Operation
Automatic drain sequence for potable water (not softened)
When configured to run a potable water humidifier with an
automatic drain valve, Vapor-logic4 uses an automatic drain
sequence (ADS) to reduce mineral accumulation in the tank and
drain line, which decreases tank maintenance.
The automatic drain sequence starts by opening the drain valve to
empty the tank. When the drain duration ends, the fill and drain
valves remain open to flush the tank. When the flush duration
ends, the automatic drain sequence is complete and the humidifier
resumes normal operation. The default drain and flush durations
are model-specific and can be adjusted in the water management
section of the Setup menu.
Automatic draining and flushing parameters are defined in the
water management section of the Setup menu. First, automatic
draining and flushing must be enabled. Second, the amount of
water converted to steam before an automatic drain sequence
begins must be defined (Usage). Defaults for this value are model-
specific, and are calculated based on operating 200 hours at 100%
of capacity. Go to the Setup menu to view or change this setting for
your humidifier. Third, days of the week when the automatic drain
sequence can occur must be defined. This means that once the
Usage requirement is met, the automatic drain sequence can occur
on the first allowed day (allowed days default is all days). Last, time
of day when the automatic drain sequence occurs must be defined
(default value is midnight).
For example, if you use factory default settings for the automatic
drain sequence, the first automatic drain sequence will occur at
midnight on any day of the week once the model-specific usage
requirement has been met. If you want to change these settings, go
to the water management section of the Setup menu.
Note that the automatic drain sequence is designed for a standard
water system with electric drain and fill valves. Humidifiers using
DI/RO water do not require automatic draining and flushing, but
this feature can be enabled if the humidifier has electric drain and
fill valves.