Operation
M o d b u s , B A C n e t , L o n Ta l k
i n t e r o p e r a b i l i t y
Table 67-1:
Interoperability variable and object names (continued)
Variable name and
BACnet object name
Read Only
(RO) or
Read Write
(RW)
Modbus
register
number*
BACnet
Object
Type and
Instance
LonTalk variable
names**
Description
Units
Range
I-P
units
SI units
I-P units
SI units
Read-only digital I/O
Airflow_proving_switch
RO
DI-1
BI-01
nvoAirflowSwitch
0=Open; 1=Closed
--
--
--
--
Duct_HL_switch
RO
DI-2
BI-02
nvoDuctHLswitch
0=Open; 1=Closed
Safety_interlock
RO
DI-3
BI-03
nvoSafetyI-lock
0=Open; 1=Closed
Combustion_air_damper_
(GTS)
RO
DI-4
BI-04
nvoCombustAirDmp
0=Damper Closed;
1=Damper Open
Flue_pressure_switch_(GTS)
RO
DI-5
BI-05
nvoFluePressurSw
0=Open; 1=Closed
Power_vent_switch_(GTS)
RO
DI-6
BI-06
nvoPowerVentSwch
0=Vent Off; 1=Vent On
Low_water_sensor_ (GTS)
RO
DI-7
BI-07
nvoLowWaterSensr
0=No Water; 1=Water
Fill_valve
RO
DI-8
BO-01
nvoFillValve
0=Closed; 1=Open
Drain_valve
RO
DI-9
BO-02
nvoDrainValve
0=Not Draining;
1=Draining
Faults and alarms
Active_messages_exist
RO
DV-1
BV-01
nvoMessages
Flags all active messages
--
--
--
--
Active_auto_cleared_alarms_
exist
RO
DV-2
BV-02
nvoAlarms1
Flags all auto-cleared
alarms
Active_manually_cleared_
alarms_exist
RO
DV-3
BV-03
nvoAlarms2
Flags all manually
cleared alarms
Clear_all_faults
RW
DV-4
BV-04
nviClearAllFaults
When set will clear all
active faults
Alarm_tank_temp_sensor_
failed
RW
DV-5
BV-05
nvoAlrmTnkTmpSen
See Alarms menu.
Alarm_tank_overtemp
RW
DV-6
BV-06
nvoAlrmOvertemp
See Alarms menu.
Alarm_RH_signal_out_of_
range
RW
DV-7
BV-07
nvoAlrmRHsignal
See Alarms menu.
Alarm_dew_pt_sig_out_of_
range
nvoAlrmDewPtSgnl
See Alarms menu.
Alarm_demand_sig_out_
of_range
nvoAlrmDemndSgnl
See Alarms menu.
Alarm_duct_RH_sig_out_
of_range
RW
DV-8
BV-08
nvoAlrmDuctRHsig
See Alarms menu.
Alarm_aux_temp_sens_out_
of_rnge
RW
DV-9
BV-09
nvoAlrmAuxTemp
See Alarms menu.
Alarm_water_probe_
miswired
RW
DV-10
BV-10
nvoAlrmProbeWire
See Alarms menu.
Alarm_water_probe_failed
RW
DV-11
BV-11
nvoAlrmProbeFail
See Alarms menu.
*
See note 1 on Page 69.
** See note 2 on Page 69.
More on the next page >