Installation
I n s t a l l a t i o n : S e t u p
Table 27-1:
Setup menu (continued)
Menu item
Default
value
Minimum
value
Maximum
value
Units
Notes
Limit control
Airflow switch
--
--
--
--
Switch in system
:FT
No
:FT
--
HL switch
--
--
--
--
Switch in system
:FT
No
:FT
--
HL transmitter
--
--
--
--
Transmitter
enabled
No
No
:FT
--
Duct HL set point
80
5
95
% RH
Duct HL span
5
0
20
% RH
Span (throttle span) is an offset below the high limit set
point where the humidifier reduces output but does not
turn off until the device high limit set point is reached.
Duct HL offset
0
-20
20
% RH
Water type
Potable enabled
--
No
:FT
--
CAUTION!
Changing the water type setting from
potable or softened to DI/RO, or from DI/RO to potable
or softened requires humidifier hardware changes.
Softened enabled
--
No
:FT
--
DI/RO enabled
--
No
:FT
--
Note:
:PVSTZTUFNNBZOPUIBWFBMMPGUIFTFQBSBNFUFST
More on the next page >