7-21
CH 7/ View Event Data
RMS settings
The 4400 provides setup options to measure rms data per cycle or per second.
The RMS Voltage and RMS Current parameters are available under Journal Categories
- Standard List.
Cyclic RMS:
RMS values are computed over 1 power frequency cycle (16.67 msec @
60 Hz) in 1/2 cycle steps (every 8.33 msec). The min/max/avg of these cyclic values
are continually updated and saved every user-programmed journal interval (see Chapter
6 Advanced Setup Options - Journal Interval for Timed Readings on page 6-21).
1-Sec RMS:
Similar to cyclic rms, except that each rms value is computed over 1
second’s worth of data points (which is 1/60th of a second @ 60 Hz), rather than over 1
cycle.
NOTE: Data for Cyclic or 1-Sec sampling rates apply only to rms parameters.
MARK436
MARK514
www.
.com
1.800.561.8187
Содержание PowerGuide 4400
Страница 13: ...xiii Dranetz PowerGuide 4400 www com information itm com 1 800 561 8187 ...
Страница 14: ...xiv www com information itm com 1 800 561 8187 ...
Страница 78: ...4 16 www com information itm com 1 800 561 8187 ...
Страница 136: ...6 22 www com information itm com 1 800 561 8187 ...
Страница 158: ...7 22 www com information itm com 1 800 561 8187 ...
Страница 196: ...9 16 www com information itm com 1 800 561 8187 ...
Страница 206: ...A 10 www com information itm com 1 800 561 8187 ...
Страница 226: ...C 8 www com information itm com 1 800 561 8187 ...
Страница 228: ...D 2 www com information itm com 1 800 561 8187 ...
Страница 252: ...F 4 www com information itm com 1 800 561 8187 ...
Страница 262: ...MARK201 LEVEL 200 Scope Mode MARK202 MARK205 G 9 www com information itm com 1 800 561 8187 ...
Страница 272: ...MARK112b LEVEL 112_701 Advanced Options EN50160 Options MARK112c G 19 www com information itm com 1 800 561 8187 ...