Start-Up
44
Central Controller REGARD Ex:
●
By means of the menu
»04-8 SETI«
adjust sensor current depending on the sen-
sor used to the following values:
Sensing head Polytron SE Ex PR M and SE Ex HT M:
– for Methane detection: 270 mA
– for the detection of other gases and vapours (see page 50): 240 mA
Sensing head Polytron SE Ex LC M: 276 mA
●
Please refer to the Instructions for Use REGARD Ex.
Calibrating the Sensing Head Polytron SE Ex
To achieve the state of thermal balance, the sensing head needs to be in operation
for at least 10 minutes (warm-up time) before starting the calibration procedure.
Zero adjustment
Without calibration adapter:
●
Make sure that the sensing head is in clean air (free of combustible gases and va-
pours),
or, with calibration adapter:
●
Apply zero gas (clean air or nitrogen) to the sensor via calibration adapter, flow
rate approx. 0.5 L/min.
Central Controller Polytron SE Ex:
1,2
For channel modules without analogue indicator or with bar graph display con-
nect voltmeter (R
i
≥
1 M
Ω
) to the sockets.
Sensing head Polytron SE Ex PR M and SE Ex HT M: 0 to 4.7 V correspond to a
measuring range of 0 to 100 %LEL; so 1 %LEL correspond to 47 mV.
Sensing head Polytron SE Ex LC M: 0 to 4.7 V correspond to a measuring range
of 0 to 10 %LEL; so 1 %LEL correspond to 470 mV.
3
Use zero potentiometer to set indicator to 0 %LEL (0 mV at voltmeter).
Central Controller REGARD Ex:
●
By means of menu
»10-0 ZERO«
set zero signal.
Please refer to the Instructions for Use REGARD Ex.
0082344
7_06.eps
mV
=
3
1
2