4-15
CH 4/ Instrument Settings
Factory default
settings
Dranetz has set the default values for the various parameters of the 4400.
Current Probes:
TR2500/TR2500A for A, B, C; TR2510/TR2510A for D
Scale Factors:
1:1 for V and I, channels A, B, C, D
Circuit Type:
three phase wye
Mode of Operation:
monitor
Nominal Value:
measured V, I, frequency
Monitoring Mode:
Standard Power Quality
Advanced Operations:
individual limit setups
Transient Limits:
intantaneous peak = 3X nominal V, waveshape = 10% ,
rms dev = 10%
RMS Variation Limits:
10% Very Low, 90% Low, 110% High for voltage; none for
current
Journal Limit:
journalling By Time for the various parameters
Triggers:
all V trigger; all V and I channels
Journal Interval
Power Values:
Power Values Interval:
15 minutes
Waveform Snapshot:
On
Demand and Energy:
Demand Sub-Interval:
5 minutes
Sub-Intervals per Interval: 3
Harmonics Journal Interval:
15 minutes
Flicker:
Pst (Short Term) Interval:
10 minutes
Plt (Long Term) Interval:
2 hours
Site Name:
PowerGuide Site
Clock Type:
Analog
Date:
mm/dd/yy
Language:
English
Display
Backlight Timer:
1 minute
Contrast:
70%
Password Protect:
OFF
www.
.com
1.800.561.8187
Содержание PowerGuide 4400
Страница 13: ...xiii Dranetz PowerGuide 4400 www com information itm com 1 800 561 8187 ...
Страница 14: ...xiv www com information itm com 1 800 561 8187 ...
Страница 78: ...4 16 www com information itm com 1 800 561 8187 ...
Страница 136: ...6 22 www com information itm com 1 800 561 8187 ...
Страница 158: ...7 22 www com information itm com 1 800 561 8187 ...
Страница 196: ...9 16 www com information itm com 1 800 561 8187 ...
Страница 206: ...A 10 www com information itm com 1 800 561 8187 ...
Страница 226: ...C 8 www com information itm com 1 800 561 8187 ...
Страница 228: ...D 2 www com information itm com 1 800 561 8187 ...
Страница 252: ...F 4 www com information itm com 1 800 561 8187 ...
Страница 262: ...MARK201 LEVEL 200 Scope Mode MARK202 MARK205 G 9 www com information itm com 1 800 561 8187 ...
Страница 272: ...MARK112b LEVEL 112_701 Advanced Options EN50160 Options MARK112c G 19 www com information itm com 1 800 561 8187 ...