3G4010 Wiring Diagrams
14
Figure 3 - Telephone Connection
RED (
R
)
G
REEN (
T
)
GR
A
Y
(
R
)
BRO
W
N (
T
)
RJ-31X
RIN
G
TI
P
CONTROL PANEL
Incomin
g
Phone line
Hand
s
et
RI
TI
T1
R1
TI
P
RIN
G
4
3
2
1
5
3G4010
TIP
T1 R1
RING
Figure 4 - Power Supply and Supervision Wiring Diagram
(BLK/WHT) +13.8VDC
(BLK ) GND
Control
Panel
EOL
Resistor
See Note 3
DSC
RM-2
RELA
Y
NC
C
NO
ZONE
TERMINALS
(See Note 1)
- +
+12VDC
GND
CONTROL PANEL
Aux Power
+ -
DSC
Supervision
Relay
See Note 2
17
16
15
14
12
18
13
11
10
9
7
8
6
19
Z4
Z3
Z2
COM
20
Z1
AUX
+
PGM
3
PGM
1
PGM
4
COM
3G4010
PGM
3
DC IN
+ -
DSC ADP1310-NAU
Power Adaptor
NOTES
1.
Program the Zone/Point as “Supervisory” type
with keypad only annunciation when in Alarm.
Do
NOT use a point that is normally used for
2-Wire Smoke detectors.
2.
The power Supervision relay,
RM-2
is only used
when the 3G4010 is
not
powered by the control
panel. When the Radio is powered by the control
panel the relay is not required since a loss of input
power will generate a signal to the CMC.
3.
Output 4 on the 3G4010 must be set as “Active
High” (default).
4.
When powering the 3G4010 Radio by an
Auxiliary Power supply that has its own backup
battery, insert CON5 jumper on the radio and
remove the 1.2AH battery that came with the radio.
The following wiring diagrams (Figures 5 to 8) are examples of ULC Listed Fire Monitoring Installation
connections.