCT f Termination Without prejudice to any other rights DSC ma...

Страница 23: ...AAAEQ TXXXX The digits represented by are the REN without a decimal point e g 03 is a REN of 0 3 For earlier products the REN is separately shown on the label Incidence of Harm If this equipment 3G401...

Страница 24: ...d damage from improper maintenance damage arising out of any other abuse mishandling or improper application of the products Items Not Covered by Warranty In addition to the items which void the Warra...

Отзывы: