Operation
M o d b u s , B A C n e t , L o n Ta l k
i n t e r o p e r a b i l i t y
Table 66-1:
Interoperability variable and object names (continued)
Variable name and
BACnet object name
Read Only
(RO) or
Read Write
(RW)
Modbus
register
number*
BACnet
Object
Type and
Instance
LonTalk variable
names**
Description
Units
Range
I-P
units
SI units
I-P units
SI units
Setup variables
Run_mode
Write
HR-1
MSV-01
nviRunMode
Set the current mode of
the unit or system. The
defined options are:
1 Auto
2 Local standby
3 System standby
4 Manual drain
--
--
1 to 4
1 to 4
Read
HR-1
MSV-01
nvoRunMode
Read the current mode of
the unit or system. The
defined options are:
1 Auto
2 Local standby
3 System standby
4 Manual drain
5 Test outputs
6 Test run
--
--
1 to 6
1 to 6
Space_RH_set_point
Write
HR-2
AV-05
nviSpaceRHsetPt
Set or read the humidity
set point for the space
being humidified.
%
%
0 to 100
0 to 100
Read
HR-2
AV-05
nvoSpaceRHsetPt
%
%
0 to 100
0 to 100
Space_dew_point_set_point
Write
HR-3
AV-06
nviSpaceDewPtSP
Set or read the dew point
set point for the space
being humidified.
ºF
ºC
20 to 80
-6 to 26
Read
HR-3
AV-06
nvoSpaceDewPtSP
ºF
ºC
20 to 80
-6 to 26
Duct_high_limit_set_point
Write
HR-4
AV-07
nviDuctHLsetPt
Set or read the duct high
limit set point.
%
%
0 to 100
0 to 100
Read
HR-4
AV-07
nvoDuctHLsetPt
%
%
0 to 100
0 to 100
Fieldbus_demand_mass
Write Only
HR-5
AV-08
nviFbusDemndMass
Set the steam output
(as demanded via the
fieldbus) as a percentage
of the humidifier’s total
capacity.
lbs/hr
kg/h
0 to
100,000
0 to
100,000
Fieldbus_demand_%
Write Only
HR-6
AV-09
nviFldBusDemand%
Set the steam output (as
demanded via fieldbus)
in pounds or kilograms
per hour. If the request
exceeds the unit’s
capacity, the unit will run
at 100% capacity.
%
%
0 to 100
0 to 100
PID_band
RW
HR-7
AV-10
nciPIDband
Set the PID band.
%
%
0 to 50
0 to 50
PID-Kp
RW
HR-8
AV-11
nciPIDkp
Set the PID-Kp
(proportional gain)
factor.
--
--
0 to 1000
0 to 1000
PID-Ki
RW
HR-9
AV-12
nciPIDki
Set the PID-Ki (integral
gain) factor.
--
--
0 to 1000
0 to 1000
PID-Kd
RW
HR-10
AV-13
nciPIDkd
Set the PID-Kp
(derivative gain) factor.
--
--
0 to 1000
0 to 1000
*
See note 1 on Page 69.
** See note 2 on Page 69.
More on the next page >