84
Technical Manual
|
Dräger Polytron
®
8000 Series
Factory default settings
15.3.3 Polytron
®
8200 CAT DrägerSensor
®
DQ
15.3.4 Polytron
®
8200 CAT DrägerSensor
®
LC
15.3.5
Sensor range catalytic bead (CatEx) sensors
Default alarm values for all CatEx sensors are the same.
Menu
Default setting
Range
A1 Alarm
20 % LEL
1 to 100 %LEL
A2 Alarm
40 % LEL
Hysteresis for A1
alarm at direc-
tion rising
1 % LEL
0 to A1
Hysteresis for A2
alarm at direc-
tion rising
1 % LEL
0 to A2
Calibration inter-
val [days]
180
0 to 360
Display capture
offset
0 % LEL
-5 to 4 %LEL
Display capture
low
-5 % LEL
-5 to 0 %LEL
Display capture
high
2 %LEL
0 to 4 %LEL
Full scale deflec-
tion
100 %LEL
Range is not adjustable
Menu
Default setting
Range
A1 Alarm
2.0 % LEL
0.1 to 10 % LEL
A2 Alarm
4.0 % LEL
Hysteresis for A1
alarm at direc-
tion rising
0.1 % LEL
0 to A1
Hysteresis for A2
alarm at direc-
tion rising
0.1 % LEL
0 to A2
Full scale deflec-
tion
10 % LEL
5 to 10
1)
% LEL
1 to 10 % LEL
1) For firmware versions < 3.0.0
Calibration inter-
val [days]
180
0 to 360
Display capture
offset
0 % LEL
-0.5 to 0.4 % LEL
Display capture
low
-0.5 % LEL
-0.5 to 0 % LEL
Display capture
high
0.2 %LEL
0 to 0.4 % LEL