1BHF t %3*45&&. 7BQPSMPHJD *OTUBMMBUJPO BOE 0QFSBUJPO .BOVBM
Installation
I n s t a l l a t i o n : S e t u p
Table 30-1:
Setup menu (continued)
Menu item
Default
value
Minimum
value
Maximum
value
Units
Notes
Remote temp sensor
CAUTION!
Changing temperature sensor settings
can require component changes for system to operate
correctly.
Temp compensation
--
--
--
--
Temp comp enabled
--
No
:FT
--
Temp monitor
--
--
--
--
Temp monitor enabled
--
No
:FT
--
Temp sensor offset
--
--
--
--
Used to calibrate temperature monitoring sensor and
temperature compensation sensor
Temp sensor offset
0
-20
20
°F
0
-11
11
°C
Communications
CAUTION!
Changing communications settings can
require component changes for system to operate
correctly.
BACnet
--
--
--
--
BACnet
enabled
--
No
:FT
--
BACnet baud rate
38400
9600
76800
--
BACnet
address
99
0
255
--
Modbus
--
--
--
--
Modbus
enabled
--
No
:FT
--
Modbus baud rate
9600
4800
38400
--
Modbus
address
99
0
255
--
LonTalk
--
--
--
--
LonTalk
enabled
--
No
:FT
--
Network IP address
--
--
--
--
Network IP address
192.168.1.195
192.168.1.195
255.255.
255.255
--
Enable
DHCP
No
No
:FT
--
Use keypad/display to access this menu item. This item
is not available when using the Web interface.
Note:
:PVSTZTUFNNBZOPUIBWFBMMPGUIFTFQBSBNFUFST