3G4010 Wiring Diagrams

14

 Figure 3 - Telephone Connection

RED (

R

)

G

REEN (

T

)

GR
A

Y

 (

R

)

BRO

W

N (
T

)

RJ-31X

RIN

G

TI

P

CONTROL PANEL

Incomin

g

Phone line

Hand

s

et

  RI

TI

T1

R1

TI

P

RIN

G

4

3

2

1

5

3G4010

TIP

T1 R1

RING

 Figure 4 - Power Supply and Supervision Wiring Diagram

(BLK/WHT)  +13.8VDC

(BLK )  GND

Control

Panel 

EOL

Resistor

See Note 3

DSC

RM-2 

RELA

Y

NC

C

NO

ZONE 

TERMINALS
(See Note 1)

-    +

   

   

+12VDC

GND

CONTROL PANEL

Aux Power

+    - 

      

DSC 
Supervision 
Relay

See Note 2

17

16

15

14

12

18

13

11

10

9

7

8

6

19

Z4

Z3

Z2

COM

20

Z1

AUX

+

PGM

3

PGM

1

PGM

4

COM

3G4010

PGM

3

DC IN

+     -

DSC ADP1310-NAU

 

Power Adaptor

NOTES
1. 

Program the Zone/Point as “Supervisory” type 

with keypad only annunciation when in Alarm. 

Do 

NOT use a point that is normally used for 
2-Wire Smoke detectors.
2.

 The power Supervision relay, 

RM-2

 is only used 

when the 3G4010 is 

not 

powered by the control 

panel. When the Radio is powered by the control 
panel the relay is not required since a loss of input 
power will generate a signal to the CMC. 

3.

 Output 4 on the 3G4010 must be set as “Active 

High” (default).

4.

 When powering the 3G4010 Radio by an 

Auxiliary Power supply that has its own backup 
battery, insert CON5 jumper on the radio and 
remove the 1.2AH battery that came with the radio.

The following wiring diagrams (Figures 5 to 8) are examples of ULC Listed Fire Monitoring Installation 

connections.

Содержание 3G4010

Страница 1: ...CATOR INSTALLATION MANUAL V4 0 WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manu facturer The en...

Страница 2: ...10 4 Status LEDS 5 Operating Principles 6 Simulated Landline Mode 6 Panel Transmission Monitoring PTM 6 Wireless Communications Sequence 6 Inputs 6 Outputs 7 Activating the Outputs 7 Swinger Shutdown...

Страница 3: ...user to Not attempt to service this product Opening or removing covers may expose the user to dangerous voltages or other risks Any servicing shall be referred to trained service persons only Use aut...

Страница 4: ...upply rated for the application external power limited source NOTE The power supply must be Class 2 Power Limited For residential applications a suitable power adap tor is model DSC ADP1310 NAU for US...

Страница 5: ...ircuit boards Maintain at least 1 25 4mm separation A minimum 1 4 6 4mm of separation must be maintained at all points between Power Limited wiring and all other non Power Limited wiring Route wires a...

Страница 6: ...d as a sole means of communication supervision window of 200s required at monitoring station or as a back up when used in conjunction with a POTS line dialer The 3G4010 shall be powered from any compa...

Страница 7: ...OTE The green LEDs will indicate the signal strength The bottom green LED must be ON for the location to be acceptable Please refer to the Status LEDs section for more information 6 Power down the 3G4...

Страница 8: ...ED This LED is normally Off but it will flash in the event of a trouble This LED will switch on within three minutes in the event of wireless Module 16 trouble or when the wireless Network is unavaila...

Страница 9: ...ction sequence before switching The 3G4010 performs this sequence on any phone number that is detected on the line Specific central station phone numbers can be programmed into the 3G4010 if desired U...

Страница 10: ...he 3G4010 must be set as Active High NOTE Once an output has been activated automatically it will not restore its state until all the causes of activation are cleared Contact ID Events Description Eve...

Страница 11: ...panel or DC transformer to DC input backup battery if CON5 OFF Wiring Backup Incoming line to RING TIP on 3G4010 R 1 T 1 of 3G4010 to RING TIP of control panel R 1 T 1 of control panel to house phone...

Страница 12: ...means Trouble Status Trouble Status Troubleshooting Steps One Flash 3G4010 Low Battery Measure the battery under load and verify it is charged to at least 12 5 VDC If not wait at least 1 hour for the...

Страница 13: ...ion to verify that the 3G4010 programming is correct port IP address DNIS Contact your central station to verify they are not experiencing any receiver issues Seven Flashes DC Supply Trouble Ensure th...

Страница 14: ...control panel has the correct account num ber programmed Verify the reporting codes are programmed or the auto Contact ID option is enabled Ensure the control panel communicator is enabled Connect a h...

Страница 15: ...he lights will continue to flash in this sequence until the battery is charged above 12 4VDC Swinger Shutdown for Telephone Line Monitor TLM transmissions for backup units If the 3G4010 is configured...

Страница 16: ...ections are correct before turning on Connect relay contacts to a zone input on the alarm control panel for 3G4010 troubles supervision 24hr type zone Optional use of PGM output See Programming WARNIN...

Страница 17: ...tor NOTES 1 Program the Zone Point as Supervisory type with keypad only annunciation when in Alarm Do NOT use a point that is normally used for 2 Wire Smoke detectors 2 The power Supervision relay RM...

Страница 18: ...Control Unit Outputs Fire Supervisory Trouble DSC Subscribers Unit Fire Zone Inputs TIP TIP RING PGM1 DSC Keypad LCD4501 PK55XX 3G Wireless Transmitter 3G4010 T1 R1 TIP RING Zone Input PGM4 AUX Power...

Страница 19: ...TIP RING PGM1 DSC Keypad LCD4501 PK55XX 3G Wireless Transmitter 3G4010 T1 R1 PGM1 TIP RING Zone Input PGM4 AUX Power 12V 700mA RM1C ULC Relay PC5003C PC4050CR cabinet 3G HSPA 2G GPRS PSTN AC Input AC...

Страница 20: ...eless Network Supervision Relay Redundant Fire Alarm Transmission NOTE Use EOL resistor in series with N O contacts of the relay connected to PGM4 3 2 DC IN AUX 2 3 1 COM 4 1 COM T1 R1 TIP RING 4 PGM...

Страница 21: ...ork Supervision Relay Phone Line Supervision Relay and Redundant Fire Alarm Transmission NOTE Use EOL resistor in series with N O contacts of the relay connected to PGM4 5 6 KOhm 5 6 KOhm Wireless Net...

Страница 22: ...ees to the terms of this EULA If the SOFTWARE PRODUCT is an upgrade any transfer must also include all prior versions of the SOFTWARE PRODUCT f Termination Without prejudice to any other rights DSC ma...

Страница 23: ...AAAEQ TXXXX The digits represented by are the REN without a decimal point e g 03 is a REN of 0 3 For earlier products the REN is separately shown on the label Incidence of Harm If this equipment 3G401...

Страница 24: ...d damage from improper maintenance damage arising out of any other abuse mishandling or improper application of the products Items Not Covered by Warranty In addition to the items which void the Warra...

Отзывы: